8
ACC-SVN67H-EN
Installation
1.
Remove heater compartment access panel and unit
control box access panel. See
.
Note:
On downflow units with or without duct work
installed or horizontal units without ductwork
installed, remove horizontal supply cover from the
rear of the heater compartment.
2. Remove insulation to expose perimeter of removable
panel in the vestibule panel. See
.
3. Clip or cut the retaining tabs around the perimeter of
the removable panel.
4. Remove the panel.
5. Check the opening in the vestibule panel. Remove any
metal burrs or slivers that could damage or pinch the
heater elements resulting in a short circuit when
elements are installed in the opening.
Note:
Locator tabs on the vestibule panel support the
electric heat assembly and secure the inward edge
of the electric heat accessory control panel. Slits in
the insulation should allow the tabs to protrude
through the insulation and be visible. However, it
may be necessary to work the insulation back from
the tabs and slightly bend the tabs outward if
difficulty is encountered engaging the electric
heater panel or the electric heat accessory control
panel. See
6. The electric heater element assembly has "BOTTOM"
stamped in the mounting panel to identify the proper
position for mounting.
7.
. If the unit/heater combination being
installed is the same as any in this table
and the
application is for horizontal airflow
, the limit
control TCO-A must be replaced with the extra limit
control shipped with the heater. Replace TCO-A
following the instructions in steps 8 and 9. If the unit/
heater combination being installed does not
correspond to any in this table or if the application is for
downflow airflow, skip steps 8 and 9 and go on to step
10.
WARNING
Hazardous Voltage w/Capacitors!
Failure to disconnect power and discharge capacitors
before servicing could result in death or serious injury.
Disconnect all electric power, including remote
disconnects and discharge all motor start/run
capacitors before servicing. Follow proper lockout/
tagout procedures to ensure the power cannot be
inadvertently energized. Verify with an appropriate
voltmeter that all capacitors have discharged.
For additional information regarding the safe discharge
of capacitors, see PROD-SVB06A-EN
WARNING
Fire Hazard!
On BAYHTRA, BAYHTRB, BAYHTRD, BAYHTRU, and
BAYHTRW heater kits, failure to allow a one inch
clearance from the supply ductwork to any combustible
materials could cause the combustible materials to
catch on fire which could result in death, serious injury,
or property damage.