Ingersoll-Rand EAC180-300AK Скачать руководство пользователя страница 15

RT-SVX052A-EN

15 

Installation

Unit Foundation

Horizontal Units

Notes:

For complete step by step instructions on how to install 
a Horizontal Conversion Kit, please refer to ACC-
SVN159*-EN.

For units with optional Condensate Overflow Switch 
(COF), the switch will not work properly if unit is not 
level or slightly sloped toward switch.

To assure proper condensate flow during operation the 
unit and the curb must be level.

If the unit is installed at ground level, elevate it above the 
snow line. Provide concrete footings at each support 
location with a “full perimeter” support structure or a slab 
foundation for support. Refer to 

Table 1, p. 14

 for the unit’s 

operating and point loading weights when constructing a 
footing foundation.

If anchoring is required, anchor the unit to the slab using 
hold down bolts or isolators. Isolators should be installed 
to minimize the transmission of vibrations into the 
building.

For rooftop applications, if anchoring is required, anchor 
the unit to the roof with hold-down bolts or isolators.

Check with a roofing contractor for proper waterproofing 
procedures.

Ductwork

Elbows with turning vanes or splitters are recommended 
to minimize air noise due to turbulence and to reduce static 
pressure.

When attaching the ductwork to the unit, provide a water- 
tight flexible connector at the unit to prevent operating 
sounds from transmitting through the ductwork.

All outdoor ductwork between the unit and the structure 
should be weather proofed after installation is completed.

Note:

For sound consideration, cut only the holes in the 
roof deck for the ductwork penetrations. Do not cut 
out the entire roof deck within the curb perimeter.

If a Curb Accessory Kit is not used:

a. The ductwork can be attached directly to the 

factory-provided flanges around the unit’s supply 
and return air openings. Be sure to use flexible duct 
connections at the unit.

b. For “built-up” curbs supplied by others, gaskets 

must be installed around the curb perimeter flange 
and the supply and return air opening flanges.

General Unit Requirements

The checklist listed below is a summary of the steps 
required to successfully install a commercial unit. This 
checklist is intended to acquaint the installing personnel 
with what is required in the installation process. It does not 
replace the detailed instructions called out in the 
applicable sections of this manual.

Check the unit for shipping damage and material 
shortage; file a freight claim and notify appropriate 
sales representative.

Verify correct model, options and voltage from 
nameplate.

Verify that the installation location of the unit will 
provide the required clearance for proper operation.

Assemble and install the roof curb (if applicable). Refer 
to the latest edition of the curb installers guide that 
ships with each curb kit.

Fabricate and install ductwork; secure ductwork to 
curb.

Rigging the unit.

Set the unit onto the curb; check for levelness.

WARNING

Risk of Roof Collapsing!

Confirm with a structural engineer that the roof 
structure is strong enough to support the combined 
weight of the roofcurb and the unit. Refer to 

“Unit 

Weights,” p. 14

 for typical unit and curb weights. Failure 

to ensure proper structural roof support could cause the 
roof to collapse, which could result in death or serious 
injury and property damage.

NOTICE: 

Water Damage! 

Non-factory penetrations through the base of this unit 
are not allowed. Any penetration in the base of the unit 
may affect the water tight integrity of the unit and lead 
to water leaks into the conditioned space. Failure to 
follow instructions could result in equipment and 
property damage.

WARNING

Proper Field Wiring and Grounding 
Required!

All field wiring MUST be performed by qualified 
personnel. Improperly installed and grounded field 
wiring poses FIRE and ELECTROCUTION hazards. To 
avoid these hazards, you MUST follow requirements for 
field wiring installation and grounding as described in 
NEC and your local/state electrical codes. Failure to 
follow code could result in death or serious injury. 

Содержание EAC180-300AK

Страница 1: ...ing Improperly installed adjusted or altered equipment by an unqualified person could result in death or serious injury When working on the equipment observe all precautions in the literature and on t...

Страница 2: ...icates a potentially hazardous situation which if not avoided could result in minor or moderate injury It could also be used to alert against unsafe practices NOTICE Indicates a situation that could r...

Страница 3: ...r contact a qualified service organization with qualified experienced HVAC technicians to properly diagnose and repair this equipment WARNING Proper Field Wiring and Grounding Required All field wirin...

Страница 4: ...tions 20 Unit Disconnect FIYUDC 20 Pre Start 21 Verifying Proper Air Flow Units with Belt Drive Indoor Fan 21 Electromechanical Controls Test Procedure 21 Start Up 22 Economizer Start Up 22 Compressor...

Страница 5: ...halpy 0 100 without Barometric Relief4 F Economizer Reference Enthalpy 0 100 with Barometric Relief1 4 G Economizer Comparative Enthalpy 0 100 without Barometric Relief4 H Economizer Comparative Entha...

Страница 6: ...o fieldadjustments andthe module willautomatically reset from a fault condition Discharge Line Thermostat Control The high pressure controls and discharge line thermostats are wired in series between...

Страница 7: ...rom forming inside the unit s electrical compartments and motors if The unit is stored before it is installed or The unit is set on the roof curb and temporary heat is provided in the building Isolate...

Страница 8: ...8 RT SVX052A EN Dimensional Data Figure 1 Typical installation clearance for single and multiple unit applications 5 8 5 0...

Страница 9: ...RT SVX052A EN 9 Dimensional Data Figure 2 Cooling with optional electrical heat units overview Figure 3 Cooling with optional electrical units front side views 15 25 tons standard efficiency...

Страница 10: ...52A EN Dimensional Data Figure 4 Cooling with optional electrical heat units plan view 15 25 tons standard efficiency Figure 5 Foundation units back view horizontal configuration 15 25 tons standard e...

Страница 11: ...ndard efficiency Figure 7 Downflow duct connections field fabricated 15 25 tons standard efficiency 9 1 25 4 MM CURB FLANGE LONG SIDES SHORT SIDES Notes Duct flanges mount 7 7 16 down inside the curb...

Страница 12: ...onal Data Figure 8 Downflow unit clearance 15 25 tons standard efficiency Figure 9 Barometric relief and economizer 15 25 tons standard efficiency MOTORIZED DAMPER BAROMETRIC RELIEF IS FOR USE WITH A...

Страница 13: ...RT SVX052A EN 13 Dimensional Data Figure 10 Manual damper 15 25 tons standard efficiency...

Страница 14: ...438 357 416 54 37 25 EAC300A 2208 1888 664 457 345 422 53 35 a Weights are approximate Horizontal and downflow unit and corner weights may vary slightly b Weights do not include additional factory or...

Страница 15: ...rs gaskets must be installed around the curb perimeter flange and the supply and return air opening flanges General Unit Requirements The checklist listed below is a summary of the steps required to s...

Страница 16: ...ion which could result in condensate backup due to air lock Filter Installation Each unit ships with 2 inch filters installed The quantity of filters is determined by unit size Access to the filters i...

Страница 17: ...anual Transformers rated greater than 50 Vac are equipped with internal circuit breakers If a circuit breaker trips turn Off all power to the unit before attempting to reset it The transformer is loca...

Страница 18: ...life If the voltage imbalance isover 2 percent notify the proper agencies to correct the voltage problem before operating this equipment Electrical Phasing Three Phase Motors The compressor motor s an...

Страница 19: ...e the following checklist in conjunction with the general checklist General Unit Requirements p 15 to ensure that the unit is properly installed and ready for operation Check all electrical connection...

Страница 20: ...ty found on the unit nameplate and the N E C 4 Route low voltage class II control wiring through hole in base of unit but not through high voltage conduit Feedcontrolwiringthroughbushingprovided on si...

Страница 21: ...0 using the setpoint potentiometer located on the Economizer Control ECA if applicable Electromechanical Controls Test Procedure See unit schematic for correct wire numbers Fan Test and Minimum Ventil...

Страница 22: ...ning a compressor interchange any two leads at the compressor Terminal block to check the internal phasing Refer to the following illustration for the compressor terminal phase identification Do not a...

Страница 23: ...ocedures outlined in the previous sections i e operating the unit in each of its modes through all available stages of cooling and heating perform these final checks before leaving the unit Program th...

Страница 24: ...s number represents the force in pounds required to give the needed deflection 6 Compare the force scale reading Step 5 with the appropriate force value listed in Table 5 p 24 If the force reading is...

Страница 25: ...6 p 26 If the operating pressures indicate a refrigerant shortage measure the system superheat For guidelines refer to Compressor Start Up p 22 Note Do NOT release refrigerant to the atmosphere If add...

Страница 26: ...nks provided 1 Complete Unit Model Number _____________________________________________________ 2 Unit Serial Number _____________________________________________________ 3 Wiring Diagram Numbers from...

Страница 27: ...nit operations down Unit Economizer Control ECA Verify Economizer Status by Economizer Actuator ECA LED indicator OFF No Power or Failure ON Normal OK to Economize Slow Flash Normal Not OK to Economiz...

Страница 28: ...low Schematic Type Voltage Diagram Number Description Constant Volume Power 208 230 380 2313 2202 EAC180 300 EAD180 300 60Hz Cooling only Electric Heat Control 208 230 380 2313 2207 EAC180 300 EAD180...

Страница 29: ...may also have other rights which vary from state to state Trane 2701 Wilma Rudolph Blvd Clarksville TN 37040 1008 Attention Manager Product Service GW 602 4800 This warranty is for commercial usage of...

Страница 30: ......

Страница 31: ......

Страница 32: ...portfolio of advanced controls and HVAC systems comprehensive building services and parts For more information visit www IRCO com The manufacturer has a policy of continuous product and product data...

Отзывы: