
ABQ2026IQE01_A - Installation and Operation Manual
1. Connect the grounded pole of each unit through a 35 mm
2
section cable with 1000/1500 V insulation.
This connection can be done through the cable grommets provided in the bases of the units in question.
Inverter 1
Inverter 2
2. Connect the CAN communication buses from both inverters using the cable provided. To connect the
communication buses, carry out the following process:
Inverter 1
CAN
Inverter 2
On the inverter where the grounding kit (-TSGND) is being installed, remove the end of line resistor
from the wiring between -X26.3D and -X26.4D and connect the CAN cable with the color code
described in the diagram to -X26.1C, -X26.2C, -X26.3C, -X26.4C.
70
Connection of the PV array grounding kit [optional]
Ingeteam
Содержание INGECON SUN 1170TL
Страница 1: ...INGECON SUN PowerMax TL B 1500 Vdc Installation and Operation Manual...
Страница 22: ...ABQ2026IQE01_A Installation and Operation Manual DC supply 22 Unit description Ingeteam...
Страница 174: ...Notes...
Страница 176: ...ABQ2026IQE01_A 05 2019 Ingeteam Power Technology S A www ingeteam com...