OUTFLR (Output Failure) mode:
o
Check the loads. Disconnect the excess loads and short-circuited loads if any.
o
Check the environment temperature; be sure that there is enough ventilation space around
the ups.
o
Check the Fans whether they are running properly or not, if there is a problem on the fans
than call the authorized staff.
o
By pressing the “I” button, try to restart the ups. If the failure happens again than call the
authorized staff.
During the normal operation of the ups, the possible situations, that can be faced and the things that
should be done in such situations are explained details in the following Trouble Shooting Chart:
Any audible
alarm ?
Is it at
ONLINE
mode?
Is it at
BYPASS
mode?
Is it at
SHUTD
mode?
Is it at
WTMNS
mode ?
As a running mode “normal” is
selected. Unit is online
working.
As a running mode “Green
Mode” is selected. The unit is
working at By-pass Mode.
The unit is running but the
ouput is switched off. With I
button start the unit.
Switched off by the comment
received from Comm. Interface
It is on mains waiting mode. It
will switch on automatically
when the mains come back.
Check the connections and
fuses than restart the unit.
Is it at BATTR
mode?
Is there a BUV
alarm?
Is there a
OVLD alarm?
Battery voltage is low. After
obtaining the data security, switch
off the loads.
There is exceeding load in the
circuit. Disconnect the unnecassary
loads.
Is there a
OVTE alarm?
Cooler or junction temperature is
too high. Check the environment
temperature, decrease it if
necassary.
Is there a
BOVTE
alarm?
The air temperature in the air
entrance of the unit is too high.
Check the environment temp. ,
decrease it if necassary.
Is there a
BATTF alarm?
Battery test result is negative.
Inform the authorised staff.
Is there a
BFUFL alarm?
Battery fuse is switched off. Switch
on it. If the same failure happens
again, call the authorised staff.
Is there a
FANFLR
alarm?
Fan is not working, call the
authorised staff.
Is “0” written
on the running
type section?
By pressing “I” button, run the ups
at normal mode.
Is it at
BYPASS
mode?
Is it at
OUTFLR
mode?
Is it at
INVFLR
mode?
Unit has passed to by-pass because
of some irregularities. For a long
time if it does not pass to online or
battery mode or the audible alarm
does not stop, call technical service
Unit has switched off its output temporarily because of a
possible fixable problem. The loads are unenergised. After the
Overload, short circuit, temperature controls and necassary
corrections, by pressing “I” button restart the unit.
Most probably there is a failure on the unit. Disconnect all the
loads and By using the “I” button, start the unit. If the same
situation repeats again than call the technical service.
Inform the technical service.