6.2.1 Temperature setting Range 

When controller works normally, 

automatically switch working modes of cooling and heating.

 

When TR=0 

Under normal temperature control mode, w

(

Temperature Set Value

mode with cooling indicator lamp

Indicator Light  flickering

protection; when measured temperature 

indicator light off, cooling relay stop wor

When measured temperature 

Differential Value)

, entering into

heating relay start working; when measured temperature 

Value

), heating indicator light

 

For example, Set TS=25.0

, CD=2.0

, HD=3.0

: if measured temperature 

≥27.0

(TS+CD), cooling will turn on; if measured temperature ≤25.0

, cooling will turn 

off. 

If measured temperature ≤22.0

(TS

≥25.0

, heating will turn off.

 

NOTE:

  

When TR=0, under plug in or exit setting mode, no need to compare the current measured 

temperature with the heating or cooling differential values but only compare directly with 

the TS value. 

For example, when plug in or exit setting mode, Set TS=25.0

measured temperature

TS(25.0

cooling will turn off and then return to normal temperature control mode.

If measured temperature 

≥25.0

, heating will turn off and then return to normal temperature control mode.

 

When TR=1 (Continuous Timer mode)

With this setting, the TS(temperature set value) will be

based on the setting values of S01~S12, H01~H12 and U01~U12.

For example, when periods of time within the range of the control duration of H01, if 

measured temperature PV≥(Temperature Set Value )TS1+(Cooling Differenti

then cooling on with cooling indicator light on and cooling relay start working.

About the condition that the interval time between two refrigeration operations shorten 

than PT(compressor delay time), please note 6.2.3.

 

When TR=2 (Target Timer mode)

 

 

 

ITC-310T

Inkbird Tech. Co., Ltd.                                                                        www.ink

13 

Range (TS, HD, CD) 

When controller works normally, PV screen displays current measuring temperature,

working modes of cooling and heating. 

Under normal temperature control mode, when measured temperature 

PV ≥ TS

+ CD

 (

Cooling Differential Value

), entering into

cooling indicator lamp on and cooling relay start working; when the 

flickering

, cooling device is being in the status of compressor delay 

hen measured temperature 

PV ≤ TS 

(

Temperature Set Value

off, cooling relay stop working. 

When measured temperature 

PV ≤TS (Temperature Set Value)-HD (Heating 

, entering into heating mode with heating indicator light 

heating relay start working; when measured temperature 

PV ≥ TS

 (

Temperature Set 

light off, heating relay stop working. 

For example, Set TS=25.0

, CD=2.0

, HD=3.0

: if measured temperature 

≥27.0

(TS+CD), cooling will turn on; if measured temperature ≤25.0

, cooling will turn 

If measured temperature ≤22.0

(TS

-HD), heating will turn on; if measured temperature 

≥25.0

, heating will turn off.

 

hen TR=0, under plug in or exit setting mode, no need to compare the current measured 

temperature with the heating or cooling differential values but only compare directly with 

For example, when plug in or exit setting mode, Set TS=25.0

, CD=2.0

, HD=3.0

TS(25.0

), cooling will turn on; if measured temperature ≤25.0

cooling will turn off and then return to normal temperature control mode. 

TS(22.0

), heating will turn on; if measured temperature 

, heating will turn off and then return to normal temperature control mode.

When TR=1 (Continuous Timer mode) 

With this setting, the TS(temperature set value) will be invalid and the controller will work 

based on the setting values of S01~S12, H01~H12 and U01~U12. 

For example, when periods of time within the range of the control duration of H01, if 

measured temperature PV≥(Temperature Set Value )TS1+(Cooling Differenti

then cooling on with cooling indicator light on and cooling relay start working.

About the condition that the interval time between two refrigeration operations shorten 

than PT(compressor delay time), please note 6.2.3. 

er mode) 

310T User Manual

 

Inkbird Tech. Co., Ltd.                                                                        www.ink-bird.com

 

displays current measuring temperature, 

PV ≥ TS

 

), entering into cooling 

hen the 

Cooling 

, cooling device is being in the status of compressor delay 

Temperature Set Value

), cooling 

HD (Heating 

light on and 

Temperature Set 

For example, Set TS=25.0

, CD=2.0

, HD=3.0

: if measured temperature 

≥27.0

(TS+CD), cooling will turn on; if measured temperature ≤25.0

, cooling will turn 

will turn on; if measured temperature 

hen TR=0, under plug in or exit setting mode, no need to compare the current measured 

temperature with the heating or cooling differential values but only compare directly with 

, HD=3.0

: if 

), cooling will turn on; if measured temperature ≤25.0

 

), heating will turn on; if measured temperature 

, heating will turn off and then return to normal temperature control mode. 

invalid and the controller will work 

For example, when periods of time within the range of the control duration of H01, if 

measured temperature PV≥(Temperature Set Value )TS1+(Cooling Differential Value) CD, 

then cooling on with cooling indicator light on and cooling relay start working. 

About the condition that the interval time between two refrigeration operations shorten 

Содержание ITC-310T-B

Страница 1: ...User Manual Version 1 0 Inkbird Tech Co Ltd 2016 Inkbird Tech Co Ltd All rights reserved No part of this document may be reproduced Inkbird has made every effort to ensure that the information contai...

Страница 2: ...ture Set Values 6 2 7 Cycle and Auto Mode MD AT 7 Error Description Sensor fault alarm 8 Technical Assistance and Warranty 8 1 Technical Assistance 8 2 Warranty ITC 310T Inkbird Tech Co Ltd www ink 2...

Страница 3: ...in injury due to electric shock Do not allow pieces of metal wire clippings or fine metallic shaving or filings from on to enter the product Doing so may occasionally result in electric shock Do not u...

Страница 4: ...control heating pump constant temperature cycle strain culture fermentation seed sprouting electric temperature protection and automatic temperature control ectrical equipment etc product with dual r...

Страница 5: ...0 0 70 2 58 158 On Off Control Heating and Cooling 1 999 min hr 1 90 day 24hour 1 7s Max 12 periods 1 999 times cycle or 00 infinite cycle 100 240VAC 50Hz 60Hz Current Max 10A Voltage 100 240V AC Powe...

Страница 6: ...ge of the operating Under setting mode press this DOWN button can ng value Under running mode when TR 1 or 2 press this button can view the Under setting mode press this UP button can increase the set...

Страница 7: ...eturn to normal temperature displaying mode after 3 seconds 5 2 How to Set Parameters When controller works normally press and hold SET key for more than 3 seconds to ify parameter mode SET indicator...

Страница 8: ...Inkbird Tech Co Ltd www ink 5 3 Setup Flow Chart ITC 310T Inkbird Tech Co Ltd www ink 8 310T User Manual Inkbird Tech Co Ltd www ink bird com...

Страница 9: ...ink 9 nstruction perature Control Setting When setting temperature in Centigrade Function Setting Range Default Setting Temperature Set Value 50 0 120 25 0 Heating Differential Value 0 3 15 0 2 0 Cool...

Страница 10: ...Default Sett Time Unit Setting D H M D Cycle Setting Mode 0 999 1 Auto Mode 0 or 1 0 Stage Setting Value 1 12 1 Start Stage Setting Value 1 12 1 Function Setting Range Default Setting emperature Set...

Страница 11: ...ch Co Ltd www ink 11 menu codes as below chart Function Default Setting Stage 1 Temperature Set Value 25 0 or 77 0 Same setting range as TS Control Duration 10 Finished Alarm of Stage 1 n Stage 2 Temp...

Страница 12: ...Alarm of Stage ITC 310T Inkbird Tech Co Ltd www ink 12 Control Duration 10 Finished Alarm of Stage 7 n Stage 8 Temperature Set Value 25 0 or 77 0 Control Duration 10 Finished Alarm of Stage 8 n Stage...

Страница 13: ...when measured temperature PV TS Temperature Set light off heating relay stop working For example Set TS 25 0 CD 2 0 HD 3 0 if measured temperature 27 0 TS CD cooling will turn on if measured temperatu...

Страница 14: ...Value TS1 Cooling Differential Value CD then cooling on with cooling indicator light on and cooling relay start working NOTE The control duration of each stage start timing only when the current tempe...

Страница 15: ...6 37 38 39 ITC 310T Inkbird Tech Co Ltd www ink 15 30 2 22 30 2 24 30 2 26 32 3 28 34 3 30 35 3 30 35 3 30 35 3 30 35 3 30 35 3 30 35 3 30 35 3 32 35 3 34 35 3 35 35 3 35 35 35 35 35 35 35 35 35 35 35...

Страница 16: ...eached the set temperature of current stage and total time of 5 14 19 25 and 6 2 2 Alarm High Low Limit Setting AH AL When measured temperature PV AH alarm with BI BI BIII sound until the AH or press...

Страница 17: ...When TR 0 timer function will be off there will not display the other set values follow TR and no need to set hem when TR 1 or TR 2 timer function will be activated user can set the time and the cont...

Страница 18: ...y in every 2 seconds with all output control turned off only by pressing any button will go to next stage control 6 2 7 Cycle and Auto Mode MD AT the operation time of timer and temperature set values...

Страница 19: ...tat for one years from the date of purchase when operated under normal condition by the original purchaser not transferable against defects caused by INKBIRD s workmanship or materials This warranty i...

Отзывы: