OVER CURRENT OR LOW 

CURRENT PROTECTION 

A. Check the voltage of input AC power is within 

normal range. B. Check DC power voltage on 

outdoor unit main PCB, if the voltage is lower than 

150VDC, then replace the outdoor unit main PCB; 

if the voltage is higher than 400VDC, then change 

PFC modular board, or change the inverter modular 

board. 

14 

INDOOR UNIT FAN COIL 

TEMPERATURE SENSOR 

FAILURE 

A. Connection location on indoor unit PCB is: 

CN8/T2_PIPE 

for 12kbtu/18kbtu, 

CN19/PIPE/PT

 

for 24kbtu/36kbtu, replace with new sensor; B. after 

step A, if unit still displays error code E3, change 

the indoor unit PCB. 

16 

INDOOR UNIT AMBIENT 

TEMPERATURE SENSOR 

FAILURE 

A. Connection location on indoor unit PCB is: 

CN11/ T1_ROOM

 for 12kbtu/18kbtu, 

CN20/ROOM/RT

 for 24kbtu/36kbtu, replace with 

new sensor; B. after step A, if unit still displays 

error code E2, change the indoor unit PCB. 

17 

ANTI-FROSTING IN COOLING 

MODE 

A. Check if indoor unit fan motor is operating; 

B. Check if unit is in the cooling mode when ambient 

temperature is too low; C. Check if the resistance 

data of indoor unit fan coil temperature sensor is 

correct according to resistance data table of sensors 

in this manual. 

18 

ANTI-OVERHEATING IN 

HEATING MODE 

A. Check if indoor unit fan motor is operating; 

B. Check if unit is in the heating mode when 

ambient temperature is too hot; C. Check if the 

resistance data of indoor unit fan coil temperature 

sensor is correct according to resistance data table 

of sensors in this manual. 

E21 

OUTDOOR CONDENSER 

OVERHEAT IN COOLING MODE 

A. Check if outdoor unit fan motor is operating; 

B. Check if unit is in the cooling mode when ambient 

temperature is too hot; C. Check if the resistance 

data of outdoor unit fan coil temperature sensor is 

correct according to resistance data table of sensors 

in this manual. 

Содержание UCCA-36HDC

Страница 1: ......

Страница 2: ......

Страница 3: ......

Страница 4: ......

Страница 5: ......

Страница 6: ......

Страница 7: ......

Страница 8: ......

Страница 9: ......

Страница 10: ......

Страница 11: ......

Страница 12: ......

Страница 13: ......

Страница 14: ......

Страница 15: ......

Страница 16: ......

Страница 17: ......

Страница 18: ......

Страница 19: ......

Страница 20: ......

Страница 21: ......

Страница 22: ......

Страница 23: ...s not pass change outdoor unit inverter modular board 05 OUTDOOR UNIT FAN COIL TEMPERATURE SENSOR FAILURE A Connection location on outdoor unitmain PCB is CN15 PO PG PQ for 12kbtu 18kbtu 24kbtu 36kbtu...

Страница 24: ...UNIT FAILURE A Check the wiring sequence between indoor unit and outdoor unit if wired incorrect this will cause damage to the PCB for both indoor unit and outdoor unit B Check the status of LED4 lamp...

Страница 25: ...A if unit still displays error code E2 change the indoor unit PCB 17 ANTI FROSTING IN COOLING MODE A Check if indoor unit fan motor is operating B Check if unit is in the cooling mode when ambient tem...

Страница 26: ......

Страница 27: ......

Отзывы: