background image

Step 2 – Determine Buoyancy Control Method

Step 2 is used if the Step 1 analysis shows that buoyancy control is required for the tank model and installation conditions. The site-specific maximum 

height of water outside of the tank and above the tank bottom and the depth of soil cover above the tank top must be known to complete Step 2.

Table 2 Instructions

For the appropriate tank model, select the desired buoyancy control method under each method description column. Refer to the Compatible Devices and 

Products and Step 3 – Implementation sections of this document for additional information on the buoyancy control methods shown in Table 2.

Supplemental Force

The minimum supplemental downward force required is included in Table 2 to allow custom buoyancy control methods. These values include a factor 

of safety of 1.5 applied to the calculated force required to restrain the tank. Custom-designed buoyancy control methods shall conservatively consider 

saturated conditions from the bottom-of-tank elevation to ground surface. As long as buoyancy control is provided that supplies the minimum weight listed 

in the table (for poured-concrete blocks or other methods designed by third parties), the tanks are calculated to be stable for the water height outside 

the tank and above the tank bottom and corresponding soil cover conditions. All Infiltrator strapping and fastening recommendations apply for custom-

designed buoyancy control methods. Contact Infiltrator’s Technical Services Department with any questions regarding supplemental force requirements.

Table 2: Buoyancy Control Method Selection

Tank 

Model

Parameter I:

Water height above tank bottom

Parameter II:

Soil cover depth above 

tank top

Minimum 

supplemental 

downward  

force required

1

(total, both tank 

sides)

Buoyancy Control Methods

Concrete-filled  

half pipe 

(min. length/

side)

Concrete 

parking 

bumpers  

(min. length/

side)

Concrete 

traffic 

barriers  

(min. length/

side)

Helical 

anchors 

(min. 

no./side)

Concrete collar  

(min. width x min. 

height)

IM-540

36 in (900 mm) to outlet pipe saddle

2

6 in (150 mm) to 12 in (300 mm) 2,200 lbs (1,000 kg)

3.8 ft (1.2 m)

3.8 ft (1.2 m)

3.8 ft (1.2 m)

2

 6 in (150 mm) 

x 9 in (225 mm)

IM-1060 36 in (900 mm) to outlet pipe saddle

2

6 in (150 mm) to 12 in (300 mm) 2,700 lbs (1,225 kg)

4.2 ft (1.3 m)

4.5 ft (1.4 m)

4.2 ft (1.3 m)

2

 12 in (300 mm) 

x 9 in (225 mm)

IM-1530 30 in (750 mm) to outlet pipe saddle

2

6 in (150 mm) to 12 in (300 mm) 4,300 lbs (1,955 kg)

6.3 ft (2.0 m)

6.5 ft (2.0 m)

6.3 ft (2.0 m)

2

 12 in (300 mm) 

x 9 in (225 mm)

NOTES:

1. See Supplemental Force discussion below.

2. IM-Series outlet pipe saddle height is 43 inches (1,075 mm) above tank bottom (see Figure 1).

Contact Infiltrator Water Technologies’ Technical Services Department for assistance at 1-800-221-4436.

Содержание IM -Series

Страница 1: ...gh elevation of the main water table The vertical position of the tank must account for both the seasonal high groundwater table and any existing or future perched water table condition Verify that the subsurface water elevation will not exceed the height of the outlet pipe saddle of the tank as shown in Figure 1 and described in Table 1 Table 1 Instructions 1 In the left hand column of Table 1 lo...

Страница 2: ... outside the tank and above the tank bottom and corresponding soil cover conditions All Infiltrator strapping and fastening recommendations apply for custom designed buoyancy control methods Contact Infiltrator s Technical Services Department with any questions regarding supplemental force requirements Table 2 Buoyancy Control Method Selection Tank Model Parameter I Water height above tank bottom ...

Страница 3: ...requirements for use as buoyancy control see Table 2 and the Supplemental Force section of Step 2 for more information Helical Anchors Chance No Wrench Screw Anchors with a 6 inch 150 mm diameter flight Class 7 or equal These anchors rely on the shear strength of the soil combined with the weight of the soil above the anchor flight to provide holding strength Proper installation is to 4 feet 1 2 m...

Страница 4: ...uoyancy control methods described herein are recommendations only consult a professional engineer for customized designs if desired Parts and Supplies The parts and supplies necessary are to be purchased separately from the tank All parts and supplies are either commercially available or available through Infiltrator s network of tank distributors Some parts may require fabrication on site using c...

Отзывы: