54
3. IPM continuity check
Turn off the power, let the large capacity electrolytic capacitors discharge completely, and dismount the IPM. Use a digital
tester to measure the resistance between P and UVWN; UVW and N.
Digital tester
Normal resistance value
Digital tester
Normal resistance value
(+)Red
(-)Black
∞
(Several MΩ)
(+)Red
(-)Black
∞
(Several MΩ)
P
N
U
N
U
V
V
W
W
(+)Red
4: Indoor AC Fan Motor
Measure the resistance value of each winding by using the tester.
Position
Resistance Value
RPG13B
RPG15A
RPG20B
RPG28H
RPG45B
Black -
Red
530
Ω±8%
(20
℃
/68
℉
)
(Brand:
Welling)
75
Ω±8%
(20
℃
/68
℉
)
(Brand:
Welling)
381
Ω±8%
(20
℃
/68
℉
)
(Brand:
Welling)
183.6
Ω±8%
(20
℃
/68
℉
)
(Brand:
Welling)
112
Ω±8%
(20
℃
/68
℉
)
(Brand:
Welling)
118.5
Ω±8%
(20
℃
/68
℉
)
(Brand: Broad
Ocean)
White -
Black
315
Ω±8%
(20
℃
/68
℉
)
(Brand:
Welling)
150
Ω±8%
(20
℃
/68
℉
)
(Brand:
Welling)
267
Ω±8%
(20
℃
/68
℉
)
(Brand:
Welling)
206
Ω±8%
(20
℃
/68
℉
)
(Brand:
Welling)
82
Ω±8%
(20
℃
/68
℉
)
(Brand:
Welling)
78.5
Ω±8%
(20
℃
/68
℉
)
(Brand: Broad
Ocean)
Содержание PIN413C2V31
Страница 7: ...5 2 2 Part names of Indoor Outdoor units ...
Страница 14: ...12 6 Wiring Diagram 6 1 Indoor Unit PIN413C2V31 I PIN519C2V31 I ...
Страница 15: ...13 PIN624C2V31 IW ...
Страница 16: ...14 6 2 Outdoor Unit PIN413C2V31 O PIN519C2V31 O ...
Страница 17: ...15 PIN624C2V31 O For PIN413C2V31 O ...
Страница 18: ...16 For PIN519C2V31 O For PIN624C2V31 O ...
Страница 46: ...44 P U P V ...
Страница 47: ...45 P W P N ...