2. General Troubleshooting
2.1 Error Display (Indoor Unit)
When the indoor unit encounters a recognized error, the indicator light will flash in a corresponding series, the timer
display may turn on or begin flashing, and an error code will be displayed. These error codes are described in the
following table:
Operation
Lamp
Timer
Display
Display
Error
Information
Solution
1 times
OFF
E0
Indoor unit EEPROM parameter error
Page 83
2 times
OFF
E1
Indoor / outdoor units communication error
Page 84
3 times
OFF
E2
Zero-crossing signal detection error
Page 86
4 times
OFF
E3
The indoor fan speed is operating outside of the normal range
Page 87
5 times
OFF
E4
Indoor room temperature sensor T1 is in open circuit or has
short circuited
Page 90
6 times
OFF
E5
Evaporator coil temperature sensor T2 is in open circuit or
has short circuited
Page 90
7 times
OFF
EC
Refrigerant leak detected
Page 91
1 times
ON
F0
Overload current protection
Page 92
2 times
ON
F1
Outdoor ambient temperature sensor T4 open circuit or
short circuit
Page 90
3 times
ON
F2
Condenser coil temperature sensor T3 is in open circuit or
has short circuited
Page 90
4 times
ON
F3
Compressor discharge temperature sensor TP open circuit
or short circuit
Page 90
5 times
ON
F4
Outdoor unit EEPROM parameter error
Page 83
6 times
ON
F5
The outdoor fan speed is operating outside of the normal range
Page 87
1 times
FLASH
p0
IPM malfunction or IGBT over-strong current protection
Page 93
2 times
FLASH
p1
Over voltage or over low voltage protection
Page 95
3 times
FLASH
p2
High temperature protection of IPM module
Page 96
4 times
FLASH
P3*
Outdoor ambient temperature too low
-
5 times
FLASH
p4
Inverter compressor drive error
Page 97
6 times
FLASH
P5
Indoor units mode conflict (multi-zone ONLY)
-
7 times
FLASH
P6
Low pressure protection(Only for 36K)
Page 90
*P3:
• In heating mode, when the outdoor temperature is lower than -25°C for 1 hour, the indoor unit display error code
P3.
• If the outdoor temperature is higher than -22°C for 10 minutes and compressor stop for 1 hour or outdoor
temperature is higher than -5°C for 10 minutes, then the unit will return to work.