Electric Characteristics
Outdoor Units
9
5. Electric Characteristics
Model
Power Supply
Hz
Phase
Voltage
Min.
Max.
VEM36C2HR1
60
1
220-230V
198V
242V
VEM48C2SS1
60
1
220-230V
198V
242V
VEM60C2SS1
60
1
220-230V
198V
242V
VEM60C3SS1
60
3
220-230V
198V
242V
6. Operation Limits
Temperature
Mode
Cooling operation
Room temperature
17
℃~
32
℃
Outdoor temperature
18
℃~
43
℃
(
-7
℃~
43
℃:
For the
models with low
temperature cooling
system
)
10
15
25
30
35
20
15
20
25
30
35
40
45
Indoor temperature(
℃
WB)
O
ut
door
t
em
per
a
tu
re
(
℃
D
B)
STD
Cooling
43
17
32
10
5
0
-5
-10
18
-7
With Low
Ambient
Cooling
System
©2015 Innovair Corporation. All Rights Reserved.
www.innovair.com