INFOSEC UPS SYSTEM – 4 rue de la Rigotière – 44700 Orvault – France – www.infosec-ups.com
Hot Line Tel : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 – [email protected] – 11 11 AA 68 203 16
57
7.
Specifications
E6 LCD 5000 RT
E6 LCD 6000 RT
E6 LCD 8000 RT
E6 LCD 10K RT
E6 LCD 10K RT TM
NPUT
Voltage Range (VAC)
160 - 280
277 - 485
Frequency (Hz)
45 / 65 Hz
Number of phases
Single phase + ground
Three phase, R, S, T +
N Ground
Input Power factor
> 0,99 (full load)
THD
<7%
<30%
OUTPUT
Voltage Range (Vac)
200 / 208 / 220 / 230 / 240 adjustable (120 VAC optional)
Voltage adjustment
Nominal v 1%, + 2%, + 3%, - 1%, - 2%, - 3%
Voltage regulation
± 2%
Capacity
5000 VA / 4500 W
6000 VA / 5400 W
8000 VA / 7200 W
10000 VA / 9000 W
10000 VA / 9000 W
Power Factor
0,9
Output wave form
Sine wave, THD <3% (from 0 up to 100% of load)
Frequency stability
± 0,2% (battery mode)
Frequency regulation
+/-1Hz or +/-3Hz (programmable by user)
Transfer time
0 ms
Crest factor
3:1
Efficiency
Up to 90% (normal mode) ; Up to 95% (Eco mode)
Nominal autonomy
> 3 min
> 8 min
> 5 min
Cold start
Yes
BATTERY
Capacity
12V / 5 Ah
12 V/ 7 Ah
12 V/ 7 Ah
12 V/ 9 Ah
Quantity
20
Voltage (V)
240
Recharge time
4 hours at 90%
5 hours at 90%
DISPLAY
Status on LCD and LED
Normal, Battery, Eco mode, Bypass, Battery low, Default battery, Overload and Inverter default
Data specified on LCD
Input voltage and frequency, Output voltage, Frequency voltage, Charge level, Voltage battery, internal Temperature
Self-diagnostics
In mains mode, from control panel , by software and auto test/ 24h
PROTECTION
Short circuit
Off mode immediately
Over heating
Mains mode : Bypass Transfer - Battery Mode : Automatic shutdown
Low battery
Alarm and automatic stop
EPO
Switch off immediately
Battery
Electronic system of management of battery discharge
Leakage current
< 3 mA in full load
ALARMS
Acoustics & display
Mains default / Low battery / Overload / Environment default
PHYSICALS CHARACTERISTICS
Mechanicals dimensions
(H x W x D) mm
176 x 440 x 680 (4U)
88 x 440 x 680*(2U)
132 x 440 x 680* (3U)
132 x 440 x 680* (3U)
Net battery weight
52 Kg
24+68 Kg
26+68 Kg
26+68 Kg
52 Kg
Input & Output connectors
Terminal board
ENVIRONMENT
Operating temp, range
0-40°C
Warning temperature
Battery design for use at 25°C. A higher ambient temperature will decrease its life span
Altitude
0-2000 m up to 40°C / 3000 m up to 35°C
Humidity
90% max without condensation
Noise
< 50dB (at 1 m)
INTERFACE COMPUTER
Type
Standard RS 232
Slots
Second RS 232, USB, RS 485, relay card, SNMP/ Web card
compatible systems
Windows 95/98/NT/2000/XP/Vista, Novell Netware, Linux etc
COMPLIANCE
Security
EN62040-1-1, UL1778
Standard EMC
IEC/EN 62040-2 class A ; IEC/EN 61000-4-2/-3/-4/-5/-6/-8 ; IEC/EN61000-2-2 ; IEC/EN 61000-3-2/-3
Marking
CE, cUL
*UPS without battery bank