VRF-SVX26D-EN
27
Configuration
15
External control output/
External heater signal/
Cooling operation signal/
Free cooling control signal
(a)
0: External control (Thermo On)
1: External control (Operation On)
2: External heater signal (Fan on)
(a)
3: External heater signal (Fan off)
(b)
4: Cooling operation signal
(c)
5: Free Cooling control (Cooling Thermo On)
6. Free Cooling control (Cooling/Dry Thermo On)
(a)
When used as external heater On/Off signal, the fan runs continually when the
external heater is On.
(b)
When used as external heater On/Off signal, the fan is Off when the external
heater is On with indoor unit in Cooling Only. (For Cooling Only mode, install the
mode selector (TVCTRLTCMC2000) on the outdoor unit and set it to Cooling mode.)
If the fan is set to Off and the unit is in Cooling Only mode, an external sensor or
wired remote controller is required to detect the current indoor temperature.
(c)
When the indoor unit is in Cooling or Dry mode, the contacts are closed.
17
Buzzer
0: Enabled
1: Disabled
18
Filter timer (hours of use)
2: 1000
6: 2000
N/A
19
Factory set to 3
Cannot be changed. Not seen in configuration mode.
20
Associating wireless remote
control with indoor unit(s)
0, 1: Channel 1
2: Channel 2
3: Channel 3
4: Channel 4
21
Heat setting compensation
22
Adjusted EEV position of
Thermo Off unit during oil
return/defrost mode
0: Default EEV position
1: Reduced EEV position
(a) Digit 15 requires that an external contact interface module be connected. Refer to VRF-SVN54*.
Table 1.
Installation option #1: Digit 2 = 2 (continued)
Display
screen
(mode and
On/Off)
Digit
Option description
Set digit to...
Heat setting compensation
Removing condensate in heating mode
(a)
(a) The fan operates (20 min. maximum), even after the indoor unit is turned off,
to remove condensate from an indoor unit that has switched from cooling to
heating mode. Applies to drain pump models only.
0: Disabled
Disabled
1: 3.6°F (2°C)
Disabled
2: 9°F (5°C)
Disabled
3: Disabled
Enabled
4: 3.6°F (2°C)
Enabled
5: 9°F (5°C)
Enabled