TECHNICAL DOCUMENTATION

12

P

r

e

l

iminar

y

www.inpower-sys.com 

  

                           1IPSE1A33-60

LED D

IAGNOSTICS

11. 

The system status during normal operation or fault is indicated by eight LEDs. All LEDs are on the driver 
board.

The LEDs indicate the following conditions:

LED

Description

Switch

D 15

no light: 

the driver is receiving switch OFF signal

red light: 

the driver is receiving switch ON signal

is blinking: 

input fi lter detected problem with input switching signal, i.e. too high

 

 

frequency, second switching pulse very close to the fi rst one or 

                              incorrect delay between two pulses

U sat - 1

D 16

no light: 

system is working in nominal operation

red light: 

U sat – 1 protection was operating

U sat - 2

D 17

no light: 

system is working in nominal operation

red light: 

U sat – 2 protection was operating

U sat - 3

D 18

no light: 

system is working in nominal operation

red light: 

U sat – 3  protection was operating

U sat – 4

D 19

no light: 

system is working in nominal operation

red light: 

U sat – 4 protection was operating

di/dt

D 1

no light: 

system is working in nominal operation

red light: 

di/dt protection was operating

Reset

D 14

no light: 

system is working in nominal operation

red light: 

reset of the driver or secondary voltage is below 11V

Voltage 
supply

D 20 no light: 

secondary supply voltage is missing

green light: 

system is working in nominal operation

The failure indications are illuminated until the driver is reset (switch-off  of the driver power supply).

Содержание 1IPSE1A33-60

Страница 1: ...E1A33 60 FOR MEDIUM AND HIGH POWER IGBTS M A N U A L InPower Systems GmbH Am Kornfeld 11 D 86932 P rgen Germany Tel 49 0 8196 93000 Fax 49 0 8196 930020 Email info inpower sys com VAT Id DE 221021830...

Страница 2: ...m i n a r y 2 TABLE OF CONTENTS 1 SAFETY NOTICE 3 2 HANDLING AND MOUNTING ADVICES 4 3 MAIN FEATURES 5 4 MECHANICAL DIMENSIONS 5 5 KEY DATA 6 6 INTERFACES 6 7 COMMISSIONING SUPPORT 7 8 INPUTS AND OUTPU...

Страница 3: ...te handling or transport Contact while uninstalled is permitted only with ESD protection Install only without supply voltage Use only suitable electronic devices Always keep sufficient safety distance...

Страница 4: ...not exceed 30cm Max length of simple cable should not exceed 7cm For the gate and auxiliary emitter connections it is recommended to use coaxial cable RG58 C U with auxiliary emitter connected to the...

Страница 5: ...er current in all short circuit conditions over voltage during turn off Advanced control and protection functions four level desaturation monitoring two level di dt monitoring feedback clamping with a...

Страница 6: ...rage temperature TST 40 to 85 C Input driving and output error signal optical 660nm Turn on delay time tpdON 400nsec Turn off delay time tpdOFF 400nsec Typical time of soft shut down tSSD 1 2 sec Max...

Страница 7: ...n the DC low voltage supply for the driver Make sure that there is no strange noise smell heat or otherwise originating from the driver The voltage supply LEDs should now light up green which means th...

Страница 8: ...capture the input and output signals on the oscilloscope and save the images If all is well you have got the system working correctly If something does not seem right stop the test straight away and c...

Страница 9: ...nting holes for M4 screws It is possible to use plastic or metal screws Mounting holes have different potentials The auxiliary adaptation board is including an addi tional gate capacitor C3 C2 or C1 i...

Страница 10: ...le connector Driver with cable connector Max length of coaxial cable 40cm For gate and auxiliary emitter connections use coaxial cable RG58 C U with auxiliary emitter connected to the shielding For po...

Страница 11: ...ons use coaxial cable RG58 C U with auxiliary emitter connected to the shielding For power emitter and auxiliary collector it is recommended to use HV isolation cable for instance Radox 9 GKW AX 1 5mm...

Страница 12: ...minal operation red light U sat 1 protection was operating U sat 2 D 17 no light system is working in nominal operation red light U sat 2 protection was operating U sat 3 D 18 no light system is worki...

Страница 13: ...e described hardware has been checked Discrepancies may exist nevertheless no guaranty is assumed for total congruence The information contained in this document is subject to regular revision Any alt...

Отзывы: