Inkbird Tech. Co., Ltd. www.ink
6.2.1 Temperature setting Range
When controller works normally,
automatically switch working modes of cooling and heating.
When TR=0
Under normal temperature control mode, w
(
Temperature Set Value
)
mode with cooling indicator lamp
Indicator Light flickering
protection; when measured temperature
indicator light off, cooling relay stop wor
When measured temperature
Differential Value)
, entering into
heating relay start working; when measured temperature
Value
), heating indicator light
For example, Set TS=25.0
, CD=2.0
, HD=3.0
: if measured temperature
℃
℃
℃
≥27.0
(TS+CD), cooling will turn on; if measured temperature ≤25.0
, cooling will turn
℃
℃
off.
If measured temperature ≤22.0
(TS
℃
≥25.0
, heating will turn off.
℃
NOTE:
When TR=0, under plug in or exit setting mode, no need to compare the current measured
temperature with the heating or cooling differential values but only compare directly with
the TS value.
For example, when plug in or exit setting mode, Set TS=25.0
measured temperature
>
TS(25.0
cooling will turn off and then return to normal temperature control mode.
If measured temperature
<
≥25.0
℃
, heating will turn off and then return to normal temperature control mode.
When TR=1 (Continuous Timer mode)
With this setting, the TS(temperature set value) will be
based on the setting values of S01~S12, H01~H12 and U01~U12.
For example, when periods of time within the range of the control duration of H01, if
measured temperature PV≥(Temperature Set Value )TS1+(Cooling Differenti
then cooling on with cooling indicator light on and cooling relay start working.
About the condition that the interval time between two refrigeration operations shorten
than PT(compressor delay time), please note 6.2.3.
When TR=2 (Target Timer mode)
ITC-310T
Inkbird Tech. Co., Ltd. www.ink
13
Range (TS, HD, CD)
When controller works normally, PV screen displays current measuring temperature,
working modes of cooling and heating.
Under normal temperature control mode, when measured temperature
PV ≥ TS
)
+ CD
(
Cooling Differential Value
), entering into
cooling indicator lamp on and cooling relay start working; when the
flickering
, cooling device is being in the status of compressor delay
hen measured temperature
PV ≤ TS
(
Temperature Set Value
off, cooling relay stop working.
When measured temperature
PV ≤TS (Temperature Set Value)-HD (Heating
, entering into heating mode with heating indicator light
heating relay start working; when measured temperature
PV ≥ TS
(
Temperature Set
light off, heating relay stop working.
For example, Set TS=25.0
, CD=2.0
, HD=3.0
: if measured temperature
℃
℃
℃
≥27.0
(TS+CD), cooling will turn on; if measured temperature ≤25.0
, cooling will turn
℃
℃
If measured temperature ≤22.0
(TS
℃
-HD), heating will turn on; if measured temperature
≥25.0
, heating will turn off.
℃
hen TR=0, under plug in or exit setting mode, no need to compare the current measured
temperature with the heating or cooling differential values but only compare directly with
For example, when plug in or exit setting mode, Set TS=25.0
℃
, CD=2.0
℃
, HD=3.0
TS(25.0
℃
), cooling will turn on; if measured temperature ≤25.0
cooling will turn off and then return to normal temperature control mode.
<
TS(22.0
℃
), heating will turn on; if measured temperature
, heating will turn off and then return to normal temperature control mode.
When TR=1 (Continuous Timer mode)
With this setting, the TS(temperature set value) will be invalid and the controller will work
based on the setting values of S01~S12, H01~H12 and U01~U12.
For example, when periods of time within the range of the control duration of H01, if
measured temperature PV≥(Temperature Set Value )TS1+(Cooling Differenti
then cooling on with cooling indicator light on and cooling relay start working.
About the condition that the interval time between two refrigeration operations shorten
than PT(compressor delay time), please note 6.2.3.
er mode)
310T User Manual
Inkbird Tech. Co., Ltd. www.ink-bird.com
displays current measuring temperature,
PV ≥ TS
), entering into cooling
hen the
Cooling
, cooling device is being in the status of compressor delay
Temperature Set Value
), cooling
HD (Heating
light on and
Temperature Set
For example, Set TS=25.0
, CD=2.0
, HD=3.0
: if measured temperature
℃
℃
℃
≥27.0
(TS+CD), cooling will turn on; if measured temperature ≤25.0
, cooling will turn
℃
℃
will turn on; if measured temperature
hen TR=0, under plug in or exit setting mode, no need to compare the current measured
temperature with the heating or cooling differential values but only compare directly with
, HD=3.0
℃
: if
), cooling will turn on; if measured temperature ≤25.0
℃
,
), heating will turn on; if measured temperature
, heating will turn off and then return to normal temperature control mode.
invalid and the controller will work
For example, when periods of time within the range of the control duration of H01, if
measured temperature PV≥(Temperature Set Value )TS1+(Cooling Differential Value) CD,
then cooling on with cooling indicator light on and cooling relay start working.
About the condition that the interval time between two refrigeration operations shorten