![Ingersoll-Rand YZC036E Скачать руководство пользователя страница 17](http://html1.mh-extra.com/html/ingersoll-rand/yzc036e/yzc036e_installation-operation-and-maintenance-manual_2059252017.webp)
Installation
RT-SVX46C-EN
17
Table 1.
Maximum base unit & corner weights (lbs) and center of gravity dimensions (in.) - gas/electric models
Unit
Maximum Base
Model Weights
(a)
Corner Weights
(b)
Center of Gravity (in.)
Tons
Model No.
Shipping
Net
A
B
C
D
Length
Width
3
YZC036E
690
615
154
196
73
192
33
19
4
YZC048F
848
753
196
258
126
173
40
23
5
YZC060E
949
854
200
293
121
240
40
23
(a) Weight are approximate for 1st 10 digit model number.
(b) Corner weights are given for information only.
Figure 9.
Rigging and center of gravity
Attach chain or
cable to clevis
Clevis
Center of Gravity Length
Center of Gravity
Width
A
B
C
D
Table 2.
Factory installed options (fiops)/accessory net weights (lbs)
(a),(b)
T/YZC036E
T/YZC048F, 060E
Net Weight
Net Weight
Accessory
3 Tons
4,5 Tons
460V IDM and ODM Transformer
(c)
32
39
Barometric Relief
7
10
Coil Guards
12
20
Economizer
26
36
Electric Heaters
(d)
15
30
Hinged Doors
10
12
Low Leak Economizer
68
93
Powered Convenience Outlet
(e)
38
38
Powered Exhaust
40
40
Roof Curb
61
78
Smoke Detector, Supply
5
5
Smoke Detector, Return
7
7
Stainless Steel Heat Exchanger
(f)
4
6
Through the Base Electrical
8
13
Through the Base Gas
5
5
Unit Mounted Circuit Breaker
5
5
Unit Mounted Disconnect
5
5
(a) Weights for options not listed are <5 lbs.
(b) Net weight should be added to unit weight when ordering factory-installed accessories.
(c) Apply weight with all 460V units.
(d) Applicable to Cooling units only.
(e) Available for 208/230V units only.
(f) Applicable to Gas/Electric units only.