DS 13.01 - ICS0x - Innotech Control Station

September 2013

Program Functions Of The Innotech Control 

Station

To enter Programming mode depress and hold the 

  and        

  buttons for 5 seconds.  The display will become blank 

indicating that you are in the Programming Mode.  Release both 

keys and the display will show parameter 0.

Whilst in the programming mode the following buttons are 

active:

  

Change to the next parameter

 

Increase the current parameters value

 

 

    

 

Decrease the current parameters value

Parameter 0 - Global Address

The display will show the current GLOBAL Address of the device.

•  The range of address is 2 to 127. The default address is 2.

Parameter 1 - Maximum Input Value

The display will show the Maximum Input Value to which the 

module’s input can be set.

•  The range of Maximum Input Value is 0.0 to 99.9

•  The factory default setting is 30.0

Parameter 2 - Minimum Input Value

The display will show the Minimum Input Value to which the 

module’s input can be set.

•  The range of Minimum Input Value is 0.0 to 99.9

•  The factory default setting is 15

Parameter 3 - Decimal Places

The display will show the number of decimal places which will be 

displayed for both the input and output values.

•  The range of Decimal Places is 0 to 2

•  The factory default setting is 1

Parameter 4 - Baud Rate

The display will show an indication of the communications Baud 

Rate:

•  0 

4800 Baud

•  1 

38400 Baud

•  The factory default setting is 38400 Baud

To exit the Programming Mode depress the 

 and 

  

buttons and the new setting will be saved.

IF PARAMETER 4 IS CHANGED, POWER TO THE  ICS0x MUST BE 

RECYCLED, AFTER EXITING PROGRAMMING MODE.

Start Up Default Settings

The Innotech Control Station Module can be set to start with default 

settings for Set Point, Run Status and Fan Speed (ICS02 only).

To set the start up default settings adjust the Innotech Control Station 

to the desired Set Point, Run Status and Fan Speed (ICS02 only) and then 

press and hold the 

 and 

 buttons for 5 seconds.

The display will become blank indicating that the new default start up 

settings have been saved.

Operating Functions Of The Control Station

Numerical Output

The Innotech Control Station will display a 4-digit  value with up to 3 

decimal places.

Numerical Input

The Innotech Control Station will provide a 4-digit value with up to 3 

decimal places to Innotech controllers on the global network.

The value can be modified by pressing the  

 button to increment  by 

the least significant digit or the  

 button to decrement by the least 

significant digit.

 Digital Input Value

The 

 button on the Innotech Control Station provides 

a digital input value to the Innotech Controllers.  This operates as a 

standard momentary switch, i.e. Pressing  the 

 button produces a 

short period ON value to the controller.

Digital Output LED

The Innotech Control Station displays a digital state via the system LED 

during normal operation.  This LED, however, cannot be overridden 

whist the Digital Input Value is in a transitional state.

Fan Speed Button (ICS02 Only)

The 

  button provides means of setting a fan speed.  Pressing the

 button cycles between low/medium/high fan speeds.  This is 

indicated on the LEDs above the 

 button.  The 

 button and LEDs 

are disabled whilst the Control Station is off (ie. there is no ventilation 

only mode).