For 30K~36K:
At first test the resistance between every two ports of U, V, W of IPM and P, N. If any result of them is 0 or close to 0, the
IPM is defective. Otherwise, please follow the procedure below:
Yes
Check whether the power voltage
is normal.
Measure whether outdoor terminal
voltage is normal
?
Restart the unit when the power supply gets
normal
No
Yes
No
Reconnect it well
Yes
Measure whether the voltage
between L and N is normal
?
Yes
Measure whether input voltage of
bridge rectifier is normal
?
No
No
Check the wiring of
power wires well or
correctly
Reconnect it well
Check the wiring of L
and N well or correctly
Reconnect it well
Check the wiring of
bridge rectifier well or
correctly
No
Yes
Replace the PFC module(If has)
No
Measure whether the voltage between P
and N is normal refer to the 5.1.5
Normal voltage of P and N
?
Replace the bridge rectifier
No
Check whether bridge
rectifier is normal
Check the wiring of reactor
or inductance
Reconnect the wiring
No
Check whether reactor or
inductance is normal
Yes
Replace reactor or
inductance
No
Check whether the connecting
wire between main board and
the IPM board is connected
tightly
Reconnect it well
No
Check if the outdoor unit
ventilation is good
Yes
Make the outdoor unit ventilate well
Check whether the refrigerant system is ok
No
Check if the outdoor fan runs
properly
Please refer to the solution of [fan speed
has been out of control malfunction] .
Find out the cause and have it solved.
No
Yes
No
Yes
Yes
Check the compress is
normal
Yes
Replace the compressor
No
Replace IPM board
Replace the outdoor main PCB
No
Check whether the connecting
wire of the compressor is
connected correctly or tightly
Reconnect it well
No
Yes
Yes