Vacuum pump

INSTALLER

Humid air left inside the refrigerant circuit can cause com-
pressor malfunction. After having connected the indoor
and outdoor units,

evacuate

the air and humidity from the

refrigerant circuit using a vacuum pump.

(1) Unscrew and remove the caps from the 2-way and 3-

way valves.

(2) Unscrew and remove the cap from the service valve.
(3) Connect the vacuum pump hose to the service valve.
(4) Operate the vacuum pump for 10-15 minutes until an

absolute vacuum of 

350 microns

 has been reached.

(5) With the vacuum pump still in operation, close the

low-pressure knob on the vacuum pump coupling. Stop
the vacuum pump.

(6) Open the 2-way valve by 1/4 turn and then close it

after 10 seconds.Check all the joints for leaks using
liquid soap or an electronic leak device.

(7) Turn the body of the 2-way and 3-way valves. Discon-

nect the vacuum pump hose.

(8) Replace and tighten all the caps on the valves.

Evacuation

INSTALLER

INDOOR

UNIT

Vacuum pump

Vacuum pump

Connect to the

indoor unit

Twisting moment (

lbf-inch

)

274

-

310

443

-

487

531

-5

75

70-75

ĭ

5/8"

ĭ

3/4"

Diameter (

inch

)

ĭ

3/8"

ĭ

1/2"

1

33

-

177

ĭ

1/4"

(9) If the specification of outdoor unit gas valve is 3/8

,

     but curstomer needs to install 1/2

indoor unit so that 

     it is need to use a “pipe joint subassembly” (Code 06643008) 
     to make a conversion joint with outdoor unit gas valve and 
     connection pipe, as show in following.

conversion joint

Refrigerant fluid direction of flow

3-way valve

2-way valve

Ser vice
inlet

(2)Turn
(8) Secure

(7)Turn to open fully

(2)Turn

(8) Secure

Valve cap

(6) Open by 1/4 turn

(7)Turn to open fully

(2)Turn

(8) Secure

Valve cap

9

Drain-water hole

Bottom frame

Drain plug

Hose (available commercially,
inner dia. 16mm)

Drain connecter

Use bolts to secure the unit to a flat, solid floor.
When mounting the unit on a wall or the roof, make
sure the support is firmly secured so that it cannot
move in the event of intense vibrations or a strong
wind.

Do not run the refrigerant lines in pits or air vents

Install the drain fitting and the drain hose(for
model with heat pump only)

Condensation is produced and flows from the outdoor unit 

when the appliance is operating in the heating mode. In order
not to disturb neighbours and to respect the environment,
install a drain fitting and a drain hose to channel the conden-
sate water. Install the drain fitting and rubber washer on the 
outdoor unit chassis and connect a drain hose to it as shown 
in the figure.

Use suitable connecting pipes and equipment for the 
refrigerant R410A.

Wrap all the  refrigerant pipes and joints.

Tighten the connections using two wrenches working 

in opposite directions.

Caution: Installation Must be Performed in Accordance

with the NEC/CEC by Authorized Personnel Only

The refrigerant pipes must not exceed the maximum

heights

16ft

(18K) or 

33ft

(24K

,

30

 & 42

K).

INSTALLING THE OUTDOOR UNIT

Models( )

18K

24

,

30

,42

K

Maximum equivalent length for all
piping with multiple indoor units.

66

230

Max. connection pipe length(Simple
one indoor unit)

33

66

ft

Warning and Caution

Содержание 4TXM6518A1

Страница 1: ...upersedes September 2012 MS SVN 25A EN The manufacturer has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice Only q...

Страница 2: ...OSION which could result in death or serious injury WARNING Electrocution and Fire Hazards with Improperly Installed and Grounded Field Wiring Improperly installed and grounded field wiring poses FIRE...

Страница 3: ...ONFORMITY AND RANGE GENERAL INFORMATION GENERA L INFORMATION Please read this owner s manual carefully before operating the unit and keep it in a safe place for future reference The air conditioner yo...

Страница 4: ...wires If the power cable and signal control wire were damaged change them by professional Otherwise it may cause electric shock or damage Rated voltage of this air conditioner 208 230V 60Hz The compre...

Страница 5: ...person in order to avoid a hazard OUTDOOR UNIT No Description 1 Air outlet grille 2 Valve 1 2 3 GENERAL INFORMATION The temperature of refrigerant circuit will be high please keep the interconnection...

Страница 6: ...230V 1 60Hz Refrigerant gas R410A 4TXM6530A1040BA Minimum power cable section 20 12 AWG oz in in in in in L P H A B Fuse or air switch 48 32 2 15 0 23 5 21 7 14 0 MODE Electricity supply Electrical d...

Страница 7: ...power supply To unit B cable cable To unit A 5 4TXM6518A1020BA 4TXM6518A1020BA L1 L2 L1 L1 L2 L2 ELECTRICAL CONNECTIONS INSTALLER cable cable cable 5 power cable and power cable with the terminal at t...

Страница 8: ...ational wiring regulations Note the above figures are only intended to be a simple e h t o t d n o p s e r r o c t o n y a m d n a e c n a i l p p a e h t f o m a r g a i d appearance of the units tha...

Страница 9: ...onnection cable should be put in from hole A B and C 4 If connecting with four indoor units the connection cable should be put in from hole A B C and D All power cables and connection cables must be p...

Страница 10: ...with four indoor units the connection cable should be put in from hole A B C and D All power cables and connection cables must be protected with conduits After having removed the packaging check that...

Страница 11: ...irection of flow 3 way valve 2 way valve Service inlet 2 Turn 8 Secure 7 Turn to open fully 2 Turn 8 Secure Valve cap 6 Open by 1 4 turn 7 Turn to open fully 2 Turn 8 Secure Valve cap 9 Drain water ho...

Страница 12: ...ase refer to the actual product 10 4TXM6530A1040BA 4TXM6524A1030BA 4TXM6530A1040BA 4TXM6542A1050BA INSTALLER Use suitable instruments for the refrigerant R410A Do not use any other refrigerant than R4...

Страница 13: ...break down or the components may be burned out Have the length of refrigerating pipe and refrigerant charge amount been recorded 11 Notes a The refrigerant charge mentioned in the technical data does...

Страница 14: ...Mode Priority First Unit ON Cool All Other Units Cool Off Fan First Unit ON Fan All Other Units Cool Off 6 If a Mode Priority unit is set to FAN and another unit is turned to Heat Mode the Fan will s...

Страница 15: ......

Отзывы: