Function Menu Description 

Press and hold the SET button for 3 seconds and release it to enter the function menu interface (F01-F09). Press the + and - buttons to switch in  

between menus. Select the menu and click the SET button to enter the setting state. The display starts flashing. Set the data with + and - keys, long 

press the SET key to automatically save the data and exit. It will return to the original current interface. If the selected function is wrong, user can click 

the ESC key to return to the function menu selection interface to re-select. 
For details of the function menu interface, see the following table: 

Note

: If user do not want to use a particular function, kindly set the parameter to 000 to close the particular function. 

Function Menu 

Number 

Menu Feature Description 

 F01 

Current upper limit setting: (Range: lower limit ~ range): When the lower limit function is closed, the range is: > 0 ~ range. 
After setting the parameter, if the detected current exceeds the parameter, the relay on the module will act (pull in). 

 F02 

Current lower limit setting: (Range: > 0 ~ upper limit): When the upper limit function is closed, the range is: > 0 ~ range. 
After setting the parameter, if the detected current is lower than the parameter, the relay on the module will act (pull in). 

 F03 

Power-on delay time setting: (Range: 0.01S ~ 99.9S) 
Power-on delay means, after the module is powered ON, the module does not do any checks within the delay time. It is mainly used 

to avoid the instantaneous flow of current of the device when the module and the device under test are powered ON at the same 

time, causing the relay to act (pull-in). 

 F04 

Delay protection time setting: (Range: 0.01S ~ 99.9S) 
Delay protection means that after the current detected by the module exceeds the set current value and the duration exceeds the 

set time, the module relay will act (pull in). 

F05 

Delay recovery time setting: (Range: 0.01S ~ 99.9S) 
Delay recovery means that the current detected by the module exceeds the set current value. After the relay acts (closes) and the 

current returns to normal, the relay does not releases immediately, but continues to attract until the set time and then the relay  

releases. 
An extended function is added to this function: When this time is set to OFF, after the relay acts, it will not recover by itself, and it 

needs to be recovered manually. 
OFF setting method: After entering the setting interface of this function menu, click the SET button to move the blinking cursor to the 

highest position, and keep pressing the + button until OFF is displayed. Press and hold the SET button to save and exit. 
When the relay on the module operates, regardless of the current, the relay does not releases automatically. The relay state can 

only be restored manually. 
OFF closing method: After entering the function menu setting interface, directly press the - key to display 99.9, and then use the 

SET key to change positions and +/- keys to set the required time. 
Manually restore the setting: When the detection current returns to normal, press and hold the ESC key. The relay can return to its 

initial state. 

F06 

Transformer winding turns setting: Default: 001 
In the actual use process, if the current line is passed through the transformer for 2 turns, the current of 1 A will be displayed as 2 A. 

At this time, when the parameter is set to 2, the display shows the actual current of 1 A. 

Note:

 This parameter can only be used when the transformer is threaded, the number of the parameter should be set the 

same with the number of the turns threaded. 

 F07 

Range display: Used to display the maximum current range of the module. 

Note:

 This parameter cannot be changed by the user at will. Otherwise, it will cause test errors. 

 F08 

Relay action record: This item saves the current value of the last action of the relay on the module. It is only for viewing and cannot 

be set. 

 F09 

ID display: This function is only used when the module has RS485 output. User can check the module ID through this function or 

user can directly set the ID through the + and - keys on the function interface. No need to connect to a computer. 

Key Function Description

 

SET key 

Press and hold 3S to enter the function menu interface. After selecting, click this key to enter the setting interface. After entering 

the setting interface, click this key to perform the cursor transposition operation. After the setting is completed, press and hold for 

3S to automatically save the data and exit. 

+ Key 

Used after entering the function menu or function setting interface. 

- Key 

Used after entering the function menu or function setting interface. 

ESC key 

After performing the wrong operation, click this key to return to the previous menu immediately, and the data will not be saved.  

In the relay manual recovery mode: after the current returns to normal, long press this key to restore the initial state of the relay. 

RS485 Modbus - RTU Protocol 

The protocol adopts the standard Modbus-RTU protocol, only open 03 and 06 function codes, all commands and replies are in Hex (hexadecimal) 

format. Factory ID default: 01 
The CRC check is calculated in reverse order of A001 or 8005, and the calculation code is shown in the attachment. 
The communication setting format is as follows: 

Baud rate 

Data bits 

Check bits 

Stop bits 

9600 (default) 

8 bits 

None 

1 bit 