Ingersoll-Rand 4WCA4024A1000A Скачать руководство пользователя страница 17

88-4WCA4001-1A-EN

17

Step 5 — Unit Startup

P

Prre

e--S

Stta

arrtt Q

Qu

uiicckk C

Ch

he

ecckklliisstt

Is the unit properly located and level with the
proper clearances? See Figures 1 and 2.

Is the duct work correctly sized, run, taped,
insulated, and weatherproofed with proper unit
arrangement as shown in the ductwork installation
section?

Is the condensate line properly sized, run, trapped,
and pitched and shown in the Condensate Drain
Piping section?

Is the filter of the correct size and quantity? Is it
clean and in place? See Air Filter Installation
section.

Is the wiring properly sized and run according to the
unit wiring diagram?

Are all the wiring connections, including those in
the unit tight?

Has the unit been properly grounded and fused
with the recommended fuse size?

Is the thermostat well located, level, and correctly
wired? See Electrical Wiring section

Have the air conditioning systems been checked at
the service ports for charge and leak tested if
necessary?

Do the condenser fan and indoor blower turn free
without rubbing and are they tight on the shafts?

Has all work been done in accordance with
applicable local and national codes?

Are all covers and access panels in place to prevent
air loss and safety hazards?

S

Stta

arrttiin

ng

g tth

he

e U

Un

niitt iin

n C

Co

oo

olliin

ng

g M

Mo

od

de

e

N

No

otte

e:: See the section on Sequence of Operation for a

description of the cooling operating sequence.

To start the unit in the cooling mode, set the comfort
control to C

CO

OO

OL

L and to a setting below room

temperature. The condenser fan motor, compressor
and evaporator fan motor will operate automatically.
Continuous fan mode during Cooling operation may
not be appropriate in humid climates. If the indoor air
exceeds 60% relative humidity or simply feels
uncomfortably humid, it is recommended that the fan
only be used in the A

AU

UT

TO

O mode.

O

Op

pe

erra

attiin

ng

g P

Prre

essssu

urre

e C

Ch

he

ecckkss

After the unit has operated in the cooling mode for a
short period of time, install pressure gauges on the
gauge ports of the discharge and suction line valves
(behind the Compressor access panel). Check the
suction and discharge pressures and compare them to
the normal operating pressures provided in the unit’s
SERVICE FACTS.

N

No

otte

e:: Do not use the PRESSURE CURVES from the

unit's SERVICE FACTS to determine the unit
refrigerant charge. The correct charge is shown
on the unit nameplate. To charge the system
accurately, weigh in the charge according to the
unit nameplate and check subcooling against the
Subcooling Charging Table in the SERVICE
FACTS.

V

Vo

olltta

ag

ge

e C

Ch

he

ecckk

With the compressor operating, check the line voltage
at the unit (contactor is located behind the Control
access panel). The voltage should be within the range
shown on the unit nameplate. If low voltage is
encountered, check the size and length of the supply
line from the main disconnect to the unit. The line may
be undersized for the length of the run.

C

Co

oo

olliin

ng

g S

Sh

hu

utt D

Do

ow

wn

n

Set the comfort control to O

OF

FF

F or to a setting above

room temperature.

IIm

mp

po

orrtta

an

ntt:: De-energize the main power disconnect

ONLY when servicing the unit. Power may
be required to keep the heat pump
compressor warm and to boil off
refrigerant in the compressor.

S

Stta

arrttiin

ng

g tth

he

e U

Un

niitt iin

n H

He

ea

attiin

ng

g M

Mo

od

de

e

N

No

otte

e:: See the section on Sequence of Operation for a

description of the heat pump heating operating
sequence.

Check that all grills and registers are open and all unit
access panels are closed before start-up.

Set the comfort control above room temperature until
achieving a first stage call for heat and set the fan to
A

AU

UT

TO

O or O

ON

N.

H

He

ea

attiin

ng

g S

Sh

hu

utt D

Do

ow

wn

n

Set the comfort control to O

OF

FF

F or at a setting below

room temperature.

Содержание 4WCA4024A1000A

Страница 1: ...ment by an unqualified person could result in death or serious injury When working on the equipment observe all precautions in the literature and on the tags stickers and labels that are attached to t...

Страница 2: ...le ec ct tr ri ic ca al l c cu ur rr re en nt t a ar re e g gr ro ou un nd de ed d I If f g gr ro ou un nd di in ng g w wi ir re es s s sc cr re ew ws s s st tr ra ap ps s c cl li ip ps s n nu ut ts s...

Страница 3: ...ine Unit Clearances 5 Step 3 Review Location and Recommendation Information 7 Step 4 Unit Installation 8 Step 5 Unit Startup 17 Sequence of Operation 18 Heater and Airflow Tables 20 Maintenance 22 Imp...

Страница 4: ...t S Sh hi ip pm me en nt t 1 Check for damage after the unit is unloaded Report promptly to the carrier any damage found to the unit Do not drop the unit I Im mp po or rt ta an nt t To prevent damage...

Страница 5: ...88 4WCA4001 1A EN 5 Step 2 Determine Unit Clearances Figure 1 OUTLINE DRAWING...

Страница 6: ...5 1 32 712 3 28 1 32 712 3 28 1 32 568 8 22 13 32 568 8 22 13 32 568 8 22 13 32 568 8 22 13 32 645 0 25 13 32 645 0 25 13 32 460 1 18 1 18 460 1 18 1 18 460 1 18 1 18 460 1 18 1 18 510 9 20 1 8 510 9...

Страница 7: ...on for instruction on converting the supply and return airflow covers to down airflow 3 The field assembled Roof Mounting Curb BAYCURB060A or a field fabricated curb should be in place before the unit...

Страница 8: ...of the structure with at least two 2 inches of insulation and weatherproof There must be a weatherproof seal where the duct enters the structure 5 Do not expose the unit to direct roof water runoff 6...

Страница 9: ...ATHERPROOF OR RAIN SHIELD FLEXIBLE DUCT CONNECTORS OUTDOOR AIR DISCHARGE SUPPORT PAD FOUNDATION Table 1 Recommended Service Clearance Recommended Service Clearance BACK SIDE LEFT SIDE RIGHT SIDE FRONT...

Страница 10: ...ng requires accessory kit BAYLIFT002A It includes a kit of four 4 lifting lugs 2 Insert the four lifting lugs in the openings provided in the drip lip on each end of the unit A tap or jerk to the lug...

Страница 11: ...provide unit dimensions 11 Continue with the following installation sections to complete the installation Ductwork Filter and Electrical Wiring R Ro oo of ft to op p I In ns st ta al ll la at ti io o...

Страница 12: ...op Horizontal Airflow Application with Frame Supply Air Return Air Roof Flashing Channel Iron Center Support Center Support required on all frame applications Angle Iron Frame S St te ep p 4 4 U Un ni...

Страница 13: ...w these guidelines for ductwork construction Connections to the unit should be made with three 3 inch canvas connectors to minimize noise and vibration transmission Elbows with turning vanes or splitt...

Страница 14: ...st be Made of 3 4 pipe size Pitched 1 4 per foot to provide free drainage to convenient drain system Trapped Must be connected to a closed drain system unless the trap is properly vented Figure 8 Typi...

Страница 15: ...problem within the building structure 1 Remove the Control Heat access panel Pass the power wires through the Power Entry hole in the end of the unit 2 Connect the high voltage wires to the appropria...

Страница 16: ...iring unless Class 1 wire of proper voltage rating is used Route the thermostat cable or equivalent single leads of No 18 AWG colored wire from the thermostat subbase terminals through the rubber grom...

Страница 17: ...y be used in the A AU UT TO O mode O Op pe er ra at ti in ng g P Pr re es ss su ur re e C Ch he ec ck ks s After the unit has operated in the cooling mode for a short period of time install pressure g...

Страница 18: ...rought on when the indoor temperature drops 1 1 2 degrees below the thermostat setting T TS SH H 2 2 contacts close providing power to the W W terminal on the indoor thermostat and to the supplementar...

Страница 19: ...essor operating correctly and has the system been checked with a charging chart Has the voltage and running current been checked to determine if it is within limits Has the thermostat been checked for...

Страница 20: ...0 4 0 5 0 6 0 7 0 8 0 9 1 Low CFM 898 835 773 710 WATTS 112 119 126 132 Medium CFM 931 880 822 764 705 WATTS 230 239 248 256 262 High CFM 917 WATTS 386 4WCA4030A1 ESP 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0...

Страница 21: ...7 0 8 0 9 1 Low CFM 1673 1596 1515 1441 1372 WATTS 348 365 380 393 404 Medium CFM 1802 1725 1645 1579 1514 1446 1391 WATTS 427 446 464 478 491 502 521 High CFM 1794 1721 1658 1590 1530 1475 1432 1391...

Страница 22: ...and drive system components economizer gaskets for possible replacement safety controls for mechanical cleaning electrical components and wiring for possible replacement and connection tightness conde...

Страница 23: ...88 4WCA4001 1A EN 23 N No ot te es s...

Страница 24: ...ency We are a global business committed to a world of sustainable progress and enduring results ingersollrand com The AHRI Certified mark indicates Ingersoll Rand participation in the AHRI Certificati...

Отзывы: