28
If users switch on AC by remote controller, the compressor will run at the Fmax frequency for 7
minutes according to outdoor ambient temp. During the 7 minutes, frequency limitation is active.
7 minutes later, the compressor running frequency will be controlled as below:
While
Temp. zone
A
B
C
D
E
F
G
Frequency
F8
F8
F7
F6
F5
F3
F1
Note:
When the value of T1 minus Ts keeps in the same temp. zone for 3 minutes, the compressor will run
as the below rules:
℃
20
22
28
30
40
38
45
43
Fmax=F4
Fmax=F7
Fmax=F8
Fmax=F6
Fmax=F3
T4
℃
-1.0
-0.5
0.5
1.0
1.5
2.0
2.5
3.0
3.5
A
B
C
D
E
F
G
H
T1-TS