88-4WCA4001-1A-EN
13
Table 4.
Typical Rooftop Down Airflow Application with Frame
Return Air
Roof Flashing
Channel Iron Center Support
(center support required on all
frame applications).
Angle Iron Frame
Roof
Flashing
Supply
Air
D
Du
uccttw
wo
orrkk IIn
nsstta
alllla
attiio
on
n
A
Atttta
acch
hiin
ng
g D
Do
ow
wn
nffllo
ow
w D
Du
uccttw
wo
orrkk tto
o R
Ro
oo
off C
Cu
urrb
b
Supply and return air flanges are provided on the roof
curb for easy duct installation. All ductwork must be
run and attached to the curb before the unit is set into
place.
A
Atttta
acch
hiin
ng
g D
Do
ow
wn
nffllo
ow
w D
Du
uccttw
wo
orrkk tto
o R
Ro
oo
off F
Frra
am
me
e
Follow these guidelines for ductwork construction:
Connections to the unit should be made with three (3)
inch canvas connectors to minimize noise and vibration
transmission.
Elbows with turning vanes or splitters are
recommended to minimize air noise and resistance.
The first elbow in the ductwork leaving the unit should
be no closer than two (2) feet from the unit, to minimize
noise and resistance.
To prevent leaking, do not attach the ductwork to the
bottom of the unit base. Refer to the bottom example in
the figure below.
Figure 5.
Attaching Down Airflow Ductwork
FIELD DUCT
UNIT DUCT
FLANGE
UNIT BASE
AIR PROOF
THIS SEAM
FIELD DUCT
UNIT DUCT
FLANGE
UNIT BASE
AIR PROOF
THIS SEAM
FIELD
DUCT
UNIT DUCT FLANGE
UNIT BASE
AIR PROOF
THIS SEAM
FIELD DUCT
UNIT DUCT
FLANGE
UNIT BASE
NOT RECOMMENDED
WATERPROOF SEAM
WITH BUTYL OR
SILICONE
S
Stte
ep
p 4
4 —
— U
Un
niitt IIn
nsstta
alllla
attiio
on
n