User’s manual
Using the Control Panel
7
Chapter 2
Using the Control Panel
2.1
For authorized persons
Attention:
Insert and turn the key. The panel will enable access level 2. The panel will hold level 2
status for 30 seconds.
2.2
Danger signaling
Note:
In the event of fire hazard, always follow the fire department approved fire drill.
2.2.1
For building occupants
2.2.2
For authorized persons
To force the panel into alarm status, regardless of its status, press
EVACUATE
.
ALARM LED on
Evacuate the building immediately.
PRE-ALARM LED
on
In the event of real danger, press the
EVACUATE
button to broadcast the alarm and
evacuate the building immediately. Or, if you consider evacuation to be an unnecessary
measure, inform the person/s in charge of the safety of the building and its occupants
immediately. To silence the beeper, press
SILENCE
.
ALARM/PRE-
ALARM/RESET
LED on
At least one zone is in alarm/pre-alarm status:
• If there is no intervention during a pre-alarm, the panel will generate an alarm
when the pre-set pre-alarm time expires.
• To request investigation time, press
INVESTIGATE
and check the building.
Investigation time cannot be refreshed.
• In the event of a false alarm, press
SILENCE
. The panel beeper and the
silenceable outputs will be silenced until a new event occurs. If the panel is
operating in Night mode, the panel beeper and the silenceable outputs will be
unsilenced automatically after the pre-set time, and the panel will generate
pre-alarm status.
• If you wish to re-activate pre-alarm/alarm status after pressing the
SILENCE
button, press the
SILENCE
button again: pre-alarm/alarm signaling and the
outputs will re-activate.
• To clear all alarm/fault signaling and the memory, press
RESET
. If the
conditions persist, the panel will generate another alarm.
SILENCED LED
on
Indicates that the control panel has been silenced but has not yet been reset.
RESET LED on
The control panel is in alarm or pre-alarm status, you must press
SILENCE
before
pressing
RESET
.