Sunpak® Infrared Heaters 

8

Fire Sprinklers 

Fire Sprinklers must be located at an appropriate 

distance from each heater to avoid accidental 
activation of the sprinkler. Ethylene glycol or 
propylene glycol must never be used in fire sprinkler 
systems where heaters are present as these 
substances may become flammable when heated.  A 
fire sprinkler professional must be consulted when 
heaters are installed where fire sprinklers are 
present to insure that heaters and the fire sprinkler 
system are properly integrated. Specific guidelines 
can be found in NFPA 13 regarding design and 
specifications for Fire Sprinkler Systems near 
heaters.

 WARNING 

Suspension Hazard 

Mounting kits and hanging supports must 
be able to withstand a minimum working 
load of 75 lbs (33 kg). Failure of the 
supports can result in death. 

Local codes regarding head clearance 
requirement must be observed. 

Heater Mounting and Support 

Heaters shall be mounted in a fixed position 
independent of gas and electrical supply line. 
Hangers and brackets shall be of noncombustible 
material.

Heaters subject to vibration shall be provided with 

vibration isolating hangers. 

Suitable materials for hanging infrared heaters are 

steel pipe, steel channel, or fabricated hangers of at 
least 16-gage material. Hanger and brackets must 
be secured with adequate anchor to a secure 
structure using good building practices. Additional 
bracing to protect against seismic forces may be 
required in seismically active areas. 

CAUTION

Sharp Edges 

Every effort has been made to remove sharp 
edges from this heater; however care should 
be taken to avoid injury when reaching inside 
the heater during installation and when 
servicing this unit. 

Electrical

1.  Provide only 24 VAC with a NEC Class 2 transformer to 

the heaters. Each heater requires approximately 20VA 
or 0.8 amps. When multiple heaters are connected to 
one transformer, the transformer must be sized to 
accommodate the entire load. A transformer must 
NEVER be located inside the heater control 
compartment. 

2.  Control wire used to electrically connect one or more 

heaters together must have adequate capacity and 
insulation temperature rating for the total connected 
load. Use at least 18 GA wire up to 50 feet from heater 
to transformer or wall switch. Use a minimum of 16 GA 
wire for over 50 feet distance. 

3.  If any of the original wire supplied with the appliance 

must be replaced, it must be replaced with wiring 
material having a temperature rating of at least 105 
degrees Centigrade. 

 WARNING 

Electrical Shock Hazard 

Disconnect electrical power and gas supply before 
servicing 

This heater must be connected to a properly 
grounded electrical source. 

Failure to follow these instructions can result in 
death or electrical shock. 

Содержание Sunpak S25

Страница 1: ...is equipment Installation and replacement of gas piping gas utilization equipment or accessories and repair and servicing of equipment shall be performed by a qualified agency familiar will all precautions required regarding this type of equipment and that has complied with all requirements of the authority having jurisdiction Infrared Dynamics SUNPAK Gas Fired Unvented High Intensity Infrared Hea...

Страница 2: ...ds the flame sensor will shut OFF the gas valve To relight the pilot and burner shut OFF power Wait 5 minutes Turn power back ON If the heater will not light turn the manual gas valve to OFF position and the electrical switch OFF to the heater and call your quality service agency or gas supplier Shutting Down Your Heater Turn electrical power to the heater OFF Should you need to shut down your hea...

Страница 3: ...options Sunpak heaters may be laid out in a number of configurations depending on the structural constraints of the patio and heating requirements One approach is to face heaters straight down over the table and seating areas Another approach is to locate heaters to the side and to angle them inward A third approach is to cluster the heaters in the center of the patio and angle heaters outward It ...

Страница 4: ...e the patio environment Wind breaks shall NOT interfere with the ventilation of combustion air requirement of the heater s ANGLE MOUNTING Most models of the SUNPAK heater may be angle mounted to a maximum of 30º to accommodate mounting the heaters around the edges of the patio Note that the top clearance to combustibles increase when heater is tipped from the horizontal NOTE Local codes may have s...

Страница 5: ...Sunpak Infrared Heaters 5 ...

Страница 6: ...pply pressure and manifold pressure required for each heater are listed below For gas supply line pressures in excess of psig consult with your representative or the factory Gas Inlet Pressure Nat Gas Propane Maximum Pressure psig psig Minimum Pressure 6 W C 11 W C Manifold Pressure 5 W C 10 W C It is important that the gas piping system be adequately sized for all the gas appliances it serves Cle...

Страница 7: ...Sunpak Infrared Heaters 7 ...

Страница 8: ...anger and brackets must be secured with adequate anchor to a secure structure using good building practices Additional bracing to protect against seismic forces may be required in seismically active areas CAUTION Sharp Edges Every effort has been made to remove sharp edges from this heater however care should be taken to avoid injury when reaching inside the heater during installation and when ser...

Страница 9: ...se an open flame Use a soap and water solution 6 For gas supply line pressures in excess of psig consult the factory or your local representative 7 Installation of 1 8 N P T plugged tapping accessible for test gage connections is required upstream of the gas supply connections to the heater Initial Start Up Procedure 1 Before turning on the manual gas valve to the heater verify that the control sy...

Страница 10: ...e end of the burner Carefully slide burner down and out When reinstalling be sure both ends of the burner are beneath the reflector end flanges g To reinstall burner reverse procedure 2 Removal of RAM 3 Direct Spark Ignition Control a Disconnect two 24 VAC power leads b Disconnect two gas valve leads c Disconnect igniter lead from control d Disconnect green ground lead from casing e Remove two 2 8...

Страница 11: ...Sunpak Infrared Heaters 11 ...

Страница 12: ...Sunpak Infrared Heaters 12 ...

Страница 13: ...Sunpak Infrared Heaters 13 ...

Страница 14: ...Sunpak Infrared Heaters 14 ...

Страница 15: ...eterioration of Front Grill Sunpak heater must be installed in such a manner as to allow the products of combustion or hot gases to vent out the top of the heater When operating normally only radiant heat passes through the front grill If conditions exist which force hot gases through the front grill of the heater the installation must be altered to correct the condition Rumbling Burner Noise Rumb...

Страница 16: ...livery charges for forwarding the new heater or replacement part from the nearest distributor and returning the claimed defective heater or part to such distributor c All cost necessary or incidental for handling and administrative charges and for any materials and or permits required for installation of the replacement heater or part LIMITATION ON IMPLIED WARRANTIES Implied warranties including a...

Отзывы: