e:: Using the above method, it is recommended that the bulkheads that
separate each compartment be in place to isolate the compartments.
shows two Zones that have the same setpoint. The
bulkhead separating the compartments has been removed. The Host
evaporator senses temperature and controls both evaporators to the
temperature setpoint.
N
No
otte
e:: Using Method 2, it is recommended that all bulkheads be removed to
create one large compartment.
Figure 142.
Two Compartments, Same Setpoint Temperature, Bulkheads
In Place
Figure 143.
Two Compartments, Same Setpoint Temperature, Bulkhead
(s) Removed
Post-Loading Inspection
1. Make sure all the doors are closed and locked.
2. Start the unit if it was shut off to load.
3. Make sure the setpoints are at the desired settings.
4. One-half hour after loading, manually initiate a Defrost cycle. If the
evaporator coil sensor temperature is below 45 F (7 C), the unit will
Defrost. The microprocessor will terminate Defrost automatically when
the evaporator coil temperature reaches 58 F (14.5 C) or the unit has been