The temperature information from the NTC inside the heating rob(measuring the radiator
temperature) and the NTC at the main power cable outlet(measuring the room temperature)
are used to ensure correct operation of the radiator,regulated by the control unit.If the
automatic control system is faulty for whatever reason and the water temperature in the
radiator is increasing in an uncontrolled manner,the system has two safety mechanisms to
prevent excessive pressure in the radiator.Firstly,the entire system is completed shut down
electronically when a water temperature of 95°C is reached. If this protection mechanism
fails for whatever reason,a simple downstream thermal fuse ensures complete shut-down,and
the heating rob dies.
6.2 Room temperature compensation
As the NTC that measures the room temperature and feeds back information to the
controller is located on the back of the controller,it is close to the warm radiator. The
measured temperature will therefore not accurately reflect the temperature in other part of the
room.For this reason,there is an automatic temperature adjustment of -3°C in the control unit.
6.3 Open window/door detection
This automatic function detects when the temperature falls by 2°C or more over a short
period of time without any changes having been made to the control unit temperature setting.
In this case,the system assumes that this reduced temperature is due to opened windows or
doors, “
OP
” will be displayed on the controller unit .
In order to save energy,the radiator heating system is switched off automatically where
the heating system was in operation at the time. And it will be active to heat automatically
again once the temperature is detected in stable condition.