13
1402-001
INSTALLATION (continued)
INPUT AND OUTPUT CONNECTIONS
1. Input connections are made directly to the unit’s 3 pole main input circuit breaker and input ground
lug provided. Note the bottom access wire run route illustrated below.
2. Output connections are made directly to the output breaker(s) and output neutral and ground bus
provided. The load current is not to exceed 80% of the output breaker(s) rating, and not to exceed
the rated total current.
63.000
66.000
TVSS
(MOUNTED TO MID-PANEL)
BYPASS SWITCH
MONITOR ALERT LIGHTS
INPUT BREAKER
(CUSTOMER'S INPUT
CONNECTS TO TOP)
AIR
INLET
FRONT VIEW
80A
400V
OUTPUT
BREAKER
60A
400V
OUTPUT
BREAKER
TVSS
BREAKER
167.64 cm
160.02 cm
NEUTRAL & GROUND OUTPUT
TERMINALS CONSIST OF
PK9 GROUNDING BAR
WIRE: 14 AWG. - 4 AWG.
& TA 2/0 LUG
WIRE: 14 AWG - 2/0 (2.5mm
2
- 50mm
2
)
(2.5mm
2
- 25mm
2
)
Содержание Transtector 700 A/VS Series