Mechanical Settings

Select

Type        Heatpump
Fan Type          Elec
C/O Type      w/Cool
2nd Stage Heat    N

Mechanical Settings

a. 

Press the 

MENU

 button twice.

b. 

Press and hold the two inner buttons for 3 seconds to view 

Installer Settings

c. 

Scroll down to 

System Settings

 and press the Select button.

d. 

Scroll to 

Mechanical Settings

 (it is the first option), then press 

the 

Select button.

e. 

Choose option A-D below:

For Gas Furnace - Multistage Mechanical Settings

a. 

Scroll down to 2nd Stage Heat.

b. 

Press the + button to change the setting to Y for Yes.

c. 

If your system also has 2nd stage cooling, scroll down to 2nd 
Stage Cool and Press the + button to change the setting to Y for 
Yes. 

d. 

Press the Done button 4 times and go to Perform System 

Checkout.

For Electric Furnace Mechanical Settings

a. 

Scroll down to Fan Type.

b. 

Press the + button to change the setting Electric.

 

Î

If Single Stage System, press Done 4 times and go 
to Perform System Checkout.

 

Î

If Multistage System, continue with steps c through f.

c. 

Scroll down to 2nd Stage Heat.

d. 

Press the + button to change the setting to Y for Yes. 

e. 

If your system also has 2nd stage cooling, scroll down to 2nd 
Stage Cool and Press the + button to change the setting to Y for 
Yes.

f. 

Press the Done button 4 times and go to Perform System 

Checkout.

Heat Pump Mechanical Settings

a. 

Scroll to system Type.

b. 

Press the + button to change the setting to Y to Heat Pump.

c. 

Scroll down to Fan Type.

d. 

Press the + button to change the setting to Electric.

e. 

If Coleman, Rheem, or Rudd brand heat pump, scroll to C/O Type 
and change to 

With Heat

 

Î

If Single Stage System, press Done 4 times and go 
to Perform System Checkout.

 

Î

If Multistage System, continue with steps f through j.

f. 

Scroll down to 2nd Stage Heat.

g. 

Press the + button to change the setting to Y for Yes.

h. 

Scroll down to 2nd Stage Cool.

i. 

Press the + button to change the setting to Y for Yes.

j. 

Press the Done button 4 times and go to Perform System 

Checkout.

Enable Dual Fuel

a. 

Scroll to system Type.

b. 

Press the + button to change the setting type to Heatpump DF.  The 
default control mode is Non-restricted.

c. 

To change to Restricted, scroll to DF Type Non-restricted.  Press the 
+ button to set the mode to Restricted.

d. 

If Non-restricted control mode was selected, press the Done button 
4 times and go to Perform System Checkout.

e. 

If restricted control mode was selected, set the desired compressor 
lockout temperature.  Press the Done button 3 times then select 
User Settings.  Scroll down to Balance Point.  Use the + and 
- buttons to set the compressor lockout temperature.  Default 
compressor lockout temperature is 40°F.

f. 

Press the Done button 2 times and go to Perform System Checkout.

Содержание TRANE NEXIA TZEMT500BB32MAA

Страница 1: ...8 7707 Contents Physical Installation and Wiring 2 Field Wiring Diagrams 4 Enhanced Dehumidification Mode 7 Optional Remote Temperature Sensors Installation 8 System Settings at Thermostat 10 Perform...

Страница 2: ...ions regarding recycling and proper disposal of the old control A listing of heating ventilating and air conditioning wholesalers that participate in the Thermostat Recycling Corporation s recycling p...

Страница 3: ...information from step 6 carefully to ensure the control is wired properly After wires are secure bare wires MUST NOT touch each other See the Field Connection Wiring Diagrams on the following pages f...

Страница 4: ...eturn R 24VAC Common B C Compressor Stage 2 Y2 BK Heat Stage 2 W2 RED GREEN WHITE YELLOW BLUE BROWN Remote Temperature Sensor Connections and Operation Indoor sensor connected to RS1 Replaces internal...

Страница 5: ...24VAC Return R 24VAC Common B C Compressor Stage 2 Y2 BK RED GREEN WHITE YELLOW BLUE BROWN Remote Temperature Sensor Connections and Operation Indoor sensor connected to RS1 Replaces internal sensor...

Страница 6: ...1 24VAC Return R 24VAC Common B C Compressor Stage 2 Y2 BK RED GREEN WHITE YELLOW BLUE BROWN Remote Temperature Sensor Connections and Operation Indoor sensor connected to RS1 Replaces internal sensor...

Страница 7: ...ot connected Indoor sensor connected to RS2 Averages temperature with internal sensor RS1 not connected Indoor sensors connected to RS1 and RS2 Averages RS1 and RS2 sensor temperatures Internal sensor...

Страница 8: ...to indoor location IN Default selection in the thermostat installation set up menu and a sensor is attached to the RS2 sensor terminals of the thermostat the RS2 temperature is averaged with the ther...

Страница 9: ...ling system back on The thermostat display should turn on and begin displaying information If the thermostat display does not come on go back through the installation steps and look for problems 10 At...

Страница 10: ...then press the Select button c Scroll up or down to Set Clock it is the first option then press the Select button Done Select User Settings Set Clock Filter Service Maint Service Screen Timeout Selec...

Страница 11: ...ess the button to change the setting to Y for Yes f Press the Done button 4 times and go to Perform System Checkout Heat Pump Mechanical Settings a Scroll to system Type b Press the button to change t...

Страница 12: ...to access the Menu Selection screen b From the Menu Selection screen press and hold the two inner buttons down for 4 seconds to reach the Installer Settings menu c From the Installer Settings screen...

Страница 13: ...s the Select button e Press the Yes button to enroll the thermostat f Observe the lights on the bridge The orange light will blink while enrollment is taking place Enrollment is complete when the oran...

Страница 14: ...while exclusion is taking place Exclusion is complete when the orange light becomes solid Z Wave controllers from various manufacturers may support the Z Wave Thermostat General V2 Device class used...

Страница 15: ...ng setpoint In AUTO mode the buttons change the last call s heating or cooling setpoint The setpoints will push each other if they are adjusted to within the minimum heat cool separation setting This...

Страница 16: ...de Sensor Calibration Internal Remote 1 Remote 2 Outside Backlite Display Backlite Timeout ON Level OFF Level Contrast Usage Graph Heat Cool ESM Setpoints ESM Heat ESM Cool Zwave Install Thermostat In...

Страница 17: ...eatpump DF DF Type Nonrestrict Restrict C O Type w Heat w Cool 2nd Stage Heat Aux Heat HP 2nd Stage Cool Balance Point if DF Restrict Sched Enable Recovery Enable H C Delta H Delta Stg1 ON H Delta Stg...

Страница 18: ...e and press the Select button 4 Make choice from the following options A C A To View Reset Filter Runtime 5 The Filter Runtime is displayed in hours 6 To reset the Filter Runtime counter press the Res...

Страница 19: ...d Screen Timeout This is the time before any screen reverts to the Minimized Screen temperature display only after you stop pushing buttons Minimized Screen feature is disabled by setting this time to...

Страница 20: ...rature is 77 and the number of degrees of offset being applied is 1 Change the Sensor Calibration 1 Press the MENU button 2 Scroll to User Settings and press the Select button 3 Scroll to Sensor Calib...

Страница 21: ...cklight 5 Scroll to Backlite Timeout 6 Press the plus or minus buttons to change the number of seconds The backlight time out can be set between 0 and 120 seconds Thirty 30 is the default setting When...

Страница 22: ...me MRT 1 9 Minutes 3 Sets the minimum run time before a heating cooling cycle can turn off to prevent rapid cycling Thermostat screen will display Cool ON or Heat ON while the minimum run time is bein...

Страница 23: ...time When the thermostat is in Recovery mode the display will show Recov Recovery works for all scheduled periods 1 4 and in HEAT COOL or AUTO modes While in Recovery the Aux Heat stage will not engag...

Страница 24: ...tricted Non restricted mode will follow thermostat demand for each heating stage Restricted mode will lock out the compressor at a selectable outdoor temperature Default balance point is 40 F C O Type...

Страница 25: ...3 Scroll to Systems Settings and press the Select button 4 Scroll to Sched Enable and press the plus button to enable scheduling or the minus button to disable scheduling When scheduling is enabled in...

Страница 26: ...hange to Copy 6 Press the Copy button 7 For each day to which you want to copy the day schedule change the N no to Y yes Use the left or right arrow buttons to scroll to the day and the use the Yes or...

Страница 27: ...t control if it is damaged while in your possession including but not limited to 1 damage caused by unreasonable use of the low voltage room comfort control 2 damage from failure to properly maintain...

Страница 28: ...icular installation If this equipment does cause harmful interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to corr...

Отзывы: