Innovative Circuit Technology Ltd.
5
3. LCD: Displays system voltage, system current, output current and fuse status
for each of the 12 output positions.
4. OUTPUT SELECT BUTTON: For switching between LCD screens, and resetting
network, web server and password settings to original factory default values.
5. JCASE FUSES: Location of the JCASE fuses rated up to 40A.
BACK PANEL
Figure 2.
1. NEGATIVE INPUT STUD: For DC power source connection up to 180A peak and
150A continuous.
2. OUTPUT TERMINAL BLOCK 10
–
12: For DC load connections up to 40A each
pair.
3. ALARM FORM “C” CONTACTS: For external alarm circuit to monitor alarms
generated by the panel.
4. ALARM SENSOR INPUTS: Inputs for external Dry Contact sensors.
5. LAN PORT: For remote monitoring via TCP/IP network.
6. CHASSIS GROUND STUD: For Earth ground connection.
7. OUTPUT TERMINAL BLOCK 1
–
9: For DC load connections up to 25A each pair.
8. POSITIVE INPUT STUD: For DC power source connection up to 180A peak and
150A continuous.
INSTALLATION
1. Inspect panel and accessories to make sure everything is complete and in good
condition.
2. For rack set up, install panel on the rack using appropriate size screws and star
washers on all four mounting holes. If equipment rack is not electrically
connected to Earth ground, connect a ground cable from the ground stud on the
back of the panel to a known Earth ground point. Otherwise, the four mounting
screws and washers may be sufficient for earth ground connection.
OR
For non-rack set up, connect a ground cable from the ground stud on the back of
the panel to a known Earth ground point.