background image

©2022

18-GJ82D1-1F-EN

SAFETY SECTION
AIR HANDLERS

IIm

mp

po

orrtta

an

ntt

— This document contains a wiring

diagram, a parts list, and service information. This is
customer property and is to remain with this unit.
Please return to service information pack upon
completion of work.

W

WA

AR

RN

NIIN

NG

G

H

HA

AZ

ZA

AR

RD

DO

OU

US

S V

VO

OL

LT

TA

AG

GE

E!!

F

Fa

aiillu

urre

e tto

o ffo

ollllo

ow

w tth

hiiss W

Wa

arrn

niin

ng

g cco

ou

ulld

d rre

essu

ulltt iin

n

p

prro

op

pe

errtty

y d

da

am

ma

ag

ge

e,, sse

ev

ve

erre

e p

pe

errsso

on

na

all iin

njju

urry

y,, o

orr

d

de

ea

atth

h..

D

Diisscco

on

nn

ne

ecctt a

allll e

elle

eccttrriicc p

po

ow

we

err,, iin

nccllu

ud

diin

ng

g rre

em

mo

otte

e

d

diisscco

on

nn

ne

eccttss b

be

effo

orre

e sse

errv

viicciin

ng

g.. F

Fo

ollllo

ow

w p

prro

op

pe

err

llo

occkko

ou

utt//tta

ag

go

ou

utt p

prro

occe

ed

du

urre

ess tto

o e

en

nssu

urre

e tth

he

e p

po

ow

we

err

cca

an

nn

no

ott b

be

e iin

na

ad

dv

ve

errtte

en

nttlly

y e

en

ne

errg

giizze

ed

d..

C

CA

AU

UT

TIIO

ON

N

G

GR

RO

OU

UN

ND

DIIN

NG

G R

RE

EQ

QU

UIIR

RE

ED

D!!

F

Fa

aiillu

urre

e tto

o iin

nssp

pe

ecctt o

orr u

usse

e p

prro

op

pe

err sse

errv

viicce

e tto

oo

ollss m

ma

ay

y

rre

essu

ulltt iin

n e

eq

qu

uiip

pm

me

en

ntt d

da

am

ma

ag

ge

e o

orr p

pe

errsso

on

na

all iin

njju

urry

y..

R

Re

ecco

on

nn

ne

ecctt a

allll g

grro

ou

un

nd

diin

ng

g d

de

ev

viicce

ess.. A

Allll p

pa

arrttss o

off tth

hiiss

p

prro

od

du

ucctt tth

ha

att a

arre

e cca

ap

pa

ab

blle

e o

off cco

on

nd

du

uccttiin

ng

g e

elle

eccttrriicca

all

ccu

urrrre

en

ntt a

arre

e g

grro

ou

un

nd

de

ed

d.. IIff g

grro

ou

un

nd

diin

ng

g w

wiirre

ess,, ssccrre

ew

wss,,

ssttrra

ap

pss,, cclliip

pss,, n

nu

uttss,, o

orr w

wa

assh

he

errss u

usse

ed

d tto

o cco

om

mp

plle

ette

e a

a

p

pa

atth

h tto

o g

grro

ou

un

nd

d a

arre

e rre

em

mo

ov

ve

ed

d ffo

orr sse

errv

viicce

e,, tth

he

ey

y m

mu

usstt

b

be

e rre

ettu

urrn

ne

ed

d tto

o tth

he

eiirr o

orriig

giin

na

all p

po

ossiittiio

on

n a

an

nd

d p

prro

op

pe

errlly

y

ffa

asstte

en

ne

ed

d..

W

WA

AR

RN

NIIN

NG

G

L

LIIV

VE

E E

EL

LE

EC

CT

TR

RIIC

CA

AL

L C

CO

OM

MP

PO

ON

NE

EN

NT

TS

S!!

F

Fa

aiillu

urre

e tto

o ffo

ollllo

ow

w tth

hiiss W

Wa

arrn

niin

ng

g cco

ou

ulld

d rre

essu

ulltt iin

n

p

prro

op

pe

errtty

y d

da

am

ma

ag

ge

e,, sse

ev

ve

erre

e p

pe

errsso

on

na

all iin

njju

urry

y,, o

orr

d

de

ea

atth

h..

F

Fo

ollllo

ow

w a

allll e

elle

eccttrriicca

all ssa

affe

etty

y p

prre

ecca

au

uttiio

on

nss w

wh

he

en

n

e

ex

xp

po

osse

ed

d tto

o lliiv

ve

e e

elle

eccttrriicca

all cco

om

mp

po

on

ne

en

nttss.. IItt m

ma

ay

y b

be

e

n

ne

ecce

essssa

arry

y tto

o w

wo

orrkk w

wiitth

h lliiv

ve

e e

elle

eccttrriicca

all cco

om

mp

po

on

ne

en

nttss

d

du

urriin

ng

g iin

nsstta

alllla

attiio

on

n,, tte

essttiin

ng

g,, sse

errv

viicciin

ng

g,, a

an

nd

d

ttrro

ou

ub

blle

essh

ho

oo

ottiin

ng

g o

off tth

hiiss p

prro

od

du

ucctt..

W

WA

AR

RN

NIIN

NG

G

P

PR

RE

ES

SS

SU

UR

RIIZ

ZE

ED

D R

RE

EF

FR

RIIG

GE

ER

RA

AN

NT

T!!

F

Fa

aiillu

urre

e tto

o ffo

ollllo

ow

w tth

hiiss W

Wa

arrn

niin

ng

g cco

ou

ulld

d rre

essu

ulltt iin

n

p

pe

errsso

on

na

all iin

njju

urry

y

S

Sy

ysstte

em

m cco

on

ntta

aiin

nss o

oiill a

an

nd

d rre

effrriig

ge

erra

an

ntt u

un

nd

de

err h

hiig

gh

h

p

prre

essssu

urre

e.. R

Re

ecco

ov

ve

err rre

effrriig

ge

erra

an

ntt tto

o rre

elliie

ev

ve

e p

prre

essssu

urre

e

b

be

effo

orre

e o

op

pe

en

niin

ng

g tth

he

e ssy

ysstte

em

m.. D

Do

o n

no

o u

usse

e n

no

on

n--

a

ap

pp

prro

ov

ve

ed

d rre

effrriig

ge

erra

an

nttss o

orr rre

effrriig

ge

erra

an

ntt ssu

ub

bssttiittu

utte

ess o

orr

rre

effrriig

ge

erra

an

ntt a

ad

dd

diittiiv

ve

ess..

C

CA

AU

UT

TIIO

ON

N

S

SH

HA

AR

RP

P E

ED

DG

GE

E H

HA

AZ

ZA

AR

RD

D!!

F

Fa

aiillu

urre

e tto

o ffo

ollllo

ow

w tth

hiiss C

Ca

au

uttiio

on

n cco

ou

ulld

d rre

essu

ulltt iin

n

p

prro

op

pe

errtty

y d

da

am

ma

ag

ge

e o

orr p

pe

errsso

on

na

all iin

njju

urry

y..

B

Be

e cca

arre

effu

ull o

off ssh

ha

arrp

p e

ed

dg

ge

ess o

on

n e

eq

qu

uiip

pm

me

en

ntt o

orr a

an

ny

y

ccu

uttss m

ma

ad

de

e o

on

n ssh

he

ee

ett m

me

etta

all w

wh

hiille

e iin

nsstta

alllliin

ng

g o

orr

sse

errv

viicciin

ng

g..

W

WA

AR

RN

NIIN

NG

G

W

WA

AR

RN

NIIN

NG

G!!

T

Th

hiiss p

prro

od

du

ucctt cca

an

n e

ex

xp

po

osse

e y

yo

ou

u tto

o cch

he

em

miicca

allss

iin

nccllu

ud

diin

ng

g lle

ea

ad

d,, w

wh

hiicch

h a

arre

e kkn

no

ow

wn

n tto

o tth

he

e S

Stta

atte

e o

off

C

Ca

alliiffo

orrn

niia

a tto

o cca

au

usse

e cca

an

ncce

err a

an

nd

d b

biirrtth

h d

de

effe

eccttss o

orr

o

otth

he

err rre

ep

prro

od

du

uccttiiv

ve

e h

ha

arrm

m.. F

Fo

orr m

mo

orre

e iin

nffo

orrm

ma

attiio

on

n g

go

o

tto

o w

ww

ww

w..P

P6

65

5W

Wa

arrn

niin

ng

gss..cca

a..g

go

ov

v..

IIm

mp

po

orrtta

an

ntt:: Panel damage can occur with prolonged

exposure to POE lubricants. Air handler
front panels that come in contact with POE
oil must be washed immediately with
soapy water.

IIm

mp

po

orrtta

an

ntt:: The TAM9 air handlers are only compatible

with BAYEA** internal electric heaters.

N

No

otte

e:: Representative illustrations only included in this

document. Most illustrations display the upflow
configuration.

Содержание TAM9A0A24V21DB

Страница 1: ...d result in death or serious injury When working on the equipment observe all precautions in the literature and on the tags stickers and labels that are attached to the equipment February 2022 1 18 8...

Страница 2: ...he en n e ex xp po os se ed d t to o l li iv ve e e el le ec ct tr ri ic ca al l c co om mp po on ne en nt ts s I It t m ma ay y b be e n ne ec ce es ss sa ar ry y t to o w wo or rk k w wi it th h l l...

Страница 3: ...ation 19 Setting the Unit Horizontal Installations 21 Connecting the Duct work 22 Refrigerant Line 23 Refrigerant System Layout 23 Refrigerant Line Brazing 24 Condensate Drain Piping 27 Electrical Low...

Страница 4: ...g t th he e D Di is sp pl la ay y A Ai ir r F Fl lo ow w T Ta ab bl le es s a an nd d T Tr ro ou ub bl le es sh ho oo ot ti in ng g F Fl lo ow wc ch ha ar rt ts s I Im mp po or rt ta an nt t The low v...

Страница 5: ...d other penetrations are allowed in the blower section for installation of Side Return Kit Typical both sides Screws are allowed up to 3 3 4 from the top of the cabinet heater compartment Typical both...

Страница 6: ...move Heater Panel 1 Turn screws on Heater panel 2 Pull panel straight out away from cabinet 3 Set aside Removal of the Line Set panel is required for all refrigerant line brazing and some condensate l...

Страница 7: ...ted in a horizontal position it must be laid on its back marked REAR on carton Note After unit is removed from the carton verify coil is pressurized Carefully remove the liquid line plug If no pressur...

Страница 8: ...Kit with 16 x 20 Filter A to C BAYFRKIT175 Front Return Kit for 17 5 Cabinet A BAYFRKIT210 Front Return Kit for 21 0 Cabinet B BAYFRKIT235 Front Return Kit for 23 5 Cabinet C TAYBASETAMA Downflow Sub...

Страница 9: ...l bar and pull the seal bar straight out 3 Disconnect all wiring connections routed to the blower assembly 4 Slide Blower assembly out of unit using built in blower support channels and set aside Note...

Страница 10: ...oil Support Channel 7 Use a 5 16 Allen wrench on the locking mechanism on each side of the bottom half of the cabinet to loosen the locking mechanism The locks loosen by turning counter clockwise appr...

Страница 11: ...the Coil section up and away from the Blower section Set aside Note When separating the two cabinet pieces make sure the gasket remains intact O Op pt ti io on na al l C Ca ab bi in ne et t D Di is s...

Страница 12: ...ough a small opening remove the top panel and all cross members Use a manual driver to avoid stripping screw holes 10 Continue preparation by following the proper carrying procedures shown in the next...

Страница 13: ...f cut wire ties that held the sensor wiring must be replaced Important Under no conditions should metal strapping be attached to the unit to be used as support mechanisms for carrying or suspension pu...

Страница 14: ...Height inches Unit Net Weight pounds D H W TAM9A0A24V21DB 49 9 x 17 5 x 21 8 28 1 116 TAM9A0B30V31DB 55 7 x 21 3 x 21 8 33 9 138 TAM9A0C36V31DB 56 9 x 23 5 x 21 8 35 1 146 TAM9A0C42V41DB 56 9 x 23 5 x...

Страница 15: ...ccordingly Note The air handlers are shipped from the factory suitable for four way application Note Entry for low voltage connections is allowed on either side of cabinet Airflow Upflow Configuration...

Страница 16: ...Connections Inside Unit Control Pocket Inside Unit Horizontal Left Configuration Horizontal Right Configuration Airflow Control Pocket Inside Unit Low Voltage Connections Inside Unit Refrigerant Conn...

Страница 17: ...ve e o or r u ut ti il li it ty y r ro oo om m a as s a a f fo os ss si il l f fu ue el l d de ev vi ic ce e Non Ducted Return Installations Installation in a closet an alcove or a utility room withou...

Страница 18: ...the air handler must be made prior to or at the same time as the installation of the outdoor unit in order to allow access for refrigerant lines Consider the overall space needed when external access...

Страница 19: ...ionable sound BAYINSKT175A for use with 17 5 cabinets BAYINSKT215A for use with 21 5 cabinets BAYINSKT235A for use with 23 5 cabinets Typical Closet Installation Table 7 Upflow Installation TASB Insta...

Страница 20: ...shorter Airflow Typical Plenum Installation Table 9 Downflow Installation Downflow installation must comply with national state and local codes 3 Prepare the location site as appropriate for your app...

Страница 21: ...bottom support methods are rail u channels Unistrut or other load bearing materials b The unit must be isolated carefully to prevent sound transmission Field supplied vibration isolators are recommen...

Страница 22: ...Kits are available to connect the supply plenum or for mounting on the discharge opening to provide a flush fit for 1 1 2 duct board applications If front or rear return is required the air handler m...

Страница 23: ...e required 2 All AHRI listed systems are tested with 25 feet of refrigeration tubing the rated tubing diameters are located in the electronic performance data system 3 If the refrigeration lines excee...

Страница 24: ...ction line between the Sensor and the braze joint to protect it from failure due to overheating 2 Remove the sealing plug from the indoor coil suction line 3 Remove the sealing plug from the indoor co...

Страница 25: ...as Temperature Sensor GT with a wet rag c Braze the refrigerant line connections Important Care must be taken during brazing to avoid damage to unit components and wiring Note The suction line must be...

Страница 26: ...et Note Charge system using Outdoor unit s Installer Guide or Service Facts Note Use soapy water to wipe any refrigerant oil off the panels 1 MIN 10 Replace the Line Set panel a Allow time for tubing...

Страница 27: ...the cover from the needed condensate drain connections and connect condensate piping d If the secondary condensate opening is not used plug the condensate opening with the fitting supplied in the docu...

Страница 28: ...sweating where dew point temperatures may be met Optional depending on climate and application needs Provide a means of drainage to prevent winter freeze up of condensate line Optional depending on cl...

Страница 29: ...mbined Control Wire 24 Volt WIRE SIZE MAX WIRE LENGTH 18 AWG 100 FT Combined Table 15 Low Voltage Hook up Instructions Note Strain relief must be provided on the inside of the air handler cabinet for...

Страница 30: ...orizontal Right Installations Only 5 Remove the control board completely from the control pocket Rotate the control board 180 degrees Place the control board 2 3 inches back into the control pocket 6...

Страница 31: ...1 Y2 G BK W1 W2 W3 O R B Y1 YO W3 Y2 G BK W1 W2 R B Y1 Y2 COMFORT CONTROL 1 OR 2 STAGE COOLING WITH TAM9 TAMG VARIABLE SPEED AIR HANDLER INDOOR UNIT OUTDOOR UNIT NOTES 1 Cut the BK jumper on the AFC w...

Страница 32: ...BK jumper on the AFC when using the BK fuctionality from the thermostat 2 Y1 and YO connections must be made as shown for freeze protection and internally mounted condensate overflow circuits to func...

Страница 33: ...Board J7 Motor J8 24 VAC Input J9 Display Assembly J5 External Switch J12 Humidifier Low Voltage thermostat harness STATUS LED FAULT LED UNIT LED 8 Set Jumper and Dip Switches Set the system refriger...

Страница 34: ...r or an external switch to the air handler locate the harness es in the doc pack The plug on the harness will plug into the AFC control board Humidifier Harness External Switch Harness AFC J5 External...

Страница 35: ...assembly into the control pocket until fully seated The control plate should be flush with the outer edge of the unit 2 Replace coil panel making sure that the wires are located within the wire pass...

Страница 36: ...e e n ne ec ce es ss sa ar ry y t to o w wo or rk k w wi it th h l li iv ve e e el le ec ct tr ri ic ca al l c co om mp po on ne en nt ts s d du ur ri in ng g i in ns st ta al ll la at ti io on n t te...

Страница 37: ...trical heater size needs to be set in the Configuration Menu Connect L1 L2 and ground wiring to pigtail harness in Heater Compartment using wire nuts The incoming ground wiring will mate up with the g...

Страница 38: ...8 Place the coil panel bracket into position and use screw to secure the coil panel bracket and seal plate to the support bar Important The Coil Seal Plate and screw secure the coil in the center of...

Страница 39: ...AS LINE BRAZE LIQ LINE BRAZE TAM9A0A24V21DB 49 9 39 6 14 5 17 5 14 5 7 3 24 4 EEV 3 4 3 8 TAM9A0B30V31DB 55 7 45 5 18 4 21 3 18 4 9 2 24 8 EEV 3 4 3 8 TAM9A0C36V31DB 56 9 46 7 20 5 23 5 20 5 10 3 24 2...

Страница 40: ...Up Down menu keys simultaneously for 10 seconds To Exit the technician menu section press the Up Down menu keys simultaneously for 10 seconds To move to the top of any menu tree press the Left Right...

Страница 41: ...ote 1 System Status will rotate automatically with active alerts Only alerts with a notification level of aUser or Critical re shown same as the thermostat up to four 4 alerts will be shown most recen...

Страница 42: ...Monitor menu allows the technician to monitor the different aspects of the system while the air handler is running No changes can be made in the Monitor Menu Superheat is only shown in cooling and de...

Страница 43: ...ations for the components are o AF Air Flow control o EV Expansion Valve control o DA Display Assembly The second line of text contains any action that may take place because of the fault and the orde...

Страница 44: ...ter size availability is based on unit size for this menu The OD unit type must be configured for 24 volt systems only o 1 1 is a single stage single compressor OD unit o 2 1 is a two stage single com...

Страница 45: ...te control o First value is current selection Second value is actual airflow o Use left or right menu keys to decrease or increase airflow in 100 CFM increments o Press ENTER to initiate new CFM deman...

Страница 46: ...Single Compressor 2 Stage HP TAM9A0B30V31DB 4A6H6024E G 4TWX6024E G 4A6H7024 4TWX8024 9 TAM9A0C36V31DB 4A6H6036E G 4TWX6036E G 4A6H7036 4TWX8036 10 TAM9A0C48V41DB 4A6H6048E G 4TWX6048E G 4A6H7048 4TWX...

Страница 47: ...els are securely in place and that all wiring has been properly dressed and secured 2 Set the system thermostat to OFF OFF 3 Turn on electrical power disconnect s to apply power to the indoor and outd...

Страница 48: ...EVC will now control superheat for 2nd stage 5 When a request for cooling is removed the AFC will turn off the blower motor after any user selected fan off delays have expired N No ot te e Delay prof...

Страница 49: ...no ot t e en ne er rg gi iz ze ed d d du ur ri in ng g t th he e U Un ni it t T Te es st t M Mo od de e 1 EVC drives the EEV motor to the 1st stage position for 5 seconds 2 EVC drives the EEV motor t...

Страница 50: ...ults can also be accessed through the Alert Menu in the Display Assembly Clearing Fault History Option 1 1 Scroll to the Alert Menu in the Display Assembly 2 Scroll to the Alert History section 3 Scro...

Страница 51: ...bing if necessary so tubes do not rub against each other or any component when unit runs Ductwork is sealed and insulated All drain lines are clear with joints properly sealed Pour water into drain pa...

Страница 52: ...lications For more information please visit www trane com or www americanstandardair com The manufacturer has a policy of continuous data improvement and it reserves the right to change design and spe...

Отзывы: