Infocharger 

DC POWER SUPPLY/BATTERY CHARGER 

 

 

 

 

 

 

 

 

 

 

 

Содержание Infocharger

Страница 1: ...Infocharger DC POWER SUPPLY BATTERY CHARGER...

Страница 2: ...tions For the staff and equipment safety it is necessary for the users to fully read and save this manual before working on this equipment Description of the Symbols IMPORTANT NOTICE Please follow the...

Страница 3: ...connection 5 4 Switch On and Switch OFF procedures 6 4th1 System Switch ON 6 4th2 System Switch OFF 6 5 Operating Instructions 7 5th1 Unit Operation 7 5th1 1 Operation modes 7 5th2 Displays 8 5th2 1...

Страница 4: ......

Страница 5: ...missioning have to be done by authorized technical service Earth Ground connection should be done Do not plug in off the communication interface cables during bad weather conditions with lightning To...

Страница 6: ...ing on the battery type These are initial charge float charge boost charge and temperature or auto controlled charging types The charge voltages per cell for initial charge 2 04V for float charge 2 23...

Страница 7: ...Battery Charger features and benefits Feature Benefit PWM technology Transformerless design Compact design small dimensions and low weight Microprocessor controller To use all the sources in optimum...

Страница 8: ...3rd1 Handling If needed to move the battery charger it is obligatory to pack the unit It is suggested to keep the original packing 3rd2 Storage Please store the battery charger in an environment wher...

Страница 9: ...onnection between the grounding unit of the Infocharger and the ground can be made according to the minimum cross sectioned cables which are given in the technical specifications table below 3rd4 2 In...

Страница 10: ...he automatic fuses on the front panel if mains voltage is within the limits the unit switches on Inforcharger makes self test for few seconds to check if everything is normal and then starts to charge...

Страница 11: ...25 30 35 1 6 11 16 21 26 31 36 41 46 51 TIME CURRENT VOLTAGE 0 0 5 1 1 5 2 2 5 Ibat Vbat Cell Battery current is controlled in a way to keep stable the power transferred to batteries in direct charge...

Страница 12: ...our display sections on the control panel as follows On the Operation mode section of the display the actual operating mode is seen On the left part of this display section the following messages can...

Страница 13: ...the output voltage is adjustable between values 0 30 0 60 0 140 VDC Iout It is adjustable between 0 255 the current is adjustable between values 0 60 0 30 0 15 A according to the type of Infocharger I...

Страница 14: ...ress between 0 8 Ver Seri no Serial number 5th2 1 2 Buttons There are mainly four buttons in the front panel The functionalities of the buttons are given below button Scroll down to next line button S...

Страница 15: ...n be chosen on the control panel This voltage level can not be less than 1 65V which is the minimum voltage level per cell 2 Delay module This module is designed for the automation processes and has 8...

Страница 16: ...n the unit than you should perform the following Disconnect the loads Bring all the fuses on the unit to 0 position Clean the unit with a slightly moistened cloth Do not drop any liquid and solid fore...

Страница 17: ...se check input fuses If you can read the battery and load voltage on front panel but can not measure the same voltage at battery and load then check the battery and load fuses If there is an over temp...

Страница 18: ...running 90 280 V Input frequency range at mains running 45 Hz 65 Hz Power factor at nominal input voltage 0 99 Current Total Harmonic Distortion THD 3 Efficiency 90 Output Output voltage 24VDC 48VDC...

Страница 19: ...e range at mains running 176 265 V Input frequency range at mains running 45 Hz 65 Hz Power factor at nominal input voltage 0 8 Efficiency 90 OUTPUT Output voltage 24VDC 48VDC 110VDC 220VDC Initial ch...

Страница 20: ...Cable cross section area mm2 Current value absorbed by t he load Amp 1 5 18 4 34 6 44 10 61 16 82 25 108 35 135 50 168 70 207 95 250 120 292 150 335 185 382 240 453 300 504 THESE UNITS ARE GIVEN FOR...

Страница 21: ...I TAFICS RCU ddb BLOCK DIAGRAM 1 1 CHARGE RECTIFIER INF561 Y18 S101 1 00 MAIN CONTROL BOARD DISPLAY DRIVER SUP CONTROL RELAY X4 X403 X404 FAN X101 X101 X401 X403 X101 X102 X103 X205 X206 L L X1 X2 X3...