4.1 Wireless terminal parameters
4. Programming wireless terminal
The programming of a wireless terminal can only be done through the control panel programming software.
On accessing the software, it is necessary to open a solution, configuration of the real system to be
designed. Successively a terminal previously configured or to be configured as “wireless” must be selected.
After which it will be possible to access the device programming in order to select or change the device type
and its parameters.
4.1 Wireless terminal parameters
Use detector
LED
The red LED on the device provides visual signalling of alarm or tamper conditions on the device itself.
This option must be enabled on all the terminals of the device.
Bypass tamper
This option disables open/dislodgement tamper signalling.
Disable wireless
monitoring
Enabling this option (disabled at default), disables wireless monitoring on the detector.
In the event of the loss of the specific detector, no event will be generated and no fault signal will be signalled
on the keypad.
Disable detector
on partition dis-
arming
In order to increase battery life, the PIR detector will deactivate when the partitions it belongs disarm and
activate when the partitions it belongs to arm.
When the detector is deactivated it will not generate alarms.
From the moment the partitions arm, there may be a delay of up to 3 minutes before the detector receives the
activation command.
Alarm pulses
This is the number of pulses (each lasting as long as the programmed “Alarm pulse duration”) necessary to
generate a zone alarm event.
If this value is more than 1, you must also program the “Multi-pulse time” parameter.
Multi-pulse time
This parameter applies only when the “Alarm pulse num.” is higher than 1.
This is the window during which a number of alarm pulses must be detected (each lasting as long as the pro-
grammed “Alarm pulse duration”) equal to the value programmed for “Alarm pulses” in order for the system
to generate an alarm.
This time window can be expressed in seconds or minutes.
Alarm pulse dur-
ation
This is the length of time (after detection of alarm conditions) the zone will allow before generating an alarm.
Expressed in multiples of 15 milliseconds or minutes.
Selection of the
magnetic reed
contact
Magnet long side - for detection on the long side of the magnetic contact.
Magnet short side - for detection on the short side of the magnetic contact.
Both magnets - for detection on at least one side of the magnetic contact.
Tamper on inact-
ive reed relay
Detects magnetic-contact tamper when both reeds are in standby status.
Broadcast RF
This option assures the activation/deactivation of the output within 2 seconds of the control panel command.
Valid for terminals T1 and T2 configured as outputs.
4.2 Real-time
For each configured device the software provides a direct software-to-device connection which allows visu-
alization of the real-time values of the following features of the wireless sounder: