background image

Installation Manual

 | DCPDU2B Series Power Distribution Units

16

 +1 (208) 635-6400  |  www.transtector.com

12.0  INSTALLING CIRCUIT BREAKERS

The DCPDU2B Series employs pluggable circuit breakers that can be easily installed, removed 

or replaced using the supplied puller tools.  This operation is carried out without the need to 

dismount the unit from it’s installation.
Installation, removal or replacement of a circuit breaker and connection or disconnection of a 

load circuit should be carried out only by only by qualified technical persons who are trained 

in the use of power systems and are well aware of the hazards involved.
Although it may be necessary on some occasions to carry out this operation while power 

remains applied to the panel, it is always preferable to switch off the power if possible before 

proceeding.

12.1   Removing the cover plate.

  To remove the cover plate undo the two knurled retaining 

screws at the left and right side of the unit and pull forward.

12.2   Removing a breaker or blanking panel.

  To remove a breaker pull the toggle switch 

handle using the supplied puller tool until the breaker comes free.  To remove a 

blanking panel lever it out at the top or bottom using a flat bladed screwdriver.

12.3  Installing a breaker or blank panel.

  To insert a breaker carefully push the breaker 

firmly into the socket and make sure that it is fully seated.  To fit a blanking panel use 

the two supplied retaining screws to fit it into position.

 

Repeat the above procedure from 12.2 to 12.3 for all positions and then replace the 

cover plate.

12.4  Conditions for breaker positioning.

  For thermal reasons, when operating the panel 

continuously at the current ratings stated in note (2) on page 15, the circuit breaker 

current shall not exceed the continuous rating as defined in the table.

 

Adjoining gaps on each side of the circuit breaker must be provided for current ratings 

70A to 200A.  None are required for 2.5A to 60A.

Circuit Breaker Gap Requirements

CB Current

Rating

Number

Poles

Max. Continuous 

Load

Adjoining Gap

(each side)

2.5A to 60A

1

80% of CB rating

(70% @ 70°C)

NO

70A to 100A

1

75% of CB rating

(50% @ 70°C)

YES

125A to 200A

2

62.5% of CB rating

(37.5% @ 70°C)

YES

Содержание Transtector DCPDU2B Series

Страница 1: ...Installation Manual 2021 Infinite Electronics Inc Transtector is a registered trademark of Infinite Electronics Inc DCPDU2B M Rev 1 DCPDU2B Series Power Distribution Units...

Страница 2: ...duction Release DR 01 29 21 Contents 1 0 INTRODUCTION 4 2 0 FEATURES 4 3 0 PRODUCT LINE 5 4 0 SAFETY INDUSTRY STANDARDS 6 5 0 WARRANTY summary 6 6 0 DESCRIPTION OF OPERATION 7 7 0 SPECIFICATIONS 8 8 0...

Страница 3: ...Block Diagram 7 Figure 3 Front Panel View 8 Figure 4 Back Panel View 9 Figure 5 Input Bus Bar Detail 9 Figure 6 Output Barrier Strip Detail 10 Figure 7 Alarm Connection Detail 11 Figure 8 Form C Relay...

Страница 4: ...ide up to 20 breakers single bus 450A or 10A 10B 450A 450A distribution and alarm capabilities The A and B sections of the dual bus panel are fully isolated can be separately configured for 24 48 volt...

Страница 5: ...R2B 5 60 DCBKR2B 60 10 DCBKR2B 10 80 DCBKR2B 80 15 DCBKR2B 15 100 DCBKR2B 100 20 DCBKR2B 20 125 2 DCBKR2B 125 25 DCBKR2B 25 150 2 DCBKR2B 150 30 DCBKR2B 30 200 2 DCBKR2B 200 40 DCBKR2B 40 NOTES 1 Brea...

Страница 6: ...ion Panels the chassis ground terminal must be connected to the system frame ground or other proper safety ground for the protection of personnel 4 5 All connections to the Distribution Panels should...

Страница 7: ...HI CURRENT BUS BAR HI CURRENT BUS BAR HI CURRENT BUS BAR HI CURRENT BUS BAR LOADS LOADS 1 2 3 N A SIDE ALARM CIRCUITS B SIDE ALARM CIRCUITS A SIDE B SIDE S OPTION S OPTION 1 2 3 N Figure 2 Block Diag...

Страница 8: ...Clamp Terminals 16 26AWG Notes 1 See ordering guide to specify 8 0 FRONT PANEL DESCRIPTION The front panel of the DCPDU2B shown in Figure 3 below consists of the A and B sides and a center section Th...

Страница 9: ...stud length 0 50 12 7 0 625 15 88 spacing 1 4 20 stud length 0 38 9 7 0 625 15 88 spacing 0 57 14 5 0 90 22 9 0 49 12 5 x 0 31 7 9 slot 3 50 88 9 1 25 31 8 5 98 151 9 0 60 15 2 17 16 435 9 1 725 43 8...

Страница 10: ...ctions use 1 4 20 threaded studs and are rated up to 100 amperes Maximum wire size is 2 AWG Transtector recommends using FLEX wire with either Panduit LCDXN2 14A E or LCDXN2 14AF E 90deg angle lugs Wh...

Страница 11: ...ring clamp terminal blocks J3 is for the Form C relay contact of side B and J4 is for the Form C relay contact of side B Terminals 1 2 and 3 viewed from left to right are the normally open NO common C...

Страница 12: ...37 9 4 0 90 22 9 0 306 7 8 0 49 12 5 x 0 31 7 9 slot 3 50 88 9 1 25 31 8 5 98 151 9 0 60 15 2 0 76 19 3 1 725 43 82 0 56 14 2 0 21 5 3 1 13 28 7 0 22 5 6 3 45 87 6 B B A Chassis GND 1 4 20 THREAD B BU...

Страница 13: ...test the unit The freight carrier should be notified immediately and a claim for the cost of the rectifier system should be filed with the carrier for direct reimbursement Be sure to include the mode...

Страница 14: ...reliably grounded 24VDC to 48VDC SELV source b The branch circuit over current protection shall be sized appropriate to the input current and shall not exceed 600A c Use minimum 350Kmcm copper conduc...

Страница 15: ...and output connections to the load before operating the panel Reverse connections will not harm the distribution panel which is POLARITY NEUTRAL but may cause serious harm to the load Check to make su...

Страница 16: ...a breaker or blanking panel To remove a breaker pull the toggle switch handle using the supplied puller tool until the breaker comes free To remove a blanking panel lever it out at the top or bottom...

Страница 17: ...ting or disconnecting load circuits In cases where a breaker has been installed follow the instructions in section 9 4 to connect the new output wiring Ensure that the breaker is in the OFF position u...

Страница 18: ...e resistance between pins 1 and 2 This should read open Measure the resistance between pins 2 and 3 This should read short 13 5 On the A side trip circuit breaker no 1 The A side LED should turn red O...

Страница 19: ...protection requirements of our customers with responsive customer service technical support and a wide range of quality AC DC and data line surge protection products in stock and available for same da...

Отзывы: