DS 13.01

September 2013

Overview

The ICS series Control Stations form part of the Maxim & Genesis 

Direct Digital Controller range and provide a simple unitary 

Human Machine Interface (HMI).  The HMI offers on/off, setpoint 

and fan speed control.  The HMI is powered by 24VAC and 

connects directly to the Globals Comms network.

Each ICS can communicate with a designated controller on 

the network.  The ICS units are configured via the Keypad, are 

compatible with most existing Innotech digital products and are 

capable of operating at both fast or slow comms.

The interface to the controller is via global transmit and receive 

blocks, the configuration simply uses the ICS address to form 

part of the unique point name.

Features

•  One numerical value input

•  One numerical value output

•  One momentary push button digital input 

•  One LED indication digital output

•  One fan speed input (ICS02 only)

•  Housed in a switchplate that mounts in standard electrical 

wall plates

•  Isolated RS485 interconnection between Innotech Controllers

•  Adjustable user input range

•  Adjustable decimal place

•  Configurable power on settings

Applications

The Innotech Control Station extends the capabilities of 

Innotech controllers by providing a numerical value output, 

numerical value input, push button digital input and a single LED 

display output for distributed control via RS-485.  

The Innotech Control Station provides a visual display of 

a control value and a means to set a parameter.  It is not 

intended for use on a large controller network as this affects the 

operation.

Installation

•  Strictly follow the guidelines when installing the Comms wiring as 

outlined in the Genesis System Comms Wiring Recommendations.

•  Mount the Innotech Control Station in a dry and clean location free of 

excess vibration.

Wiring

•  DO NOT connect 240VAC to any terminals.

•  The cable used for RS485 Comms must be shielded single twisted 

pair, 120 ohms character impedance, 36 to 45pF per metre 

capacitance between conductors.

•  The Comms cable must be organised as a bus topology.  That is, 

starting at one end, devices are connected to it until the other end 

of the cable is reached.  No “stubs” are allowed.  To connect a device 

to the cable, a cut is made in the cable at the point where the device 

is to be situated along it.  Then, the two new ends of the cable are 

wired into the device.  The shields from the two new ends are then 

terminated into the terminals marked SHLD1.  

•  Refer to the Genesis Network Installation Instructions and DS99.04 

Cabling Manual for more information. 

Approvals

The Innotech Control Station conforms to the requirements for RCM 

labelling.

ICS0x

Innotech Control Station

MODEL:

ICS01:  

ON/OFF, Set Point

ICS02:  

ON/OFF, Set Point and 3 Speed Fan

Model Number Designations

Innotech Control Station - ICS0x

Model

On/Off

Temp. 

Display

Setpoint 

Adjust

Run Status

Fan Speed

ICS01

ICS02