32
By-pass Line
Phase number
1
Nominal frequency
50 Hz
Nominal power (kVA)
15000 VA
Nominal active power
10500 W
Nominal voltage
220 V Nominal
current
68
A
Fuse value used in the panel
80Amp – C type
Bypass input voltage range
198V – 242V
Bypass input frequency range 47Hz – 53Hz
NOTE By-pass voltage and frequency are software parameters and can be changed upon request
Transfer Time
0 ms
Batteries
Battery type
Sealed Maintenance free lead acid
The quantity and capacity of batteries located inside the ups cabinet
Nominal battery
voltage(per bat)
Battery capacity
(per battery)
App. Weight
(per battery)
Battery Quantity
Total nominal
battery voltage
Total battery
weight
12 V
12 Ah
4,1 kg
32
384 V 131,2
kg
12 V
17 Ah
6,0 kg
32
384 V 192
kg
Approximate bridging times
Full load
32 pcs 12 Ah battery
7,5 min
Half Load
32 pcs 12 Ah battery 22
min
Full load
32 pcs 17 Ah battery
13 min
Half Load
32 pcs 17 Ah battery 35
min
Battery Recharge Time ( for 32 pcs 12 Ah battery)
App. 8 Hours
Battery Recharge Time ( for 32 pcs 17 Ah battery)
App. 12 Hours
Temperature controlled battery charging
General Specifications
Audible Noise (1m away from the front of the unit)
<55 dB
Isolated Free Contact communication and serial communication ( RS232 ) according to EN60950
At Normal Operation (online & battery operation) : electronic short circuit protection
At Normal Operation (online & battery operation): overload capability
At Normal Operation (online & battery operation) : capability of holding inrush currents
Overtemperature, Overvoltage, Overcurrent and battery deep discharge protections
LCD Display
Standards
Protection Class
IP 20
EMC EN
50091-2
Performance
EN 62040-3, EN 50091-3
Safety EN
50091-1