Ingersoll-Rand YH*150 Скачать руководство пользователя страница 11

General Information

RT-SVX26J-EN

11 

Unit Inspection

As soon as the unit arrives at the job site:

Verify that the nameplate data matches the data on the 
sales order and bill of lading (including electrical data).

Verify that the power supply complies with the unit 
nameplate specifications.

Visually inspect the exterior of the unit, including the 
roof, for signs of shipping damage.

Visually inspect the internal components for shipping 
damage as soon as possible after delivery and before 
it is stored. Do not walk on the sheet metal base pans.

If concealed damage is discovered, notify the carrier’s 
terminal of damage immediately by phone and by 
mail. Concealed damage must be reported within 15 
days.

Request an immediate joint inspection of the 
damage by the carrier and the consignee.

Do not remove damaged material from the 
receiving location.

Take photos of the damage, if possible. The owner 
must provide reasonable evidence that the damage 
did not occur after delivery.

Notify the appropriate sales representative before 
installing or repairing a damaged unit.

Precautionary Measures

Avoid breathing fiberglass dust.

Use a NIOSH approved dust/mist respirator.

Avoid contact with the skin or eyes. Wear long-sleeved, 
loose-fitting clothing, gloves, and eye protection.

Wash clothes separately from other clothing: rinse 
washer thoroughly.

Operations such as sawing, blowing, tear-out, and 
spraying may generate fiber concentrations requiring 
additional respiratory protection. Use the appropriate 
NIOSH approved respiration in these situations.

First Aid Measures

Eye Contact - Flush eyes with water to remove dust. If 
symptoms persist, seek medical attention.

Skin Contact - Wash affected areas gently with soap 
and warm water after handling.

Storage

Take precautions to prevent condensate from forming 
inside the unit’s electrical compartments and motors if:

The unit is stored before it is installed; or,

The unit is set on the roof curb, and temporary heat is 
provided in the building. Isolate all side panel service 
entrances and base pan openings (e.g., conduit holes, 
S/A and R/ A openings, and flue openings) from the 
ambient air until the unit is ready for start-up.

Note:

Do not use the unit’s heater for temporary heat 
without first completing the start-up procedure 
detailed under 

“Start Up,” p. 38

.

The manufacturer will not assume any responsibility for 
equipment damage resulting from condensate 
accumulation on the unit’s electrical and/or mechanical 
components.

Unit Clearances

Figure 1, p. 12

 illustrates the minimum operating and 

service clearances for either a single or multiple unit 
installation. These clearances are the minimum distances 
necessary to assure adequate serviceability, cataloged 
unit capacity, and peak operating efficiency.

Providing less than the recommended clearances may 
result in condenser coil starvation, “short-circuiting” of 
exhaust and economizer airflows, or recirculation of hot 
condenser air.

WARNING

Fiberglass Wool! 

Product contains fiberglass wool. Disturbing the 
insulation in this product during installation, 
maintenance or repair will expose you to airborne 
particles of glass wool fibers and ceramic fibers known 
to the state of California to cause cancer through 
inhalation. You MUST wear all necessary Personal 
Protective Equipment (PPE) including gloves, eye 
protection, a NIOSH approved dust/mist respirator, long 
sleeves and pants when working with products 
containing fiberglass wool. Exposition to glass wool 
fibers without all necessary PPE equipment could result 
in cancer, respiratory, skin or eye irritation, which could 
result in death or serious injury. 

Содержание YH*150

Страница 1: ...ing Improperly installed adjusted or altered equipment by an unqualified person could result in death or serious injury When working on the equipment observe all precautions in the literature and on t...

Страница 2: ...TION Warnings Cautions and Notices appear at appropriate sections throughout this literature Read these carefully WARNING Indicates a potentially hazardous situation which if not avoided could result...

Страница 3: ...this manual and following the instructions the risk of improper operation and or component damage will be minimized It is important that periodic maintenance be performed to help assure trouble free o...

Страница 4: ...Smoke Detector 33 Through the Base Gas Utility Option 36 Pre Start 37 Test Modes 37 Verifying Proper Air Flow Units with Belt Drive Indoor Fan 37 Start Up 38 Economizer Start Up 38 Compressor Start Up...

Страница 5: ...ndard Motor w Shaft Grounding Ring C Single Zone Variable Air Volume Oversized Motor w Shaft Grounding Ring D Multi Speed Oversized Motor w Shaft Grounding Ring E VAV Supply Air Temperature Control St...

Страница 6: ...Through the Base Options 9 ReliaTel Options Module is required when ordering the following accessories Clogged Filter Switch Fan Fail Switch Condensate Overflow Switch Discharge Air Sensing Kit Frost...

Страница 7: ...the installation instruction that ships with each kit when field installation is necessary RLCI ReliaTel LonTalk Communication Interface Optional This module is used when the application calls for an...

Страница 8: ...during compressor operation the compressor for that circuit is immediately turned Off The compressor will not be allowed to restart for a minimum of 3 minutes should the contacts close If four consec...

Страница 9: ...th a Trane Integrated Comfort building management system Remote Zone Sensor BAYSENS074 This electronic sensor features single setpoint capability and timed override with override cancellation It is us...

Страница 10: ...ream or return air stream the air velocity entering the smoke detector unit must be between 500 and 4000 feet per minute Equipment covered in this manual will develop an airflow velocity that falls wi...

Страница 11: ...h soap and warm water after handling Storage Take precautions to prevent condensate from forming inside the unit s electrical compartments and motors if The unit is stored before it is installed or Th...

Страница 12: ...12 RT SVX26J EN Unit Dimensions Figure 1 Typical installation clearance for single and multiple unit applications 5 8 5 0...

Страница 13: ...nal data for 12 tons standard efficiency units 2710 mm 106 11 16 1273 mm 50 1 8 168 mm 6 5 8 651 mm 25 5 8 1799 mm 70 13 16 213 mm 8 3 8 745 mm 29 5 16 68 mm 2 11 16 25 mm 1 1453 mm 57 3 16 152 mm 6 S...

Страница 14: ...Unit dimensional data 15 25 tons standard efficiency units 3091 mm 121 11 16 1372 mm 54 173 mm 6 13 16 679 mm 26 3 4 2138 mm 84 3 16 227 mm 8 15 16 25 mm 1 830 mm 32 11 16 1643 mm 64 11 16 151 mm 5 1...

Страница 15: ...mm 1 843 mm 33 3 16 68 mm 2 11 16 1643 mm 64 11 16 152 mm 6 GAS CONNECTION SEE NOTE 1 22 mm 7 8 DIA HOLE UNIT CONTROL WIRE 76 mm 3 DIA HOLE UNIT POWER WIRE DOWNFLOW CONDENSATE DRAIN CONN 25 mm 1 NPT...

Страница 16: ...SVX26J EN Figure 8 Unit dimensional data 15 25 tons standard efficiency units 12 25 tons high efficiency units Figure 9 Horizontal duct dimensional data 15 25 tons standard efficiency units 12 25 tons...

Страница 17: ...t 2223 707 580 425 509 YS 250F 2054 655 555 403 442 YS 300F 2054 655 555 403 442 YH 300F 2207 702 579 422 507 Table 2 Typical unit weights and point loading data kg Unit Models Net Weights 25mm 18mm C...

Страница 18: ...at the gasket on the curb is not damaged while positioning the unit WARNING Heavy Objects Ensure that all the lifting equipment used is properly rated for the weight of the unit being lifted Each of t...

Страница 19: ...uirements The checklist listed below is a summary of the steps required to successfully install a commercial unit This checklist is intended to acquaint the installing personnel with what is required...

Страница 20: ...ate drain line must be connected to the P Trap Pitch the drain lines at least inch for every 10 feet of horizontal run to assure proper condensate flow Do not allow the horizontal run to sag causing a...

Страница 21: ...al and national codes Field Installed Control Wiring An overall layout of the various control options available with the required number of conductors for each control device is illustrated in Figure...

Страница 22: ...lowed when interconnecting the DC binary output devices and the system components utilizing a DC analog input output signal to the unit Note Resistance in excess of 2 5 ohms per conductor can cause de...

Страница 23: ...System Sensor smoke detectors are connected together using terminals 1 and 12 on each detector If you have supply and return smoke detectors in all HVAC units you can connect a maximum of five HVAC u...

Страница 24: ...Installation 24 RT SVX26J EN Figure 19 Smoke detector connections up to 10 HVAC units...

Страница 25: ...26J EN 25 Figure 20 Typical field wiring diagrams for optional controls ReliaTel only BAYSENS075 BAYSENS075 BAYSENS119 BAYSENS110 BAYSENS108 BAYSENS106 BAYSENS073 BAYSENS074 BAYSENS075 ASYSTAT669A OPT...

Страница 26: ...d Example 2 illustrates three sensors squared in a series parallel circuit Example 3 illustrates the circuit required for this senor Table 5 lists the temperature versus resistance coefficient for all...

Страница 27: ...Installation RT SVX26J EN 27 Table 6 Space temperature averaging examples...

Страница 28: ...0 w c Manifold Gas Pressure b b Staged gas heat units have a negative pressure gas valve Never adjust the staged gas pressure valve to a positive pressure 0 2 w c Combustion Blower Suction Pressure 1s...

Страница 29: ...onnect switch to the Off position Connect the phase sequence indicator leads to the terminal block or to the Line side of the optional factory mounted disconnect switch as follows Black phase A to L1...

Страница 30: ...procedure to bypass some time delays and to start the unit at the control panel Each step of unit operation can be activated individually by temporarily shorting across the Test terminals for two to t...

Страница 31: ...found on the unit nameplate and the N E C 4 Route low voltage class II control wiring through hole in base of unit but not through high voltage conduit Feedcontrolwiringthroughbushingprovided on side...

Страница 32: ...including remote disconnects and discharge all motor start run capacitors before servicing Follow proper lockout tagout procedures to ensure the power cannot be inadvertently energized Verify with an...

Страница 33: ...ned above proceed with the installation of the return air smoke detector as follows 1 Remove the smoke detector assembly from its shipping position in the indoor fan compartment This assembly is attac...

Страница 34: ...t will be necessary to remove the barometric relief filter open the barometric relief damper and reach inside through the barometric relief outlet to access and connect the copper exhaust elbow to the...

Страница 35: ...ris accumulated on the indoor coil and filters To insure that airflow through the unit is adequate for proper sampling by the return air smoke detector complete adherence to the maintenance procedures...

Страница 36: ...NG Hazardous Voltage w Capacitors Disconnect all electric power including remote disconnects and discharge all motor start run capacitors before servicing Follow proper lockout tagout procedures to en...

Страница 37: ...across the Test 1 and Test 2 terminals on LTB1 one time to start the Minimum Ventilation Test Once the supply fan has started check for proper rotation The direction of rotation is indicated by an ar...

Страница 38: ...LTB1 one additional time if continuing from previous component start up or until the desired startup component Test is started Scroll Compressors a Once each compressor has started verify that the ro...

Страница 39: ...it is not recommended to set the supply air temperature below 50 F In cooling mode if the supply air temperature is more than 3 5 F warmer than the selected temperature a stage of cooling will be turn...

Страница 40: ...U Active DWU Off DWU or Cooling1 2 3 4 VAV Cooling1 DWU or Cooling1 2 3 4 VAV Cooling or Heating1 Off Off4 Off4 Notes 1 If Cooling is selected the supply fan will run continuously If VAV Heating is ac...

Страница 41: ...in place Close the main disconnect switch or circuit protector switch that provides the supply power to the unit s terminal block or the unit mounted disconnect switch Figure 34 RTAM module Static pr...

Страница 42: ...number represents the force in pounds required to give the needed deflection 6 Compare the force scale reading Step 5 with the appropriate force value listed in Table 17 p 42 If the force reading is...

Страница 43: ...place it Refer to Fan Belt Adjustment Belt Drive Units p 42 for belt replacement and adjustments Verify that all wire terminal connections are tight Remove any corrosion present on the exterior surfac...

Страница 44: ...the blanks provided 1 Complete Unit Model Number _____________________________________________________ 2 Unit Serial Number _____________________________________________________ 3 Wiring Diagram Numbe...

Страница 45: ...ting Refer to the sequence of operations for each mode to assist in verifying proper operation Make the necessary repairs and proceed to Step 7 and Step 8 7 If no abnormal operating conditions appear...

Страница 46: ...ogged filter switch has closed check the filters Simultaneous Heat and Cool Failure Emergency Stop is activated Method 2 The second method for determining system status is done by checking voltage rea...

Страница 47: ...losed The LED will be turned off immediately after resetting the switch to the Normally Open position or any time that the IDM is turned Off If the switch remains closed and the IDM is turned On the S...

Страница 48: ...the high end will measure from approximately 24 to 38 Vdc 4 Verify all modes of operation by running the unit through all of the steps in the Test Modes section discussed in Start Up p 38 5 After ver...

Страница 49: ...izer Actuator ECA LED indicator OFF No Power or Failure ON Normal OK to Economize Slow Flash Normal Not OK to Economize Fast Flash 1 4 Second On 2 Seconds Off Error Code Communications Failure Pulse F...

Страница 50: ...with or without Dehumidification 380 575 2313 1502 YS 150 300 YH 150 300 50 60HZ 2 Stage Gas Heat with or without Dehumidification 2313 1504 YS 150 300 YH 150 300 50 60HZ Modulating Gas Heat with or...

Страница 51: ...Module Connections 208 230 460 575 60 Hz 2313 2050 YS 180 300 YH 150 300 2 Stage Gas Heat 2313 2051 YS 180 300 YH 150 300 Modulating Gas Heat Multi zone Variable Air Volume Multi speed Fans Single Zon...

Страница 52: ...vanced controls and HVAC systems comprehensive building services and parts For more information visit www IRCO com The manufacturer has a policy of continuous product and product data improvement and...

Отзывы: