Ingersoll-Rand EBC180-300 Скачать руководство пользователя страница 25

Start Up

RT-SVX50F-EN

25 

When there is a call for Cool 2, the second compressor is 
energized and the Supply Fan will switch to High Speed.

The unit will stage down compressors for cooling in 
reverse order that they were staged and the supply fan will 
follow the unit mode transitions. Once it is determined 
through normal cooling control that the second 
compressor is no longer necessary to meet cooling 
demand, the second compressor will be staged back and 
the supply fan will switch to Low Speed until the unit 
stages all cooling off or receives a call for Cool 2 again. 
Once the Supply Fan is no longer requested ON after a 
Cooling call is cleared, the Supply Fan will remain 
energized at Low Speed for 60 seconds as on traditional 
units.

If the economizer is enabled and is being utilized as the 
first stage of cooling (Y1 active), if the unit receives a Y2 
request, the unit will energize the first compressor and will 
switch the supply fan to high speed until the Y2 request is 
cleared.

Economizer Minimum Position Handling for 2-
Speed Fan

Due to the low and high speeds of the indoor fan, when the 
unit is in Fan Only, Cool 1, or Economizer Only and the 
indoor fan is at low speed, the unit will not be bringing in 
as much fresh air as normal. By setting a higher minimum 
damper position this problem could be solved, but that 
would mean more fresh air than may be desired when the 
supply fan is at high speed. To overcome these situations, 
the control will require the setting of two economizer 
minimum positions to be used when the fan is at low and 
high speed to compensate for the lower amount of fresh 
air at lower fan speeds and the potential for more fresh air 
than desired at higher fan speeds. These minimum 
positions will be obtained from the Bldg Design Min 
Position and DCV Min Position pots on the RTEM-EM. The 
economizer minimum position that will be utilized while 
the supply fan is at low speed will be set with the DCV Min 
Position pot with a range of 0-100% and the minimum 
position that will be utilized while the supply fan is at high 
speed will be set with the Building Design Min Position pot 
with a range of 0-50%. If the Building Design Min Position 
is set to be higher than the DCV Min Position, the setpoints 
will be capped at the DCV Min Position and the setpoint for 
the min position at low and high fan speed will be the DCV 
Min Position.

Phase Monitor

The phase monitor is a 3 phase line monitor module that 
protects against phase loss, phase reversal and phase 
unbalance. It is intended to protect compressors from 
reverse rotation. It has an operating input voltage range of 
190-600 VAC, and LED indicators for ON and FAULT. There 
are no field adjustments and the module will automatically 
reset from a fault condition.

Low Pressure Cutout

The low pressure cutouts are wired in series with the high 
pressure cutouts and the temperature discharge limits. If 
this circuit is open before a compressor is started, the 
compressor in that circuit will not be allowed to operate.

Anytime this circuit is opened, the compressor in that 
circuit is turned off immediately.

High Pressure Cutout and Temperature 
Discharge Limit

The high pressure controls and temperature discharge 
limit are wired in series between the compressor outputs 
on the LTB and the compressor contactors. If the high 
pressure safety or temperature discharge limit opens, the 
compressor on the affected circuit is turned off. 

Locking Safety Device with Compressor Anti 
Short Cycle Timer

This device monitors compressor safety switch trips to 
prevent short cycling, protecting the compressor. A 
manual reset is required after a fourth safety switch trip.

Coil Frost Protection

The Frostat™ control monitors the evaporator coil 
temperature to prevent the evaporator from freezing due 
to low operating temperatures whenever there is a 
demand for cooling. When a open circuit has occurred, the 
Frostat opens the 24VAC ground and opens all of the 
cooling contactors. 

Heating Operation

Standard unit operation for heating will continue on units 
equipped with a two-speed indoor fan. During heat mode, 
all units configured with staged electric or gas heat will 
heat the supply air and space as normal utilizing full speed 
indoor fan.

Emergency Stop

This input de-energizes the 24VAC output from the phase 
monitor and can be activated by opening a field supplied 
device connected to the LTB.

Содержание EBC180-300

Страница 1: ...ining Improperly installed adjusted or altered equipment by an unqualified person could result in death or serious injury When working on the equipment observe all precautions in the literature and on...

Страница 2: ...n minor or moderate injury It could also be used to alert against unsafe practices NOTICE Indicates a situation that could result in equipment or property damage only accidents WARNING Proper Field Wi...

Страница 3: ...ir respective owners Revision Summary Added Third Side Condenser Fork Access option Updated Model Number Description and Unit Weights Sections WARNING Follow EHS Policies Failure to follow instruction...

Страница 4: ...21 Unit Disconnect FIYUDC 21 Pre Start 22 Verifying Proper Air Flow Units with Belt Drive Indoor Fan 22 Electromechanical Controls Test Procedure 22 Start Up 23 Sequence Of Operation 23 Standard Econo...

Страница 5: ...Low Leak Economizer Dry Bulb w o Barometric Relief4 L Low Leak Economizer Reference Enthalpy w o Barometric Relief4 N Low Leak Economizer Comparative Enthalpy w o Barometric Relief4 Digit 15 Supply Fa...

Страница 6: ...porary heat is provided in the building Isolate all side panel service entrances and base pan openings e g conduit holes S A and R A openings and flue openings from the ambient air until the unit is r...

Страница 7: ...or the discharge line thermostat open the 24VAC signal from the thermostat is interrupted and the compressor is disabled There is no automatic lockout Power Exhaust Control Optional The power exhaust...

Страница 8: ...SOR wire and R terminal at customer connections The occupancy sensor must utilize a normally open contact for proper operation If an occupancy sensor is not used another option to controlling occupied...

Страница 9: ...nimum distances necessary to assure adequate serviceability cataloged unit capacity and peak operating efficiency Providing less than the recommended clearances may result in condenser coil starvation...

Страница 10: ...Dimensional Data 10 RT SVX50F EN Figure 2 Cooling with optional electrical heat units overview Figure 3 Cooling with optional electrical units front side views 15 25 tons standard efficiency...

Страница 11: ...al Data RT SVX50F EN 11 Figure 4 Cooling with optional electrical heat units plan view 15 25 tons standard efficiency Figure 5 Foundation units back view horizontal configuration 15 25 tons standard e...

Страница 12: ...ndard efficiency Figure 7 Downflow duct connections field fabricated 15 25 tons standard efficiency 9 1 25 4 MM CURB FLANGE LONG SIDES SHORT SIDES Notes Duct flanges mount 7 7 16 down inside the curb...

Страница 13: ...re 8 Downflow unit clearance 15 25 tons standard efficiency Figure 9 Barometric relief and economizer 15 25 tons standard efficiency MOTORIZED DAMPER BAROMETRIC RELIEF IS FOR USE WITH A DOWNFLOW ECONO...

Страница 14: ...Dimensional Data 14 RT SVX50F EN Figure 10 Manual damper 15 25 tons standard efficiency...

Страница 15: ...EBC180 2146 1826 621 475 365 365 56 37 17 EBC210 2155 1835 624 477 367 367 55 37 20 EBC240 2180 1860 632 484 372 372 55 37 25 EBC300 2206 1886 641 490 377 377 55 36 a Weights are approximate Horizont...

Страница 16: ...askets must be installed around the curb perimeter flange and the supply and return air opening flanges General Unit Requirements The checklist listed below is a summary of the steps required to succe...

Страница 17: ...mostat with or without switching subbase Connect properly sized control wiring to the proper termination points between the zone thermostat and the unit control panel Condensate Drain Configuration An...

Страница 18: ...ustrated below Refer to the customer connection diagram that is shipped with the unit for specific termination points The termination points depending on the customer option selected would be a factor...

Страница 19: ...Line Voltage reading that deviates the farthest from the average voltage Example If the voltage readings of the supply power measured 221 230 and 227 the average volts would be VD reading farthest fr...

Страница 20: ...o position Close the main power disconnect switch and the unit mounted disconnect switch if applicable Checklist Use the following checklist in conjunction with the general checklist General Unit Requ...

Страница 21: ...ty found on the unit nameplate and the N E C 4 Route low voltage class II control wiring through hole in base of unit but not through high voltage conduit Feedcontrolwiringthroughbushingprovided on si...

Страница 22: ...using the setpoint potentiometer located on the Economizer Control ECA if applicable Electromechanical Controls Test Procedure See unit schematic for correct wire numbers Fan Test and Minimum Ventila...

Страница 23: ...energizes the indoor fan relay coil F to start the indoor fan motor IDM The fan relay F de energizes after the cooling requirement has been satisfied When the heating cycle is terminated the indoor fa...

Страница 24: ...timer will prevent unit start up for three minutes Low Ambient Operation Optional During low ambient operation outside air temperature below 50 F the Low Ambient Controller will cycle the outdoor fan...

Страница 25: ...Building Design Min Position pot with a range of 0 50 If the Building Design Min Position is set to be higher than the DCV Min Position the setpoints will be capped at the DCV Min Position and the se...

Страница 26: ...eed fan DCV OA Good to economize Y1 I Y2 I FAN SPD Y1 O Y2 O Occupied Unoccupied Below CO2 set No Off Off High 0 v Off 0 v Off VENTMIN Closed On Off High 24 v On 0 v Off VENTMIN Closed On On High 24 v...

Страница 27: ...e Y1 I Y2 I FAN SPD Y1 O Y2 O Occupied Unoccupied Below set No Off Off High 0 v Off 0 v Off VENTMIN Closed On Off High 24 v On 0 v Off VENTMIN Closed On On High 24 v On 24 v On VENTMIN Closed Yes Off...

Страница 28: ...omize Y1 I Y2 I FAN SPD Y1 O Y2 O Occupied Unoccupied Below set No Off Off Low 0 v Off 0 v Off VENTMIN L Closed On Off Low 24 v On 0 v Off VENTMIN L Closed On On High 24 v On 24 v On VENTMIN H Closed...

Страница 29: ...onomize Y1 I Y2 I FAN SPD Y1 O Y2 O Occupied Unoccupied Below set No Off Off Low 0 v Off 0 v Off VENTMIN L Closed On Off Low 24 v On 0 v Off VENTMIN L Closed On On High 24 v On 24 v On VENTMIN H Close...

Страница 30: ...elay is defaulted to 5 minutes and can be changed in the Advanced Setup menu 2SP FAN DELAY When the unit has a call for Y1 In and in the free cooling mode and there is a call for Y2 In the 2 speed fan...

Страница 31: ...connect switch to the Off position or proceed to the next component start up procedure Remove electro mechanical test mode connections if applicable LLE Controls Test Procedure See unit schematic for...

Страница 32: ...ter contactor if applicable 4 Verify that the heater stage is operating properly 5 To stop the SERVICE TEST turn the main power disconnect switch to the Off position or proceed to the next component s...

Страница 33: ...s number represents the force in pounds required to give the needed deflection 6 Compare the force scale reading Step 5 with the appropriate force valuelistedin Table 16 p 33 Ifthe force reading is ou...

Страница 34: ...data on an operator s maintenance log like the one shown in Table 17 p 35 If the operating pressures indicate a refrigerant shortage measure the system superheat For guidelines refer to Compressor St...

Страница 35: ...zzle and the microchannel coil is 1 3 Final Process For future reference you may find it helpful to record the unit data requested below in the blanks provided 1 Complete Unit Model Number ___________...

Страница 36: ...ll exists after you clear it it re displays within 5 seconds Low Leak Economizer Fault Codes Low Leak Economizer Alarms CO2 Sensor Error SYS Alarm Actuator Undervoltage Actuator Overvoltage Actuator S...

Страница 37: ...hen the condensate overflow switch is closed a drain pan overflow condition is indicated and it will shut unit operations down Unit Economizer Control ECA Verify Economizer Status by Economizer Actuat...

Страница 38: ...matic Type Voltage Diagram Number Description Constant Volume Power 208 575 1213 2717 EBC180 300 60Hz Cooling only Electric Heat Control 208 575 1213 2724 EBC180 300 60Hz Cooling only Electric Heat Mu...

Страница 39: ...0 This warranty is for commercial usage of said equipment and not applicable when the equipment is used for a residential application Commercial use is any application where the end purchaser uses the...

Страница 40: ...t and protect food and perishables and increase industrial productivity and efficiency We are a global business committed to a world of sustainable progress and enduring results ingersollrand com Inge...

Отзывы: