94
DC connection
Ingeteam
ABS2011IQM01_G - Installation and Operation Manual
Fuses recommended for PV-
Maximum string power Impp
Fuse
Phoenix Contact fuse reference
13 A
25 A
PV-PRO/M/F-200/F-1500/20
15 A
9.3. DC connection process
9.3.1. STD Version
With the switch OFF and the AC cables without voltage, open the unit’s lower compartment.
1. Uninstall the polycarbonate guard.
2. Follow the steps below according to the cable diameter.
Option 1. Cable diameter 12 ~ 20 mm: cables pass through M40 packing gland
a. Ensure that the spade terminal dimensions allow it to pass through the M40 packing gland.
b. Fit the spade terminal on the cable.
c. Loosen the head of the M40 packing gland and remove the cap.
d. Pass the power cables through the M40 packing gland, using the diameter reducer provided.
e. Place each terminal in its terminal block, respecting the polarity, and tighten the packing gland head to
ensure the sealing.
Option 2. Cable diameter 20 ~ 28 mm: cables pass through M40 cable grommet membrane
a. Remove the M40 packing gland.
b. Install the cable grommet membrane in the hole.
c. Fit the spade terminal on the cable.
d. Pass the cables through the M40 membrane (a soapy solution can be used).
e. Place each terminal in its terminal block respecting the polarity.
Option 3. Cable diameter 28 ~ 35 mm: cables pass through M50 cable grommet membrane
a. Remove the M50 caps.
b. Install the cable grommet membrane in the hole.
c. Fit the spade terminal on the cable.
d. Pass the cables through the M50 membrane (a soapy solution can be used).
Содержание INGECON SUN 3Play 100TL
Страница 3: ...3 Ingeteam ABS2011IQM01_G Deutsch DE English EN Español ES Français FR Italiano IT Português PT ...
Страница 60: ...Anmerkungen Notes Notas Remarques Note Notas ...
Страница 170: ...Anmerkungen Notes Notas Remarques Note Notas ...
Страница 226: ...Anmerkungen Notes Notas Remarques Note Notas ...
Страница 336: ...Ingeteam Power Technology S A www ingeteam com ABS2011IQM01_G 09 2021 ...