DS 13.01 - ICS0x - Innotech Control Station
September 2013
Program Functions Of The Innotech Control
Station
To enter Programming mode depress and hold the
and
buttons for 5 seconds. The display will become blank
indicating that you are in the Programming Mode. Release both
keys and the display will show parameter 0.
Whilst in the programming mode the following buttons are
active:
Change to the next parameter
Increase the current parameters value
Decrease the current parameters value
Parameter 0 - Global Address
The display will show the current GLOBAL Address of the device.
• The range of address is 2 to 127. The default address is 2.
Parameter 1 - Maximum Input Value
The display will show the Maximum Input Value to which the
module’s input can be set.
• The range of Maximum Input Value is 0.0 to 99.9
• The factory default setting is 30.0
Parameter 2 - Minimum Input Value
The display will show the Minimum Input Value to which the
module’s input can be set.
• The range of Minimum Input Value is 0.0 to 99.9
• The factory default setting is 15
Parameter 3 - Decimal Places
The display will show the number of decimal places which will be
displayed for both the input and output values.
• The range of Decimal Places is 0 to 2
• The factory default setting is 1
Parameter 4 - Baud Rate
The display will show an indication of the communications Baud
Rate:
• 0
4800 Baud
• 1
38400 Baud
• The factory default setting is 38400 Baud
To exit the Programming Mode depress the
and
buttons and the new setting will be saved.
IF PARAMETER 4 IS CHANGED, POWER TO THE ICS0x MUST BE
RECYCLED, AFTER EXITING PROGRAMMING MODE.
Start Up Default Settings
The Innotech Control Station Module can be set to start with default
settings for Set Point, Run Status and Fan Speed (ICS02 only).
To set the start up default settings adjust the Innotech Control Station
to the desired Set Point, Run Status and Fan Speed (ICS02 only) and then
press and hold the
and
buttons for 5 seconds.
The display will become blank indicating that the new default start up
settings have been saved.
Operating Functions Of The Control Station
Numerical Output
The Innotech Control Station will display a 4-digit value with up to 3
decimal places.
Numerical Input
The Innotech Control Station will provide a 4-digit value with up to 3
decimal places to Innotech controllers on the global network.
The value can be modified by pressing the
button to increment by
the least significant digit or the
button to decrement by the least
significant digit.
Digital Input Value
The
button on the Innotech Control Station provides
a digital input value to the Innotech Controllers. This operates as a
standard momentary switch, i.e. Pressing the
button produces a
short period ON value to the controller.
Digital Output LED
The Innotech Control Station displays a digital state via the system LED
during normal operation. This LED, however, cannot be overridden
whist the Digital Input Value is in a transitional state.
Fan Speed Button (ICS02 Only)
The
button provides means of setting a fan speed. Pressing the
button cycles between low/medium/high fan speeds. This is
indicated on the LEDs above the
button. The
button and LEDs
are disabled whilst the Control Station is off (ie. there is no ventilation
only mode).