ABQ2026IQE01_A - Installation and Operation Manual
19.6.4. Settings
In this menu you can make the following settings:
Date & time
To modify the date and time of the inverter.
Languages
Selection of the language for the text on the inverter display.
Modbus ID
Assignation of a number that identifies the inverter. In installations with more than one
inverter, each one must be assigned a different number. Ingeteam recommends using
correlative numbering.
Partial deletion
Deletes the partial meters.
Strings settings
Not applicable.
Power settings
Reduce the unit power.
Test fans
By accessing this option it is possible to run a test to check the inverter fans are working
properly.
Autotest
This menu is only available when the standard selected is
CEI 0-21 SPI INTERNO,
CEI-0-16
or
DEWA INTEGRATED IPS
.
The autotest enables an automatic verification of the grid voltage and frequency limits,
bringing these limits toward the real value of the measurement and ensuring that the
unit disconnects in the set time when the measurement does not comply with the limit.
Local command
This menu is only available when the standard selected is
CEI 0-21 SPI INTERNO,
CEI-0-16
or
DEWA INTEGRATED IPS
.
From this menu you can change the bottom and top frequency limits. These limits must
correspond to the selected standard.
19.6.5. Autotest
Autotest allows for the grid voltage and frequency limits to be tested automatically, checking that the unit
disconnects correctly within the time set by standard. This menu is only available for some standards, such as
CEI
0-21 SPI INTERNO, CEI-0-16
or
DEWA INTEGRATED IPS
.
During autotest, the disconnection time of the following protections is tested:
Fmax (81>.S1)
Lowest upper limit of the frequency protection.
Fmin (81<.S1)
Highest lower limit of the frequency protection.
Fmax (81>.S2)
Highest upper limit of the frequency protection.
Fmin (81<.S2)
Lowest lower limit of the frequency protection.
Vmax (59.S1)
Lowest upper limit of the voltage protection.
Vmax (59.S2)
Highest upper limit of the voltage protection.
Vmin (27.S2)
Lower limit of the voltage protection.
There are three different states:
Non eseguito
No autotest running and none has been performed during the time in which the inverter has
been switched on.
Riconnessione
State awaiting reconnection for the next measurement after an Fmax, Fmin, Vmax or Vmin
check.
Completato
A full autotest has been carried out during the time in which the inverter has been switched on.
Press on
Avviare Autotest
to start autotest. Access
Risultati
to consult the results of the different tests, observing whether the result is
correct or incorrect. An autotest can be stopped when running by pressing
on
Eseguire Autotest
.
The results screens for an autotest are then displayed if the test has been completed and a second case in which
the test has not been completed:
132
Display control
Ingeteam
Содержание INGECON SUN 1170TL
Страница 1: ...INGECON SUN PowerMax TL B 1500 Vdc Installation and Operation Manual...
Страница 22: ...ABQ2026IQE01_A Installation and Operation Manual DC supply 22 Unit description Ingeteam...
Страница 174: ...Notes...
Страница 176: ...ABQ2026IQE01_A 05 2019 Ingeteam Power Technology S A www ingeteam com...