background image

© MASS ELECTRONICS Pty Ltd  2006

Models:

GENII MZS REM: 

Multi-zone Station Remote Expansion Module

DS 15.11

August 2013

  

GENII MZS REM

Multi-zone Station Remote Expansion Module

Applications

Expands GENESIS Controller capabilities by providing a numeric output 

display, numerical value input, a single toggle digital input switch and 

single LED display output for distributed control via RS485. 

The GENII MZS REM Module provides a visual display of up to 6 control 

values and a means to set up to 6 parameters.

Application Notes

A GENESIS Controller must have version 4 firmware installed to support 

REM Modules. Version 4.0 or higher Config Software must be used to 

configure a GENESIS Digital Controller that has REM Modules connected 

to it.

One GENESIS Controller can have up to 15 GENII MZS REM Modules* 

connected to it via the REM comms bus.

For detailed connection information to the pre-version 5 GENESIS 

Digital Controller Family, please refer to DS 99.03

Overview

The Innotech GENII MZS REM Multi-zone Station Module is an 

expansion device for the GENESIS range of Digital Controllers.

The module is powered by 24VAC and provides a limited User 

Interface to the GENESIS Controller. There are no physical 

connections between field equipment and the GENII MZS REM, 

all input/output values are edited and viewed on the wall unit.

The GENII MZS REM may be located remotely from the GENESIS 

Controller providing a distributed User Interface for the system.

The GENII MZS REM communicates with the Genesis Controller 

via the REM Comms port. The remote link uses RS-485 at a baud 

rate of 38400. For pre-Version 5 controllers, a Gen II RMI Remote 

Module Interface is required. 

Please refer to DS 15.01 for further information.

Features

•  One three decimal place numerical value input.

•  One three decimal place numerical output.

•  One toggle digital input.

•  One LED digital display output.

•  One ‘current zone’ input.

•  Housed in a switchplate that mounts in standard electrical 

wall plates.

•  RS485 interconnection between REM Modules.

•  24VAC operation.

•  Wiring Diagrams for modules generated by GEN2Config 

Software.

•  Adjustable user input range.

•  Configurable power on settings.

•  Display Auto Dim when lights out.

•  LED indication of network traffic on rear to ease debugging & 

setup.

Approvals

The GENII MZS REM conforms to:

•  EN 55011 Class B Group 1 & AS/NZS 2064:1997 for RCM 

Labelling

•  FCC Title 47 CFR, Part 15 Class A for FCC Marking

•  UL listed to UL916, File Number E242628