© MASS ELECTRONICS Pty Ltd 2006
Models:
GENII MZS REM:
Multi-zone Station Remote Expansion Module
DS 15.11
August 2013
GENII MZS REM
Multi-zone Station Remote Expansion Module
Applications
Expands GENESIS Controller capabilities by providing a numeric output
display, numerical value input, a single toggle digital input switch and
single LED display output for distributed control via RS485.
The GENII MZS REM Module provides a visual display of up to 6 control
values and a means to set up to 6 parameters.
Application Notes
A GENESIS Controller must have version 4 firmware installed to support
REM Modules. Version 4.0 or higher Config Software must be used to
configure a GENESIS Digital Controller that has REM Modules connected
to it.
One GENESIS Controller can have up to 15 GENII MZS REM Modules*
connected to it via the REM comms bus.
For detailed connection information to the pre-version 5 GENESIS
Digital Controller Family, please refer to DS 99.03
Overview
The Innotech GENII MZS REM Multi-zone Station Module is an
expansion device for the GENESIS range of Digital Controllers.
The module is powered by 24VAC and provides a limited User
Interface to the GENESIS Controller. There are no physical
connections between field equipment and the GENII MZS REM,
all input/output values are edited and viewed on the wall unit.
The GENII MZS REM may be located remotely from the GENESIS
Controller providing a distributed User Interface for the system.
The GENII MZS REM communicates with the Genesis Controller
via the REM Comms port. The remote link uses RS-485 at a baud
rate of 38400. For pre-Version 5 controllers, a Gen II RMI Remote
Module Interface is required.
Please refer to DS 15.01 for further information.
Features
• One three decimal place numerical value input.
• One three decimal place numerical output.
• One toggle digital input.
• One LED digital display output.
• One ‘current zone’ input.
• Housed in a switchplate that mounts in standard electrical
wall plates.
• RS485 interconnection between REM Modules.
• 24VAC operation.
• Wiring Diagrams for modules generated by GEN2Config
Software.
• Adjustable user input range.
• Configurable power on settings.
• Display Auto Dim when lights out.
• LED indication of network traffic on rear to ease debugging &
setup.
Approvals
The GENII MZS REM conforms to:
• EN 55011 Class B Group 1 & AS/NZS 2064:1997 for RCM
Labelling
• FCC Title 47 CFR, Part 15 Class A for FCC Marking
• UL listed to UL916, File Number E242628