background image

 

Specifications are subject to change without notice.   No liability accepted for errors or omissions. 

750 Watt  

No-Break™ DC 

charger for lead acid batteries 

N

o

-B

re

a

k

 D

C

 

MODELS 

DC Output

 

Output (V)

 

PSU Rated  

(A) 

Charge 

 Limit (A) *

1

 

Recomm. 

Load  (A) 

Peak load on 

power fail (A) 

SR750

i

12 

13.8 

54 

54 

42 

81 

SR750

i

24 

27.6 

27 

27 

19 

40 

SR750

i

30 

34.5 

21 

21 

14 

31 

SR750

i

36 

41.4 

18 

18 

12 

27 

SR750

i

48 

55.2 

13.5 

13.5 

8.5 

20 

PHYSICAL

 

AC Input connector 

 

DC Output Connections 

 

 
Alarm Connections 

 

 

Enclosure 

 

Weight 
 
Dimensions 

IEC320 inlet socket 

 

M8 brass stud or plug-in/ screw terminal 
block (20A/ terminal) 

 

Plug in/ screw terminal block

 

 

Powder coated steel 

 

4.3kg 
 
225W x 304D x 70H mm (excluding mount-
ing feet and terminals) 

SCHEMATIC BLOCK DIAGRAM

 

STANDARD MODEL TABLE

 

ACCESSORIES SUPPLIED 

 

Mounting feet  together with screws 
AC power cord 1.5m  with IEC320 socket & AUS/NZ plug 
Mating screw terminal plug for  DC connector for ‘X’ version 
Mating screw terminal plug for alarm outputs 
Crimp lugs for ’S’ version 

OPTIONS 

 

19”Rack Mount 
 
 
Wall Mount Enclosure 
 
 
Parallel redundancy 

 

 

Internal Digital V/I Meter 

 

 

MODEL IDENTIFICATION CODES 

SR750 

i

 

12 T F S L-LAN+ 

2U sub rack option:

 

add 

SR-RM2U 

Optional V/I meter for subrack

: SR-METER

 

 
PSU may be fitted into enclosure with MCBs 
and terminals. 

Code:  SEC-SR

 

 
Use external output diode, eg 

+P50.  

Please 

refer to separate application notes. 

 

Add code 

+INT-METER 

 

 

SR

... i......-LAN+

=

~

ALARMS

ethernet
comms 
port 
for 
SNMP

LOAD

BATTERY

AC input

+

-

+

-

Temperature sensor to be
 placed on or near battery

230V AC  

+ switch = 

 230V AC  

no switch = blank 

110V AC  

+ switch = 

U

  110V AC  

no switch = 

G

 

110V DC  

+ switch = 

H

  110V DC  

no switch = 

J

 

Input voltage and front 
panel standby switch: 

Stud = 

S

      Phoenix combicon (plug in /screw terminal block) = 

X

 

Output DC Connector type:  

 Fan cooled = 

F

 

Cooling 

Yes = 

T

 

 

No  = blank 

Temperature Compensation  

12, 24, 30, 36, 48V 

DC output: Nominal voltage  

= No-Break

DC with communication port 

Function 

Power 

750W 

Communication port: 

LAN+ 

= Ethernet (SNMP) 

*1 charge current limit may be varied at 
time of order 

Содержание SR750i

Страница 1: ...w innovative co nz Phone 64 9 835 0700 Fax 64 9 837 3446 NZ Freephone 0800 654 668 AU Freephone 1800 148 494 Email info innovative co nz No BreakTM DC UPS with SNMP communications port 750W SR750i LAN...

Страница 2: ...ent Batteries and cooling fans also suffer shortened lifetimes if subjected to high ambient temperatures both should be included in a routine maintenance schedule to check for signs of reduced effi ci...

Страница 3: ...U MAX CURRENT ELECTRONIC CIRCUIT BREAKER POWER CONVERSION BATTERY MANAGEMENT ALARM CIRCUIT BATTERY CURRENT SENSE OUTPUT VOLTAGE CURRENT LIMIT BATTERY CHARGE CURRENT CONTROL I CHARGE BATTERY TEMP SENSO...

Страница 4: ...es of system ensure that they match the equipment All loads should be isolated 2 Check polarity of all wiring Place temperature sensor probe near or on batteries 3 Plug in input power POWER OK LED wil...

Страница 5: ...battery detection interval time For full list of LED flash codes please refer to page 7 BATTERY SYSTEM OK LED on Battery present and above V batl POWER OK LED on Input power present STANDBY LED on Ch...

Страница 6: ...Bccl Maximum charge current as of rated PSU rated current 2 Comms communications mode of PSU F continuous data stream of status M responds only to request made by a controller M BatDetect Battery dete...

Страница 7: ...ttery missing ECB has tripped Normal Alarm Input power off battery system is OK battery volts Vbatl Alarm Alarm Input power off and battery has discharged to V batl Alarm Alarm Input power off ELVD ha...

Страница 8: ...Over voltage protection on output at 130 of nominal output voltage Settings to be specified at time of order Control of BCT is implemented using the SNMP software BCT relay provided to control an exte...

Страница 9: ...ector for X version Mating screw terminal plug for alarm outputs Crimp lugs for S version OPTIONS 19 Rack Mount Wall Mount Enclosure Parallel redundancy Internal Digital V I Meter MODEL IDENTIFICATION...

Страница 10: ...y for very critical applications with redundancy of the battery in addition to the power supply The diodes isolate the units from one another in the event of a short circuit appearing at the other out...

Страница 11: ...or high peak loads All No Break alarms are available and the low voltage disconnect for the peak load is optionally implemented with an external relay 5 N 1 for No Break DC charger and single battery...

Страница 12: ...es Ltd warrants its power supplies for 24 months two years from date of shipment against material and workmanship defects Innovative Energies liability under this warranty is lim ited to the replaceme...

Отзывы: