In D:CutOff
(
In Door Day
Temperature
Cutoff)
The controller closes the valve completely when the In Door temperature average (supplied from
host computer) is higher than this set point during the Day - time between Day Begin and Day
End (
D:ICOFF
state). Range: 40 to 90 °F
In N:CutOff
(In Door Night
Temperature
Cutoff)
If the In Door temperature average (supplied from host computer) is higher than this set point
and the time is between Day End and Day Begin, then the valve will be closed completely
(
N:ICOFF
state). Range: 40 to 80 °F
D_Band
Used along with ‘In Door Temperature’ parameter and ‘In Door Day/Night Temperature Cutoff’ Set
Point. This parameter defines the allowable delta between the actual In Door Temperature and
Cutoff Set Point.
Range: 0.1°F to 19.9°F with 0.1°F steps
Day Begin
Hours and minutes (with 10 minutes step) when Day Begins
Day End
Hours and minutes (with 10 minutes step) when Day Ends
WinterBegin
Month and Day when Winter Begin (dependent of the region)
WinterEnd
Month and Day when Winter End (dependent of the region)
Cycle Span
Heating cycle period, minutes.
Range: 20 to 90 minutes, Step 10minutes. Default value is 60 minutes
Heat Limit
This parameter overrides the system calculated ‘ON’ period if ‘ON’ bigger than ‘Hit Limit’
Default value is 100%.
Motor Type
Motorized valve nominal timing (in seconds) for 90° or 160° stroke.
Range:{15,30,45,60,72,90,144,180,240}seconds. Default = 30seconds.
HeatUpStp
New cycle will comment when the system temperature on the Cold Pipe Temperature Sensor
reaches this set point (please see diagram on Figures 5-7, red line).
Range: 40 to 240°F, Step 1°F Default value is 125°F
CoolDwnStp
Heating can start if the system temperature drops below this set point (checks each time after
current cycle finished). (please see diagram on Figures 5-7, blow line).
Range: 40 to 240°F, Step 1°F Default value is 120°F
HeatUpTm
Controller can start new cycle either SYSTemp > HeatUpSP or HeatUpTm is expired.
Range: 0 to 90 minutes, Step 1minute. Default value is 5minutes.
CoolDwnTm
Heating can start
either
SYSTemp < CoolDwnStp or CoolDwnTm is expired.
Range: 0 to 90 minutes, Step 1minute. Default value is 5minutes.
TIME & DATE
The submenus of this setting allow setting up the internal real time clock of the controller. It is
essential to have the clock set properly, because the Boost, Night Saving modes and Daylight
Saving Time Adjust rely on the clocks accurate setting.
CALIBRATE
Submenu for Calibration of Temperature and Pressure Sensors. Uses to calibrate a current for
motorized valve. (Please see chapter #10)
Com.ID
Each OPLC-2100 connected to the local server via the RS485 bus. To establish proper connection
the controller should have a unique communication address (ID).
Range: 1 to 99.