innTOUCH Parameters
The innTOUCH parameters can be accessed and programmed by
simultaneously pressing and holding the
Power
,
Left Button
, and
Right
Button
. You must use the
Left Button
button to exit and
return to the home screen in order to save any parameter changes to
memory. You can also modify multiple parameters before returning
to the home screen to save your changes.
Parameter 1: Sensor Calibration Value
The actual sensor temperature reading will be displayed. Use the Up
and Down buttons to enter an offset to the sensor reading.
P1 note:
Only the integrated temperature sensor can be calibrated
from the wall unit. All other inputs can only be calibrated by the
configuration loaded on the controller.
Specifications
POWER SUPPLY REQUIREMENTS
Power input
Powered by connected controller
This is a Safety Extra Low Voltage (SELV) of 5–12VDC. The power is
connected by the 2 way Combicon plug used for communications.
Polarity (+/–) MUST be observed when connecting power.
ENVIRONMENTAL
Operating Temperature
0 to 40°C non-condensing
Storage Temperature
0 to 50°C non-condensing
BATTERY - ISS02 & ISS04 Only
Contains Lithium Type Battery, Dispose of Properly.
(In accordance with local regulations).
Type
CR-2032 Lithium
Nominal voltage
3 Volts
Shelf life
5 Years, depending on ambient
temperature
Caution: Risk of explosion if battery is replaced by an incorrect type.
ENCLOSURE
Designed to maximise airflow to the integrated thermistor. Can be
mounted with a standard vertical C-Clip, or in a standard wall enclosure.
Colour
White/Grey
Dimensions (Maximum)
(W)70mm x (H)121mm x (D)41mm
APPROVALS
EN61326-1:2013 for CE & RCM Labelling
Title 47 CFR, Part 15 Class A for FCC Marking
UL & C-UL listed to UL916, File Number E242628
INPUTS / OUTPUTS - ISS03 & ISS04 ONLY
4 physical inputs (optional) configured with software as shown below:
Input Type
Input Range
Output Range
Dry Digital Input
Open or Closed
ON or OFF
Thermistor Input
96kΩ – 677Ω
-20°C to 100°C
1 integrated thermistor input scalable for °F
Parameter 2: Default Set Point
The factory default set point is 22.5
°
C, or Fahrenheit equivalent.
P2 note:
A compatible MAXIM controller will use the default value
stored in the Set Point Net Input block until innTOUCH has been
correctly detected and configured.
Parameter 3: Set Point Minimum Value
The minimum value for the set point. Factory default is 15
°
C or
Fahrenheit equivalent.
Parameter 4: Set Point Maximum Value
The maximum value for the set point. Factory default value is 30
°
C
or Fahrenheit equivalent.
Parameter 5: Set Primary Display Mode
This parameter determines what is displayed on the primary home
screen. The options are
Temperature
[Factory Default]
, Set Point
(SP), Auxiliary value (AVAL), Time or Date.
Parameter 6: Set Secondary Display Mode
This parameter determines what is displayed on the secondary
home screen (small field at the bottom of the screen). The options
are
Temperature, Set Point (SP), Auxiliary value (AVAL), Time
[Factory
Default]
or Date
.
Parameter 7: Set Temperature Display Units
Determines whether the temperature is displayed in Celsius [Factory
Default] or Fahrenheit.
P7 note:
All temperature values will be processed using Celsius and
converted to Fahrenheit if P7 is set to display Fahrenheit.
Parameter 8: Set Primary Auxiliary Value Units
Determines how the Auxiliary value is displayed on the primary
display, if selected. The options are
Temperature
[Factory Default]
,
kW, kWh or nothing
.
Parameter 9: Set Secondary Auxiliary Value Units
Determines how the Auxiliary value is displayed on the secondary
display, if selected. The options are
Temperature, ppm, %, %Rh or
nothing
[Factory Default].
Parameter 10: Minimum Scaling Factor for Auxiliary Value
This is the minimum scaling value for the Auxiliary Value output.
Factory default is -20.
Parameter 11: Maximum Scaling Factor for Auxiliary Value
This is the maximum scaling value for the Auxiliary Value output.
Factory default is 100.
Parameter 12: Fan Speed or AC Mode
This parameter sets the operating mode for innTOUCH.
•
AHC
When selected, the operator may change the
operating mode using the Right Button. Auto,
Heat, Cool or Vent can be selected.
•
FAN
Fan speed can be adjusted with the Left Button.
Auto, Heat, Cool and Vent mode is automatically
controlled.
•
NONE
Fan speed cannot be adjusted and Auto
operation is selected. The Left and Right
buttons are not used. [Factory Default]
The Factory Default parameters shown on this page are for the
latest default firmware. Please contact Innotech or your local
distributor for details on other Firmware Versions.