Installation Manual
| DCPDU2B Series Power Distribution Units
8
+1 (208) 635-6400 | www.transtector.com
7.0 SPECIFICATIONS
The following specifications are typical at 25°C unless otherwise noted.
INPUT/OUTPUT
Panel Capacity
@35°C
.............................................................................. 450A per Bus
@40°C
.............................................................................. 400A per Bus
@50°C
.............................................................................. 320A per Bus
@70°C
.............................................................................. 200A per Bus
Configuration
..................................
450A Single Bus with 1 to 20 Breakers
900A Dual Bus 1 to 10 Breakers Each Bus
Breaker Capacity
1
................................................................. 2.5A to 200A
Voltage
1
.....................................................................................21-60VDC
Polarity ............................................
Neutral, Positive or Negative Ground
ALARMS
Alarm Indicator ....................................................Dual Color LED Per Bus
LED Status Indication ........................................................ Green = Normal
Red = CB Trip Alarm
Off = No Power
Alarm Relays .............................................. Form C Contacts for each Bus
SAFETY
.................... UL60950-1 2
nd
Ed., CSA22.2 No. 60950-1 2
nd
Ed.,
EN60950-1 2
nd
Ed.
ENVIRONMENTAL
Operating Temp. Range
.....................................................
-10°C to +70°C
Storage Temp. Range
........................................................
-40°C to + 85°C
Humidity
........................................................
0% to 95%, Non-Condensing
PHYSICAL SPECIFICATIONS
Case Material
......................................................................................Steel
Finish ............................................................................ Powder Coat Black
Case Dimensions, Inches (mm) ........................
3.45 H x 17.16 W x 5.98 D
(87.6 x 435.9 x 151.9
Weight (approx.)
...........................................................
12.5 lbs. (5.67 kg.)
Rack Mounting
...................................................................... 19 or 23 Inch
CONNECTIONS
Input Connections...........................................................................Bus Bar
Output Connections ...............................................
1/4-20 Stud, 2-hole lugs
Chassis Ground Connection..................................
1/4-20 Stud, 2-hole lugs
Alarm Relay Connections ..................
.Spring Clamp Terminals,16-26AWG
Notes:
1. See ordering guide to specify.
8.0 FRONT PANEL DESCRIPTION
The front panel of the DCPDU2B, shown in Figure 3 below, consists of the A and B sides
and a center section. The A and B sides can each accommodate up to 10 field installed/
replaceable hydraulic magnetic circuit breakers rated from 2.5A to 200A. The center section
has two green/red LEDs, one for the A side (left) and the other for the B side (right). At the
bottom of this center section is a slot for a wallet and designator card. This card permits the
recording of each output circuit by number.
A - ALM
B - ALM
1
2
3
4
5
6
7
8
9
10
A BUS - 450A MAX/100A MAX PER CB
1
2
3
4
5
6
7
8
9
10
B BUS - 450A MAX/100A MAX PER CB
NO-C-NC NO-C-NC
ALM-B
ALM-A
NO-C-NC NO-C-NC
10
9
8
7
6
5
4
3
2
1
0.63
(16.0)
0.76
(19.3)
0.42
(10.7)
0.25
(6.4)
1/4-20 stud
length = 0.50 (12.7),
0.625 (15.88) spacing
1/4-20 stud
length = 0.38 (9.7),
0.625 (15.88) spacing
0.57
(14.5)
0.37
(9.4)
0.90
(22.9)
ø
0.306 (7.8)
0.49 (12.5) x
0.31 (7.9) slot
3.50
(88.9)
1.25
(31.8)
5.98
(151.9)
0.60
(15.2)
17.16
(435.9)
0.76
(19.3)
1.725
(43.82)
0.56
(14.2)
0.21
(5.3)
1.13
(28.7)
0.22
(5.6)
3.45
(87.6)
A - BUS OUTPUT FEED
B - BUS OUTPUT FEED
A - BUS RETURN
B - BUS RETURN
B - BUS FEED BREAKERS
A - BUS FEED BREAKERS
Alarm connector
Chassis GND
(1/4-20 THREAD)
A - BUS INPUT
FEED
B - BUS INPUT
FEED
10
9
8
7
6
5
4
3
2
1
Shorting Bus (-S Models)
OUTLINE OF SAFETY COVER
(blue dotted line)
4.60
(116.8)
0.625
(15.88)
0.500
(12.70)
0.750
(19.05)
4.642
(117.91)
Figure 3. Front Panel View