135
INFOSEC UPS SYSTEM
–
15, Rue du Moulin
–
44880 Sautron
–
France
–
www.infosec-ups.com
Hot Line Tel : +33 (0)2 40 76 15 82
–
fax : +33(0)2 40 94 29 51
–
–
02 19 AA 59 203 07
Fault! CAN Fault
CAN communication fault
Contact service personnel.
Fault! TRIG0 Fault
Synchronized trigger signal fault
Contact service personnel.
Fault! Relay Fault
Inverter relay fault
Contact service personnel.
Fault! Line SCR Fail
Line SCR short circuit fault
Contact service personnel.
Fault! EEPROM Fault
EEPROM operation error
Contact service personnel.
Fault!
Parallel
Cable
Loosen Fault
As stated.
Check if the parallel cable is loose
and contact service personnel.
Fault! DSP MCU Stop
Communicate
As stated.
Contact service personnel.
Fault!
Bypass
Temperature Fault
As stated
Check if the ambient temperature
is over specification.
Or contact service personnel.
Fault! Bypass SCR Fault
As stated.
Contact service personnel.
Warning! EPO Active
Check the EPO connector
Check if the connector is loose
when EPO acts abnormally.
Warning! Over Load Fail
The load devices are demanding more
power than the UPS can supply. Line
mode will transfer to Bypass mode.
Reduce some load and check
output
Load-Capacity
and
specification
Warning!
Communicate
CAN Fail
CAN communication error
Contact service personnel.
Warning! Over Load
In Line mode, the load devices are
demanding more power than the UPS
can supply.
Reduce some load and check
output
Load-Capacity
and
specification
Warning! Battery Open
Battery is not connected.
5. Check battery breaker.
6. Check
if
the
battery
connection is well connected.
7. Check the setting of Nominal
Battery voltage.
8. Contact service personnel if
necessary.
Warning! Battery voltage
High
Battery voltage is too High
Check the setting of Nominal
Battery voltage and contact
service personnel.
Warning!
Turn
On
Abnormal
As stated.
Check if the input voltage or
frequency is out of range.
Warning! Charge Fail
As stated.
Contact service personnel.
Warning! EEPROM Fail
EEPROM operation error
Contact service personnel.
Warning! Fan Lock
As stated.
Check if the fan is blocked or
contact service personnel.
Warning! Line Phase Error As stated.
Check if the Mains phase
sequence is correct and contact
service personnel.
Warning! Bypass Phase
Error
As stated.
Check if the Bypass phase
sequence is correct and contact
service personnel.
Warning! N Loss
Neutral loss
Check if the Neutral connection is
well
and
contact
service
personnel.
Warning! Internal Initial
Fail
As stated.
Contact service personnel.