  Parameter table of inverter 

”: means that the setting value of the parameter can be changed no matter if the driver is shutdown 

or running;   
 

”: means that the setting value of the parameter cannot be changed when the driver is running;   

“●”: means that the value of the parameter is the actual test value and cannot be changed;   
 

“*”:  means  that  the  parameter  is  a  "manufacturer's  parameter",  and  can  only  be  set  by  the 

manufacturer. Users are forbidden to change it. 

Parameter

 

Name

 

Setting range

 

Default value

 

Change

 

Group F0 Basic Function Group

 

F0-00

 

GP type display

 

1: G type (constant torque load model) 

 

Determine 
specification

 

 

 

F0-01

 

 

Control mode of first 
motor

 

0: speed-less sensor vector control (SVC) 

 

1: sensor vector control with speed (FVC) 

 

2: V/F control (synchronous motor not 
supported)

 

 

2

 

 

 

 

F0-02

 

 

Command source 
options

 

0: External LCD keyboard/background 
software

 

1: Terminal command channel

 

2: Communication command channel

 

 

2

 

 

 

 

 
 
 
 
 

F0-03

 

 
 
 
 

 

Select main frequency 
command

 

0: digital setting (preset frequency F0-08, 
UP/DOWN can be modified, but not stored 
in case of power failure) 

 

1: digital setting (preset frequency F0-08, 
UP/DOWN can be modified, and stored in 
case of power failure) 

 

2: AI1

 

3: AI2

 

4: (reserved) 
5: Pulse setting (DIO1)

 

6: Multiple-stage instruction

 

7: Simple PLC

 

8: PID

 

9: Communication setting

 

10: synchronous control

 

 

 
 
 
 
 

9

 

 
 
 
 

 

 

F0-04

 

Auxiliary frequency 
source Y options

 

Same as F0-03(main frequency source X 
options)

 

0

 

 

 

F0-05

 

Options of auxiliary 
frequency source Y 
range when 
superimposed

 

0: relative to the maximum frequency

 

1: relative to frequency source X

 

 

0

 

 

 

F0-06

 

Auxiliary frequency 
source Y range when 
superimposed 

 

0%~150%

 

 

100%

 

 

 
 
 
 

 

F0-07

 

 

 
 
 
 

Frequency source 
superposition options 

Units

’ place: frequency source options

 

0: main frequency source X 
1: Calculation results of the main frequency 
and auxiliary frequency (the operation 
relationship is determined by the tens place)   
2: Switching between main frequency 
source X and auxiliary frequency source Y

 

3: Switching between main frequency 
source X and calculation results of the main 
frequency and auxiliary frequency

 

4: Switching between c auxiliary 
frequency source Y and calculation 
results of the main frequency and 
auxiliary frequency 
Ten's place: the operation 
relationship between main frequency 
source and auxiliary frequency

 

0: main + auxiliary

 

1: main - auxiliary

 

2: Larger value of both

 

3: Smaller value of both

 

4: main * auxiliary

 

 
 
 
 

 

0

 

 

 
 
 
 

 

F0-08

 

Preset frequency

 

0.00Hz~ Max. frequency (F0-10)

 

50.00Hz

 

 

 

F0-09

 

Moving direction

 

0: same direction

 

1: opposite direction

 

 

0

 

 

F0-10

 

Max. frequency

 

5.00Hz~600.00Hz

 

50.00Hz

 

 

 
 

 

Parameter

 

Name

 

Setting range

 

Default 

value

 

Change

 

 

 

F0-11

 

 

 

Upper limit 
frequency source

 

0: F0-12 setting

 

1: AI1

 

2: AI2

 

4: Pulse setting(DIO1)

 

5: Communication setting

 

6: multi-speed command

 

 

 

0

 

 

 

 

F0-12

 

Upper limit 
frequency

 

Lower limit frequency F0-14~Max. frequency 
F0-10

 

50.00Hz

 

 

F0-13

 

Upper limit 
frequency bias

 

0.00Hz~ Max. frequency F0-10

 

0.00Hz

 

 

F0-14

 

Lower limit 
frequency

 

0.00Hz~ Upper limit frequency F0-12

 

0.00Hz

 

 

F0-15

 

Carrier frequency

 

0.8kHz~12.0kHz

 

Determine 

 

Содержание CV800 Series

Страница 1: ...n should be conducive to ventilation and heat dissipation so as to ensure the heat dissipation effect and avoid the overheat caused by the sun exposure Use the specified port when the driver is instal...

Страница 2: ...ximum frequency 0 025 Control mode SVC open loop vector control synchronous motor V F control asynchronous motor Acceleration and deceleration curve Linear or S curve acceleration and deceleration mod...

Страница 3: ...mpt content Parameter program modification copying and download Fast replication of parameters and program downloads Protection Protection function Overcurrent protection overvoltage protection underv...

Страница 4: ...s breathable and waterproof Inverter input wiring plugPositive and negative high voltage input Inverter output wiring plug Motor UVW output Keyboard window Fig 2 Opened keyboard cover of the driver Te...

Страница 5: ...component D8406 11 AD2 Analog input 2 Correspond to soft component D8407 19 AGND Analog common ground 8 CANH CAN communication Fixed 250K baud rate 15 CANL CAN communication 20 485A Channel 1 485 Opti...

Страница 6: ...SS0 X input common terminal Common terminals X00 to X04 16 X05 Set No 5 X input Correspond to soft component X05 28 X06 Set No 6 X input Correspond to soft component X06 13 X07 Set No 7 X input Corre...

Страница 7: ...ort Recommended cables and lugs Table 2 1 Recommended cables and lugs at DC DC side Type Name Positive output wire 2 sets Negative output wire Lug Wiring terminal M6 OT terminal M6 OT terminal Recomme...

Страница 8: ...itioning in order to view status modify parameters and copy or download programs of CV800 equipment in the driving cab it is recommended to use external SOP 20 810 keyboard for commissioning It is rec...

Страница 9: ...efault F0 03 Select frequency source 0 digital setting F0 08 not saved after power failure 1 digital setting F0 08 saved after power failure 9 communication setting CAB by default other options of the...

Страница 10: ...tioning control panel When 23PIN aviation plug is connected to 24V the keyboard may search CV800 DCDC equipment and connected to 24V and 540VDC CV800 INV equipment may be searched When disconnect 540V...

Страница 11: ...and PLC after the three devices are searched See Appendix A for information on operation Rooting is risky please keep keyboard on line during the whole copying process If power failure occurs the mach...

Страница 12: ...enu Authority management Keyboard login input login password 37421 After keyboard login enter the keyboard upgrade menu i e Menu System operation Keyboard upgrade as shown in the figure below HEV BUS...

Страница 13: ...he copying Fig 15 Waiting interface during upgrade Import keyboard configuration file 1 Connect the keyboard to the computer via the UBS port to see following contents on the computer Please select a...

Страница 14: ...ge 15VDC Input connection mode Aviation plug pluggable OFF voltage 5VDC Input type Digital input Port filtering time 10ms Input mode Source SINK type Input impedance 4 3K Input voltage class 24VDC max...

Страница 15: ...acitors and other capacitive loads may be present under the load of electronic circuits such as inverters 4 Transistor output specification Table B 5 Basic output specification of transistor Item Spec...

Страница 16: ...thermal resistance input of Channel 3 PT3 Input Negative NTC thermal resistance input of Channel 3 PT4 Input Positive NTC thermal resistance input of Channel 4 PT4 Input Negative NTC thermal resistanc...

Страница 17: ...latest version as background programming software of the product The software will be used for application programming and download monitoring For engineering PLC type select H1U XP The maximum progr...

Страница 18: ...please refer to COM1 of general version PLC CAN communication function Controller CAN communication supports free protocol conforming to CAN2 0 protocol specification CAN communication baud rate fixed...

Страница 19: ...ut 4 channel analog voltage output are supported Special components involved include M component Description of M component D component Description of D component Input filtration coefficient M8390 Re...

Страница 20: ...grounded or short circuited Eliminate peripheral faults detect whether the motor is short circuited or the circuit is open The control mode is FVC or SVC without performing parameter tuning Set and tu...

Страница 21: ...ted within the range from 30 to 50 In the deceleration process an external force has driven the motor to run Remove the external force or install brake resistor the maximum frequency F3 26 increase fo...

Страница 22: ...ral faults Three phases of input voltage are unbalanced during motor running Check whether the motor three phase winding is normal and complete troubleshooting Driver board or IGBT module faulted Seek...

Страница 23: ...reasonable range If such warning is reported the inverter will calculate the mutual inductance and no load current based on known motor parameters and the values might be different from the optimal va...

Страница 24: ...frequency source X options 0 F0 05 Options of auxiliary frequency source Y range when superimposed 0 relative to the maximum frequency 1 relative to frequency source X 0 F0 06 Auxiliary frequency sour...

Страница 25: ...ted current 0 01A 655 35A Determine specification F1 04 Motor rated frequency 0 01Hz Max frequency F0 10 Determine specification F1 05 Motor rated speed 1rpm 65535rpm Determine specification F1 06 Asy...

Страница 26: ...0 0 F2 10 Torque upper limit setting under speed control electric 0 0 200 0 150 0 F2 11 Torque upper limit source under speed control power generation 0 upper limit number setting F2 10 1 AI1 2 AI2 4...

Страница 27: ...1 0 Parameter Name Setting range Default value Change F2 53 Generation power limiting enabled 0 not enabled 1 enabled 0 F2 54 Generation power limiting 0 0 200 0 Determine specification Group F3 V F...

Страница 28: ...0 50 5 F3 27 Torque error compensation time constant 0 1 10 0 0 5 F3 28 Automatic frequency ascending enabled 0 not enabled 1 enabled 0 F3 29 Minimum electric torque current 10 100 50 F3 30 Maximum po...

Страница 29: ...cimal places 3 3 decimal places 1 F7 13 Accumulated power on time 0h 65535h F7 14 Accumulated power consumption 0 kilowatt hour 65535 kilowatt hour F7 15 Performance temporary version number 0 65535 F...

Страница 30: ...rd latest fault occurs F9 22 Driver state when the third latest fault occurs F9 23 Power on time before occurrence of the third latest fault F9 24 Running time when the third latest fault occurs Param...

Страница 31: ...ion action options 4 Units place running time expired E26 ten s place user defined fault 1 E27 hundred s place user defined fault 2 E28 thousand s place Power on time expires E29 ten thousand s place...

Страница 32: ...3 100 0 100 0 0 0 FC 04 Multiple stage instruction 4 100 0 100 0 0 0 FC 05 Multiple stage instruction 5 100 0 100 0 0 0 FC 06 Multiple stage instruction 6 100 0 100 0 0 0 FC 07 Multiple stage instruct...

Страница 33: ...6 J1939 message format modification and check 0 65535 0 Fd 47 ID of messeage 1 received high 16 bit 0 0x1FFF 0x1400 Fd 48 ID of messeage 1 received low 16 bit 0 0xFFFF 0x9183 Fd 49 Sending cycle 1 1 6...

Страница 34: ...ing cap frequency 0 00Hz Max frequency F0 10 12 00Hz A5 01 PWM modulation mode 0 asynchronous modulation 1 synchronous modulation 0 A5 02 Dead zone compensation mode options 0 no compensation 1 compen...

Страница 35: ...tor mixed mode field weakening 3 no field weakening 1 A9 21 Synchronous motor field weakening gain 0 50 5 A9 22 Synchronous motor output voltage upper margin 0 50 5 A9 23 Max generation adjustment gai...

Страница 36: ...fan runs properly Input undervoltage Input voltage is lower than 250V Input terminal not powered Check the input voltage Check if the input terminal is powered Input overvoltage Input voltage is highe...

Страница 37: ...5 0 F3 01 Select the number of failures to display 0 65535 0 F3 02 Fault code 1 input overvoltage 2 input undervoltage 3 Module 1 output overvoltage 4 Module 1 output undervoltage 5 Module overheated...