![Ingersoll-Rand Odyssey TTA061G A Series Скачать руководство пользователя страница 50](http://html1.mh-extra.com/html/ingersoll-rand/odyssey-tta061g-a-series/odyssey-tta061g-a-series_installation-operation-and-maintenance-manual_2059234050.webp)
50
SS-SVX10H-EN
W
WA
AR
RN
NIIN
NG
G
L
Liiv
ve
e E
Elle
ec
cttrriic
ca
all C
Co
om
mp
po
on
ne
en
ntts
s!!
F
Fa
aiillu
urre
e tto
o ffo
ollllo
ow
w a
allll e
elle
eccttrriicca
all ssa
affe
etty
y p
prre
ecca
au
uttiio
on
nss
w
wh
he
en
n e
ex
xp
po
osse
ed
d tto
o lliiv
ve
e e
elle
ec
cttrriic
ca
all cco
om
mp
po
on
ne
en
nttss cco
ou
ulld
d
rre
es
su
ulltt iin
n d
de
ea
atth
h o
orr s
se
erriio
ou
us
s iin
njju
urry
y..
W
Wh
he
en
n iitt iis
s n
ne
ecce
es
sssa
arry
y tto
o w
wo
orrk
k w
wiitth
h lliiv
ve
e e
elle
eccttrriicca
all
c
co
om
mp
po
on
ne
en
nttss,, h
ha
av
ve
e a
a q
qu
ua
alliiffiie
ed
d lliicce
en
nsse
ed
d e
elle
eccttrriicciia
an
n
o
orr o
otth
he
err iin
nd
diiv
viid
du
ua
all w
wh
ho
o h
ha
as
s b
be
ee
en
n p
prro
op
pe
errlly
y ttrra
aiin
ne
ed
d
iin
n h
ha
an
nd
dlliin
ng
g lliiv
ve
e e
elle
eccttrriic
ca
all cco
om
mp
po
on
ne
en
nttss p
pe
errffo
orrm
m
tth
he
esse
e tta
asskks
s..
2. Disconnect wires from J6-11 and J6-12. Measure
the voltage between J6-11 and J6-12, should be
about 32 VDC.
3. Reconnect wires to terminals J6-11 and J6-12.
Measure voltage again between J6-11 and J6-12,
voltage should flash high and low every 0.5
seconds. The voltage on the low end will measure
about 19 VDC, while the voltage on the high end
will measure from approximately 24 to 38 VDC.
4. Verify all modes of operation, by running the unit
through all of the steps in
5. After verifying proper unit operation, exit the test
mode. Turn the fan on continuously at the ZSM, by
pressing the button with the fan symbol. If the fan
comes on and runs continuously, the ZSM is good.
If you are not able to turn the fan on, the ZSM is
defective.
RLCI Loss of Communications
If the RLCI loses input from the building management
system, the RTRM will control in the default mode after
approximately 15 minutes. If the RTRM loses the
Heating and Cooling setpoint input, the RTRM will
control in the default mode instantaneously. The
temperature sensing thermistor in the Zone Sensor
Module is the only component required for the
“
“D
De
effa
au
ulltt M
Mo
od
de
e”
” to operate.
Resetting Cooling and Heating
Lockouts
Cooling Failures and Heating Lockouts are reset in an
identical manner.
explains resetting
the system from the space;
explains
resetting the system at the unit.
N
No
otte
e:: Before resetting Cooling Failures and Heating
Lockouts check the Failure Status Diagnostics by
the methods previously explained. Diagnostics
will be lost when the power to the unit is
disconnected.
Method 1
To reset the system from the space, turn the M
MO
OD
DE
E
selection switch at the zone sensor to the O
OF
FF
F position.
After approximately 30 seconds, turn the M
MO
OD
DE
E
selection switch to the desired mode, i.e. H
HE
EA
AT
T, C
CO
OO
OL
L,
or A
AU
UT
TO
O.
Method 2
To reset the system at the unit, cycle the unit power by
turning the disconnect switch O
OF
FF
F and then O
ON
N
Lockouts can be cleared through the building
management system. Refer to the building
management system instructions for more
information.
Zone Temperature Sensor (ZTS)
Service Indicator
The ZSM SERVICE LED is a generic indicator that will
signal the closing of a Normally Open switch at any
time, providing the Indoor Motor (IDM) is operating.
This indicator is usually used to indicate an airside fan
failure.
The RTRM will ignore the closing of this Normally
Open switch for 2 (±1) minutes. This helps prevent
nuisance SERVICE LED indications.