background image

 

Specifications are subject to change without notice.   No liability accepted for errors or omissions. 

10 

#1  1 x 

No-Break™DC 

charger and 1 x battery bank

 

 
This is the basic connection which is most commonly used, and provides 
adequate protection for the majority of systems requiring DC back up in 
the event of a mains power failure. 

#2  1 x 

No-Break™DC charger and 2 x battery banks

  

 

 

 

 

The 

SR250

xxx

V

  

No-Break™DC  

UPS

 

is designed to provide superior 

battery backup availability without having to use two power supplies.   
Dual battery banks and automatic battery condition testing reduce the risk 
of battery failure for critical applications. 
 

 

 

 

 

Power OK 

YES 

Battery Missing (B1&B2) 

YES 

Battery Low (B1&B2) 

YES 

Battery Condition Test Fail 
(B1 & B2) 

YES 

Alarms Available 

 

Power OK 

YES 

Battery Missing 

YES 

Battery Low 

YES 

Battery Condition Test Fail 

YES 

Alarms Available 

 

#3  2 x 

No-Break™DC 

chargers and 2 x battery banks 

 

2 x No-Break™DC 

chargers connected in parallel with separate battery 

banks & output diodes.   This solution provides an extremely high level 
of redundancy for very critical applications,  with  redundancy of the 
battery in addition to the power supply.  The  diodes isolate the units 
from one another in the event of a short circuit appearing at the other 
output and aid current sharing. 

Power OK 

YES 

Battery Missing 

YES 

Battery Low 

YES 

Battery Condition Test Fail*

1

 

YES 

Alarms Available 

 

INPUT

LOAD

BAT 1

BAT 2

BCT LOAD

=

ALARMS

COMMS PORT

L+

L-

B1+

B1-

B2+

B2-

RES

RES

SRxxxV

ECB

=

INPUT

L+

B-

L-

ALARMS

SRxxxC

B+

LOAD

ECB

SRxxxC

SRxxxC

ALARMS

ALARMS

L+,B+

L+,B+

B-

B-

L-

L-

INPUT

INPUT

LOAD

=

=

BAT

ECB

ECB

#4  

No-Break™DC 

Connection for high peak loads

 

 
This is a basic connection which is used when there is a connected load 
with a peak current greater than 1.5 times the rated current of the 
charger.   Standing loads are connected normally and an optional exter-
nal low voltage disconnect may be used for the peak load. 

Power OK 

YES 

Battery Missing 

YES 

Battery Low 

YES 

Battery Condition Test Fail 

YES 

Alarms Available 

 

=

PEAK
LOAD

BAT

ECB

INPUT

NORMAL
LOAD

*LVD

* optional

L+,B+

B-

L-

ALARMS

SRxxxC

Single battery DC 
backup system 

N+1 redundancy for 
batteries 

N+1 redundancy for 
charger and batteries 

Single battery DC 
backup system for 
peak loads 

*

interlock circuit required for 

automated BCT 

No-Break DC & standard N+1 connections 

Содержание SR750i

Страница 1: ...w innovative co nz Phone 64 9 835 0700 Fax 64 9 837 3446 NZ Freephone 0800 654 668 AU Freephone 1800 148 494 Email info innovative co nz No BreakTM DC UPS with SNMP communications port 750W SR750i LAN...

Страница 2: ...ent Batteries and cooling fans also suffer shortened lifetimes if subjected to high ambient temperatures both should be included in a routine maintenance schedule to check for signs of reduced effi ci...

Страница 3: ...U MAX CURRENT ELECTRONIC CIRCUIT BREAKER POWER CONVERSION BATTERY MANAGEMENT ALARM CIRCUIT BATTERY CURRENT SENSE OUTPUT VOLTAGE CURRENT LIMIT BATTERY CHARGE CURRENT CONTROL I CHARGE BATTERY TEMP SENSO...

Страница 4: ...es of system ensure that they match the equipment All loads should be isolated 2 Check polarity of all wiring Place temperature sensor probe near or on batteries 3 Plug in input power POWER OK LED wil...

Страница 5: ...battery detection interval time For full list of LED flash codes please refer to page 7 BATTERY SYSTEM OK LED on Battery present and above V batl POWER OK LED on Input power present STANDBY LED on Ch...

Страница 6: ...Bccl Maximum charge current as of rated PSU rated current 2 Comms communications mode of PSU F continuous data stream of status M responds only to request made by a controller M BatDetect Battery dete...

Страница 7: ...ttery missing ECB has tripped Normal Alarm Input power off battery system is OK battery volts Vbatl Alarm Alarm Input power off and battery has discharged to V batl Alarm Alarm Input power off ELVD ha...

Страница 8: ...Over voltage protection on output at 130 of nominal output voltage Settings to be specified at time of order Control of BCT is implemented using the SNMP software BCT relay provided to control an exte...

Страница 9: ...ector for X version Mating screw terminal plug for alarm outputs Crimp lugs for S version OPTIONS 19 Rack Mount Wall Mount Enclosure Parallel redundancy Internal Digital V I Meter MODEL IDENTIFICATION...

Страница 10: ...y for very critical applications with redundancy of the battery in addition to the power supply The diodes isolate the units from one another in the event of a short circuit appearing at the other out...

Страница 11: ...or high peak loads All No Break alarms are available and the low voltage disconnect for the peak load is optionally implemented with an external relay 5 N 1 for No Break DC charger and single battery...

Страница 12: ...es Ltd warrants its power supplies for 24 months two years from date of shipment against material and workmanship defects Innovative Energies liability under this warranty is lim ited to the replaceme...

Отзывы: