Inovonics EN1215EOL Скачать руководство пользователя страница 2

8/22/19 357-05042-02 Rev A © Inovonics, 2019 - www.inovonics.com

2.5 Mount the EN1215EOL

1.

Route the external wiring through the wall, as shown in 

Figure 4.

2.

Mount the transmitter to the wall using the wall-mount screw 

holes, ensuring the housing is flush against the wall and the 

wall tamper switch is firmly depressed.

 Figure 4  

Mount the transmitter to the wall

3.

Close the housing.

4.

Secure the housing through the enclosed housing screw 

hole. Accessing this screw on an active transmitter requires 

opening the housing and removing the battery, causing a 

tamper condition.

3 Specifications

Note: 

The 2.2K ohm resistor is required to operate the 

EN1215EOL.
External contacts: N/O or N/C.

Distance, external contact to EN1215EOL: 10 feet (3 meters) 

maximum.

Power requirement: 3 VDC, 60 mA.

Typical battery life: 3-5 years.

Battery type (BAT604): Panasonic CR123A.

Operating environment: 0 to 60°C (32 to 140°F), 90% relative 

humidity, noncondensing; 0 to 49°C (32 to 120°F) for UL 

installations.

UL listings: UL 365, UL 1023, ULC/ORD-C1023-74, UL 1076, UL 

1610.

Compatible UL receiver: EN4216MR, EN4232MR, EN7285.

Note: 

Inovonics supports recycling and reuse whenever 

possible. Please recycle these parts using a certified electronics 

recycler.

Note: 

Specifications and data are subject to change without 

notice.

4 Television and Radio Interference

This equipment has been tested and found to comply with the 

limits for a Class B digital device, pursuant to Part 15 of the FCC 

Rules. These limits are designed to provide reasonable 

protection against harmful interference in a residential 

installation. This equipment generates, uses and can radiate 

radio frequency energy and, if not installed and used in 

accordance with the instructions, may cause harmful 

interference to radio communications. However, there is no 

guarantee that interference will not occur in a particular 

installation. If this equipment does cause harmful interference to 

radio or television reception, which can be determined by turning 

the equipment off and on, the user is encouraged to try to correct 

the interference by one or more of the following measures:

• Reorient or relocate the receiving antenna.

• Increase the separation between the equipment and 

receiver.

• Connect the equipment into an outlet on a circuit different 

from that to which the receiver is connected.

• Consult the dealer or an experienced radio/TV technician 

for help.

5 FCC Part 15 and Innovation, Science and 

Economic Development Canada (ISED) 

Compliance

This device complies with part 15 of the FCC Rules, and ISED 

license-exempt RSS standard(s). Operation is subject to the 

following two conditions: (1) this device may not cause 

interference, and (2) this device must accept any interference 

that may cause undesired operation of the device.

Le présent appareil est conforme aux CNR Innovation, Sciences 

et Développement économique Canada applicables aux 

appareils radio exempts de licence. L'exploitation est autorisée 

aux deux conditions suivantes: (1) l'appareil ne doit pas produire 

de brouillage, et (2) l'utilisateur de l'appareil doit accepter tout 

brouillage radioélectrique subi, même si le brouillage est 

susceptible d'en compromettre le fonctionnement.

6 Radiation Exposure Limits

6.1 FCC

This equipment complies with FCC radiation exposure limits set 

forth for an uncontrolled environment. In order to avoid the 

possibility of exceeding the FCC radio frequency exposure limits, 

human proximity to the antenna shall not be less than 20 cm 

during normal operation and must not be co-located or operating 

in conjunction with any other antenna or transmitter.

6.2 ISED

This equipment complies with ISED RSS-102 radiation exposure 

limits set forth for an uncontrolled environment. This transmitter 

must be installed to provide a separation distance of at least 20 

cm from all persons and must not be co-located or operating in 

conjunction with any other antenna or transmitter.

Cet équipement est conforme avec ISED RSS-102 des limites 

d'exposition aux rayonnements définies pour un environnement 

non contrôlé. Cet émetteur doit être installé à au moins 20 cm de 

toute personne et ne doit pas être colocalisé ou fonctionner en 

association avec une autre antenne ou émetteur.

Wall Tamper 

Switch

Отзывы: