Troubleshooting

ReliaTel Control

The RTRM has the ability to provide the service personnel 
with some unit diagnostics and system status information.

Before turning the main power disconnect switch “Off”, 
follow the steps below to check the ReliaTel™ 
Refrigeration Module (RTRM). All diagnostics and system 
status information stored in the RTRM will be lost when 
the main power is turned “Off”.

To prevent injury or death from electrocution, it is the 
responsibility of the technician to recognize this hazard 
and use extreme care when performing service 
procedures with the electrical power energized.

1.

Verify that the Liteport LED on the RTRM is burning 
continuously. If the LED is lit, go to 

Step 3

.

2. If the LED is not lit, verify that 24 Vac is presence 

between J1-1 and J1-2. If 24 Vac is present, proceed to 

Step 3

.

If 24 Vac is not present, check the unit main power 
supply, check transformer (TNS1). Proceed to 

Step 3

 if 

necessary.

3. Utilizing “Method 1” or “Method 2” in the “System 

Status Checkout Procedure, check the following: 

System status

Heating status

Cooling status

If a System failure is indicated, proceed to 

Step 4

. If no 

failures are indicated, proceed to 

Step 5

.

4. If a System failure is indicated, recheck 

Step 1

 and 

Step 

2

. If the LED is not lit in 

Step 1

, and 24 Vac is present in 

Step 2

, the RTRM has failed. Replace the RTRM.

5. If no failures are indicated, use one of the TEST mode 

procedures described in 

“Start Up,” p. 38

 to start the 

unit. This procedure will allow you to check all of the 
RTRM outputs, and all of the external controls (relays, 
contactors, etc.) that the RTRM outputs energize, for 
each respective mode. Proceed to 

Step 6

.

6. Step the system through all of the available modes, 

and verify operation of all outputs, controls, and 
modes. If a problem in operation is noted in any mode, 
you may leave the system in that mode for up to one 
hour while troubleshooting. Refer to the sequence of 
operations for each mode, to assist in verifying proper 
operation. Make the necessary repairs and proceed to 

Step 7

 and 

Step 8

.

7.

If no abnormal operating conditions appear in the test 
mode, exit the test mode by turning the power “Off” at 
the main power disconnect switch.

8. Refer to the individual component test procedures if 

other microelectronic components are suspect.

System Status Checkout 
Procedure

“System Status” is checked by using one of the following 
two methods:

Method 1

If the Zone Sensor Module (ZSM) is equipped with a 
remote panel with LED status indication, you can check the 
unit within the space. If the ZSM does not have LEDs, use 

“Method 2,” p. 46

.

BAYSENS110* and BAYSENS119* have the remote panel 
indication feature.

The LED descriptions are listed below.

LED 1 (System) 

“On” during normal operation. 

“Off” if a system failure occurs or the LED fails. 

“Flashing” indicates test mode.

LED 2 (Heat)

“On” when the heat cycle is operating.

“Off” when the heat cycle terminates or the LED 
fails.

“Flashing” indicates a heating failure.

LED 3 (Cool)

“On” when the cooling cycle is operating.

“Off” when the cooling cycle terminates or the LED 
fails.

“Flashing” indicates a cooling failure.

LED 4 (Service)

WARNING

Hazardous Service Procedures!

The maintenance and troubleshooting procedures 
recommended in this section of the manual could result 
in exposure to electrical, mechanical or other potential 
safety hazards. Always refer to the safety warnings 
provided throughout this manual concerning these 
procedures. Unless specified otherwise, disconnect all 
electrical power including remote disconnect and 
discharge all energy storing devices such as capacitors 
before servicing. Follow proper lockout/tagout 
procedures to ensure the power can not be 
inadvertently energized. When necessary to work with 
live electrical components, have a qualified licensed 
electrician or other individual who has been trained in 
handling live electrical components perform these 
tasks. Failure to follow all of the recommended safety 
warnings provided, could result in death or serious 
injury.

Содержание YH*150

Страница 1: ...ing Improperly installed adjusted or altered equipment by an unqualified person could result in death or serious injury When working on the equipment observe all precautions in the literature and on t...

Страница 2: ...TION Warnings Cautions and Notices appear at appropriate sections throughout this literature Read these carefully WARNING Indicates a potentially hazardous situation which if not avoided could result...

Страница 3: ...this manual and following the instructions the risk of improper operation and or component damage will be minimized It is important that periodic maintenance be performed to help assure trouble free o...

Страница 4: ...Smoke Detector 33 Through the Base Gas Utility Option 36 Pre Start 37 Test Modes 37 Verifying Proper Air Flow Units with Belt Drive Indoor Fan 37 Start Up 38 Economizer Start Up 38 Compressor Start Up...

Страница 5: ...ndard Motor w Shaft Grounding Ring C Single Zone Variable Air Volume Oversized Motor w Shaft Grounding Ring D Multi Speed Oversized Motor w Shaft Grounding Ring E VAV Supply Air Temperature Control St...

Страница 6: ...Through the Base Options 9 ReliaTel Options Module is required when ordering the following accessories Clogged Filter Switch Fan Fail Switch Condensate Overflow Switch Discharge Air Sensing Kit Frost...

Страница 7: ...the installation instruction that ships with each kit when field installation is necessary RLCI ReliaTel LonTalk Communication Interface Optional This module is used when the application calls for an...

Страница 8: ...during compressor operation the compressor for that circuit is immediately turned Off The compressor will not be allowed to restart for a minimum of 3 minutes should the contacts close If four consec...

Страница 9: ...th a Trane Integrated Comfort building management system Remote Zone Sensor BAYSENS074 This electronic sensor features single setpoint capability and timed override with override cancellation It is us...

Страница 10: ...ream or return air stream the air velocity entering the smoke detector unit must be between 500 and 4000 feet per minute Equipment covered in this manual will develop an airflow velocity that falls wi...

Страница 11: ...h soap and warm water after handling Storage Take precautions to prevent condensate from forming inside the unit s electrical compartments and motors if The unit is stored before it is installed or Th...

Страница 12: ...12 RT SVX26J EN Unit Dimensions Figure 1 Typical installation clearance for single and multiple unit applications 5 8 5 0...

Страница 13: ...nal data for 12 tons standard efficiency units 2710 mm 106 11 16 1273 mm 50 1 8 168 mm 6 5 8 651 mm 25 5 8 1799 mm 70 13 16 213 mm 8 3 8 745 mm 29 5 16 68 mm 2 11 16 25 mm 1 1453 mm 57 3 16 152 mm 6 S...

Страница 14: ...Unit dimensional data 15 25 tons standard efficiency units 3091 mm 121 11 16 1372 mm 54 173 mm 6 13 16 679 mm 26 3 4 2138 mm 84 3 16 227 mm 8 15 16 25 mm 1 830 mm 32 11 16 1643 mm 64 11 16 151 mm 5 1...

Страница 15: ...mm 1 843 mm 33 3 16 68 mm 2 11 16 1643 mm 64 11 16 152 mm 6 GAS CONNECTION SEE NOTE 1 22 mm 7 8 DIA HOLE UNIT CONTROL WIRE 76 mm 3 DIA HOLE UNIT POWER WIRE DOWNFLOW CONDENSATE DRAIN CONN 25 mm 1 NPT...

Страница 16: ...SVX26J EN Figure 8 Unit dimensional data 15 25 tons standard efficiency units 12 25 tons high efficiency units Figure 9 Horizontal duct dimensional data 15 25 tons standard efficiency units 12 25 tons...

Страница 17: ...t 2223 707 580 425 509 YS 250F 2054 655 555 403 442 YS 300F 2054 655 555 403 442 YH 300F 2207 702 579 422 507 Table 2 Typical unit weights and point loading data kg Unit Models Net Weights 25mm 18mm C...

Страница 18: ...at the gasket on the curb is not damaged while positioning the unit WARNING Heavy Objects Ensure that all the lifting equipment used is properly rated for the weight of the unit being lifted Each of t...

Страница 19: ...uirements The checklist listed below is a summary of the steps required to successfully install a commercial unit This checklist is intended to acquaint the installing personnel with what is required...

Страница 20: ...ate drain line must be connected to the P Trap Pitch the drain lines at least inch for every 10 feet of horizontal run to assure proper condensate flow Do not allow the horizontal run to sag causing a...

Страница 21: ...al and national codes Field Installed Control Wiring An overall layout of the various control options available with the required number of conductors for each control device is illustrated in Figure...

Страница 22: ...lowed when interconnecting the DC binary output devices and the system components utilizing a DC analog input output signal to the unit Note Resistance in excess of 2 5 ohms per conductor can cause de...

Страница 23: ...System Sensor smoke detectors are connected together using terminals 1 and 12 on each detector If you have supply and return smoke detectors in all HVAC units you can connect a maximum of five HVAC u...

Страница 24: ...Installation 24 RT SVX26J EN Figure 19 Smoke detector connections up to 10 HVAC units...

Страница 25: ...26J EN 25 Figure 20 Typical field wiring diagrams for optional controls ReliaTel only BAYSENS075 BAYSENS075 BAYSENS119 BAYSENS110 BAYSENS108 BAYSENS106 BAYSENS073 BAYSENS074 BAYSENS075 ASYSTAT669A OPT...

Страница 26: ...d Example 2 illustrates three sensors squared in a series parallel circuit Example 3 illustrates the circuit required for this senor Table 5 lists the temperature versus resistance coefficient for all...

Страница 27: ...Installation RT SVX26J EN 27 Table 6 Space temperature averaging examples...

Страница 28: ...0 w c Manifold Gas Pressure b b Staged gas heat units have a negative pressure gas valve Never adjust the staged gas pressure valve to a positive pressure 0 2 w c Combustion Blower Suction Pressure 1s...

Страница 29: ...onnect switch to the Off position Connect the phase sequence indicator leads to the terminal block or to the Line side of the optional factory mounted disconnect switch as follows Black phase A to L1...

Страница 30: ...procedure to bypass some time delays and to start the unit at the control panel Each step of unit operation can be activated individually by temporarily shorting across the Test terminals for two to t...

Страница 31: ...found on the unit nameplate and the N E C 4 Route low voltage class II control wiring through hole in base of unit but not through high voltage conduit Feedcontrolwiringthroughbushingprovided on side...

Страница 32: ...including remote disconnects and discharge all motor start run capacitors before servicing Follow proper lockout tagout procedures to ensure the power cannot be inadvertently energized Verify with an...

Страница 33: ...ned above proceed with the installation of the return air smoke detector as follows 1 Remove the smoke detector assembly from its shipping position in the indoor fan compartment This assembly is attac...

Страница 34: ...t will be necessary to remove the barometric relief filter open the barometric relief damper and reach inside through the barometric relief outlet to access and connect the copper exhaust elbow to the...

Страница 35: ...ris accumulated on the indoor coil and filters To insure that airflow through the unit is adequate for proper sampling by the return air smoke detector complete adherence to the maintenance procedures...

Страница 36: ...NG Hazardous Voltage w Capacitors Disconnect all electric power including remote disconnects and discharge all motor start run capacitors before servicing Follow proper lockout tagout procedures to en...

Страница 37: ...across the Test 1 and Test 2 terminals on LTB1 one time to start the Minimum Ventilation Test Once the supply fan has started check for proper rotation The direction of rotation is indicated by an ar...

Страница 38: ...LTB1 one additional time if continuing from previous component start up or until the desired startup component Test is started Scroll Compressors a Once each compressor has started verify that the ro...

Страница 39: ...it is not recommended to set the supply air temperature below 50 F In cooling mode if the supply air temperature is more than 3 5 F warmer than the selected temperature a stage of cooling will be turn...

Страница 40: ...U Active DWU Off DWU or Cooling1 2 3 4 VAV Cooling1 DWU or Cooling1 2 3 4 VAV Cooling or Heating1 Off Off4 Off4 Notes 1 If Cooling is selected the supply fan will run continuously If VAV Heating is ac...

Страница 41: ...in place Close the main disconnect switch or circuit protector switch that provides the supply power to the unit s terminal block or the unit mounted disconnect switch Figure 34 RTAM module Static pr...

Страница 42: ...number represents the force in pounds required to give the needed deflection 6 Compare the force scale reading Step 5 with the appropriate force value listed in Table 17 p 42 If the force reading is...

Страница 43: ...place it Refer to Fan Belt Adjustment Belt Drive Units p 42 for belt replacement and adjustments Verify that all wire terminal connections are tight Remove any corrosion present on the exterior surfac...

Страница 44: ...the blanks provided 1 Complete Unit Model Number _____________________________________________________ 2 Unit Serial Number _____________________________________________________ 3 Wiring Diagram Numbe...

Страница 45: ...ting Refer to the sequence of operations for each mode to assist in verifying proper operation Make the necessary repairs and proceed to Step 7 and Step 8 7 If no abnormal operating conditions appear...

Страница 46: ...ogged filter switch has closed check the filters Simultaneous Heat and Cool Failure Emergency Stop is activated Method 2 The second method for determining system status is done by checking voltage rea...

Страница 47: ...losed The LED will be turned off immediately after resetting the switch to the Normally Open position or any time that the IDM is turned Off If the switch remains closed and the IDM is turned On the S...

Страница 48: ...the high end will measure from approximately 24 to 38 Vdc 4 Verify all modes of operation by running the unit through all of the steps in the Test Modes section discussed in Start Up p 38 5 After ver...

Страница 49: ...izer Actuator ECA LED indicator OFF No Power or Failure ON Normal OK to Economize Slow Flash Normal Not OK to Economize Fast Flash 1 4 Second On 2 Seconds Off Error Code Communications Failure Pulse F...

Страница 50: ...with or without Dehumidification 380 575 2313 1502 YS 150 300 YH 150 300 50 60HZ 2 Stage Gas Heat with or without Dehumidification 2313 1504 YS 150 300 YH 150 300 50 60HZ Modulating Gas Heat with or...

Страница 51: ...Module Connections 208 230 460 575 60 Hz 2313 2050 YS 180 300 YH 150 300 2 Stage Gas Heat 2313 2051 YS 180 300 YH 150 300 Modulating Gas Heat Multi zone Variable Air Volume Multi speed Fans Single Zon...

Страница 52: ...vanced controls and HVAC systems comprehensive building services and parts For more information visit www IRCO com The manufacturer has a policy of continuous product and product data improvement and...

Отзывы: