innTOUCH Parameters

The innTOUCH parameters can be accessed and programmed by 

simultaneously pressing and holding the 

Power

Left Button

, and 

Right

 

Button

.  You must use the 

Left Button

 button to exit and 

return to the home screen in order to save any parameter changes to 

memory.  You can also modify multiple parameters before returning 

to the home screen to save your changes. 

Parameter 1:  Sensor Calibration Value

The actual sensor temperature reading will be displayed.  Use the Up 

and Down buttons to enter an offset to the sensor reading. 

P1 note:

 Only the integrated temperature sensor can be calibrated 

from the wall unit.  All other inputs can only be calibrated by the 
configuration loaded on the controller.

Specifications

POWER SUPPLY REQUIREMENTS

Power input

Powered by connected controller

This is a Safety Extra Low Voltage (SELV) of 5–12VDC.  The power is             

connected by the 2 way Combicon plug used for communications.

 Polarity (+/–) MUST be observed when connecting power.

ENVIRONMENTAL

Operating Temperature

0 to 40°C non-condensing

Storage Temperature

0 to 50°C non-condensing

BATTERY - ISS02 & ISS04 Only

Contains Lithium Type Battery, Dispose of Properly.

(In accordance with local regulations).
Type

CR-2032 Lithium

Nominal voltage

3 Volts

Shelf life

5 Years, depending on ambient 

temperature

   

Caution: Risk of explosion if battery is replaced by an incorrect type.

ENCLOSURE

Designed to maximise airflow to the integrated thermistor.  Can be     

mounted with a standard vertical C-Clip, or in a standard wall enclosure.
Colour

White/Grey

Dimensions (Maximum)

(W)70mm x (H)121mm x (D)41mm

APPROVALS

EN61326-1:2013 for CE & RCM Labelling
Title 47 CFR, Part 15 Class A for FCC Marking
UL & C-UL listed to UL916, File Number E242628

INPUTS / OUTPUTS - ISS03 & ISS04 ONLY

4 physical inputs (optional) configured with software as shown below:

Input Type

Input Range

Output Range

Dry Digital Input

Open or Closed

ON or OFF

Thermistor Input

96kΩ – 677Ω

-20°C to 100°C 

1 integrated thermistor input scalable for °F

Parameter 2:  Default Set Point

The factory default set point is 22.5

°

C, or Fahrenheit equivalent.

P2 note:

  A compatible MAXIM controller will use the default value 

stored in the Set Point Net Input block until innTOUCH has been 
correctly detected and configured.

Parameter 3:  Set Point Minimum Value

The minimum value for the set point.  Factory default is 15

°

C or 

Fahrenheit equivalent.

Parameter 4:  Set Point Maximum Value

The maximum value for the set point.  Factory default value is 30

°

or Fahrenheit equivalent.

Parameter 5:  Set Primary Display Mode

This parameter determines what is displayed on the primary home 

screen.  The options are 

Temperature 

[Factory Default]

, Set Point 

(SP), Auxiliary value (AVAL), Time or Date. 
 

Parameter 6:  Set Secondary Display Mode

This parameter determines what is displayed on the secondary 

home screen (small field at the bottom of the screen). The options 

are 

Temperature, Set Point (SP), Auxiliary value (AVAL), Time 

[Factory 

Default] 

or Date

.

Parameter 7:  Set Temperature Display Units

Determines whether the temperature is displayed in Celsius [Factory 

Default] or Fahrenheit.  

P7 note:

  All temperature values will be processed using Celsius and 

converted to Fahrenheit if P7 is set to display Fahrenheit.  

Parameter 8:  Set Primary Auxiliary Value Units

Determines how the Auxiliary value is displayed on the primary 

display, if selected. The options are 

Temperature 

[Factory Default]

kW, kWh or nothing

.

Parameter 9:  Set Secondary Auxiliary Value Units

Determines how the Auxiliary value is displayed on the secondary 

display, if selected. The options are 

Temperature, ppm, %, %Rh or 

nothing 

[Factory Default].

Parameter 10:  Minimum Scaling Factor for Auxiliary Value

This is the minimum scaling value for the Auxiliary Value output.  

Factory default is -20.

Parameter 11:  Maximum Scaling Factor for Auxiliary Value

This is the maximum scaling value for the Auxiliary Value output.  

Factory default is 100.

Parameter 12:  Fan Speed or AC Mode

This parameter sets the operating mode for innTOUCH.

• 

AHC    

When selected, the operator may change the  

 

 

operating mode using the Right Button. Auto,  

 

 

Heat, Cool or Vent can be selected.

• 

FAN   

Fan speed can be adjusted with the Left Button.   

 

 

Auto, Heat, Cool and Vent mode is automatically  

  

controlled. 

• 

NONE  

Fan speed cannot be adjusted and Auto    

 

 

operation is selected. The Left and Right    

 

 

buttons are not used. [Factory Default]

The Factory Default parameters shown on this page are for the 

latest default firmware. Please contact Innotech or your local 

distributor for details on other Firmware Versions.